Benutzeranleitung / Produktwartung GEN16AD-E des Produzenten Rheem
Zur Seite of 40
Questions? Help is just a moment away! Call: Generator Helpline 877-369-9400 Monday-Friday 8:00 AM to 5:00 PM Central Time Generator Systems Installation Manual GEN20AD-E GEN16AD-E GEN15ADC-E.
Thank you for purchasing this quality-built Rheem / Ruud standby generator. We are pleased that you’ve placed your confidence in the Rheem or Ruud brand. When operated and maintained according to the instructions in this manual, your Rheem / Ruud generator will provide many years of dependable service.
3 Table of Contents Important Safety Instructions ........................ 4 Installation .................................... 7 Owner Responsibilities ......................................... 7 Installing Dealer/Contractor Responsibilities .........
4 Save These Instructions WARNING Running engine gives off carbon monoxide, an odorless, colorless, poison gas. Breathing carbon monoxide could result in death, serious injury, headache, fatigue, dizziness, vomiting, confusion, seizures, nausea or fainting.
5 WARNING Generator produces hazardous voltage. Failure to properly ground generator could result in electrocution. Failure to isolate generator from utility power could result in death or serious injury to electric utility workers due to backfeed of electrical energy.
6 WARNING Starter and other rotating parts could entangle hands, hair, clothing, or accessories resulting in serious injury. t NEVER operate generator without protective housings, covers, or guards in place. t DO NOT wear loose clothing, jewelry or anything that could be caught in the starter or other rotating parts.
7 Installation Equipment Description This product is only for use as an optional generator system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience.
8 Unpacking Precautions The unit is shipped ready for installation. Avoid damage from dropping, bumping, collision, etc. Store and unpack carton with the proper side up, as noted on the shipping carton. Delivery Inspection After removing the carton, carefully inspect the generator for any damage that may have occurred during shipment.
9 Installation Checklist Carbon Monoxide (CO) Detector Carbon Monoxide (CO) detector installed and in working order . Smoke detector(s) installed and in working order . Placement Required permits have been obtained. Generator placed in an area free from Carbon Monoxide (CO) buildup.
10 Intentionally Left Blank.
11 Generator Placement Before installing generator, consult with home owner and convey the following requirements, which must be satisfied before the installation is complete. There are two equally important safety concerns in regards to carbon monoxide poisoning and fire.
12 All fossil fuel burning equipment, such as standby generators, contains carbon monoxide (CO) gas in the engine exhaust. CO gas is odorless, colorless and tasteless and is unlikely to be noticed until a person is overcome.
13 t %JSFDU UIFTUBOECZ HFOFSBUPS FYIBVTU BXBZ GSPN PS parallel to the building or structure. DO NOT direct the generator exhaust towards a potentially occupied building,.
14 Placement of Standby Generator to REDUCE THE RISK OF FIRE Requirements: NFP A 37 2010, section 4. 1. 4, Engines Located Outdoors. Engines, and their weatherproof housings if provided, that are installed outdoors shall be located at least 1.5m (5 ft) from openings in walls and at least 1.
15 A Standby weatherproof enclosure must be at least 5 ft (1.5 m) from windows, doors, any wall opening, shrubs or vegetation over 12 inches (30.5 cm) in height. B Exhaust outlet side of weatherproof enclosure must have at least 5 ft (1.5 m) minimum clearance from any structure, shrubs, trees or any kind of vegetation.
16 Electrical and Fuel Inlet Locations The 3/4 inch N.P .T . fuel inlet connector ( A ) and electrical inlet location ( B ) is shown below . A ½ inch knock-out is provided for the electrical inlet. This inlet may be enlarged or supplemented to accommodate a maximum conduit size of 1 ½ inches.
17 Lifting the Generator The generator weighs more than 500 pounds (227 kg). Proper tools, equipment and qualified personnel should be used in all phases of handling and moving the generator .
18 Access Ports The generator is equipped with an enclosure that has several access panels, as shown. The access panels and the components located behind them are listed below: A - Roof (Control Panel.
19 To open roof: 1. Insert key into lock ( A ) of front panel. Gently push down on roof above the lock to aid in turning the key. Turn key one quarter turn clockwise. 2. Lift roof to the open position. To remove front panel: 1. Remove the two bolts ( B ) that secure the panel to the unit.
20 The Gaseous Fuel System The information below is provided to assist gaseous fuel system technicians in planning installations. In no way should this information be interpreted to override applicable fuel gas codes. Consult with your local fuel supplier or Fire Marshall if questions or problems arise.
21 Fuel Consumption Estimated fuel supply requirements at half and full load for natural gas and LP vapor fuels are shown below. LP Vapor (Propane) 20kW 17kW 15kW Full Load Cu Ft/Hr 135 118 109 Gal/Hr (liquid) 3.75 3.28 3.03 BTU/Hr 337500 295000 272500 3/4 Load Cu Ft/Hr 109 99 90 Gal/Hr (liquid) 3.
22 Fuel Conversion The engine of your generator system is factory calibrated to run on natural gas (NG) or on liquefied petroleum (LP) vapor. To convert to either fuel, follow these steps: NOTICE Units are set to NG at the factory. 1. Insert key into lock of front panel.
23 System Connectors Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself with the location of these connections.
24 Generator AC Connection System A single-phase, three-wire AC connection system is used in the home generator. The stator assembly consists of a pair of stationary windings with two leads brought out of each winding. The junction of leads 22 and 33 forms the neutral lead, as shown schematically and as a wiring diagram.
25 Grounding the Generator The home generator must be installed as part of a system that includes a listed transfer switch, with neutral to ground bonding at the transfer switch in accordance with installation instructions. Unless mandated by local code, additional grounding to earth at the generator is not required.
26 System Control Panel The generator control panel, located inside the generator housing, is shown below. Brief descriptions of the controls used during installation are: The generator control board, located inside the generator, under the roof, is shown below.
27 Menu MENU ENTER THE MENU (VIEW SETTINGS) PRESS TO CONFIRM SELECTION WHEN PROGRAMMING. ESCAPE (EXIT) RETURN TO LAST MENU ITEM RIGHT ARROW TOGGLE THROUGH MENU OPTIONS SETTING SYSTEM PARAMETERS LEFT ARROW TOGGLE THROUGH MENU OPTIONS SETTING SYSTEM PARAMETERS MANUAL MODE USED TO MANUALLY START THE GENERATOR.
28 NOTE: Date and T ime were set at the fac tory and stored in the control panel memor y . The Exercise C ycle was also set at the factor y . Th e default exercise cycle occurs on T u esdays, at 2 : 00 P .M. Central Standard Time . To updated or change these settings, follow the steps belo w.
29 A UT OMA TIC MODE GENERA TOR ON (When Gener ator R unning - Aut o Mode) GENERA TOR READ Y or SERVICE CODE DESCRIPTION (When Gener ator NO T Running - Auto Mode) Control Panel Prompts Automatic Mode.
30 Advanced Settings Screen kW kW FLASHING 50/60 Hz FLASHING Hz PHASE VO LTS SOFTW ARE Ver sion Displayed VO LTS FLASHING SINGLE or THREE FLASHING E-Gov ernor Check Stepper Motor will sweep thr ough t.
31 Final Installation Considerations Engine Oil NOTICE Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure. t Refer to Maintenance in the operator’ s manual for oil fill information.
32 Initial Start-up (No Load) The unit has been set-up for NG operation at the factory. Fuel conversion, if needed, must be completed prior to performing these steps. See Fuel Conversion . Before operating the home generator or placing it into service, inspect the entire installation carefully.
33 Electronic Governor System The engine electronic governor system allows for improved control and increased generator performance compared to mechanically governed systems. The result is smooth TUFBEZTUBUF PQFSBUJPO XJUIPVU UIFiIVOUJOHw DPNNPO UP many mechanical governors.
34 Operation Automatic Operation Sequence The generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset level, the control board will signal the engine to crank and start. When utility voltage is restored above a preset voltage level, the engine is signaled to shut down.
35 Antenna Installation The supplied antenna must be installed before the wireless monitor will operate. 1. Insert key into lock of front panel. Gently push down on roof above the lock to aid in turning the key. Turn key one quarter turn clockwise. 2.
36 Wireless Monitor The generator is supplied with a battery-powered, wireless monitor. The monitor communicates wirelessly with the generator control panel.
37 Wireless Monitor Operation 1. Remove battery access cover ( A ) on back of monitor and install 2 AA batteries. (Observe correct battery polarity which is embossed in the bottom of the battery compartment). Replace battery access cover. NOTICE The wireless monitor was linked to the generator at the factory.
38 Standard Operation: Wireless Monitor Status LED’s t 5IFXJSFMFTT NPOJUPS SFDFJWFT EBUB GSPN UIF HFOFSBUPS every 10 minutes and displays the generator status through 3 LED’s. t 1SFTTJOH UIF SYSTEM UPDATE button will provide current generator status by flashing the status LED’s.
39 Schematic Diagram Schematic / Wiring Diagrams LEGEND BW - Plug for Option a l B a t tery W a rmer CB - Ci rcuit Bre a ker CMA - Control Module Assembly COM - Common EW - Plug for Option a l Engin e Oil W a rmer FS - Fuel Solenoid GND - Ground IS - Idle Solenoid LOP - Low Oil Pressure Switch (Closes on Low Press ure) N.
40 LEGEND BW - Plug for Option a l B a ttery W a rmer CB - Circuit Bre a ker CMA - Control Module Assembly COM - Common EW - Plug for Option a l Engine Oil W a rmer FS - Fuel Solenoid GND - Ground IS - Idle Solenoid LOP - Low Oil Pressure Switch (Closes on Low Pressure) N.
Ein wichtiger Punkt beim Kauf des Geräts Rheem GEN16AD-E (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Rheem GEN16AD-E noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Rheem GEN16AD-E - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Rheem GEN16AD-E reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Rheem GEN16AD-E erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Rheem GEN16AD-E besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Rheem GEN16AD-E verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Rheem GEN16AD-E. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Rheem GEN16AD-E gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.