DIGIT AL TEMPERA TURE CONTR OLLERS SERIES O TC25 N/L/P Instruction Manual.
Congratulations on your purchase of an Athena Series OTC25 Digital T emperature Controller . It is designed for ease of use and reliability wherever accurate temperature control is required. After following the instructions for installation, simply step through and set each of the unit’ s parameters using the OTC25’ s easy menu system.
T able of Contents Installation 1 Mounting 1 Wiring 2 Operation 2 OTC25 N On/Off Controller 4 OTC25 L Limit Controller 5 OTC25 P PID Controller 7 Calibration 10 Error Codes 11 IEC Requirements 11 W ar.
1 Installation Pre-Installation Instructions 1. Inspect shipping carton for obvious signs of mishandling. 2. After removing the controller from the shipping carton, inspect it carefully for damage.
2 Operation Athena Series OTC25 Digital T emperature Controller Just a few easy steps are required before your OTC25 can be placed into service. After completing the mounting and wiring procedures as previously instructed, set each controller parameter using the simple front-panel keys as instructed.
O TC25 N Operation F igure 5a. Series O TC25 N Parameters and Default Settings Parameter Descriptions Default Display This parameter determines whether the OTC25 N’ s display shows the Setpoint or the actual temperature by default.
O TC25 N Operation The Calibration High and Calibration Low selections ar e accessi- ble only when the calibration jumper is installed as instructed on page 10 (F igure 6). OTC25 N On/Off T emperature Controller Normal Operation The factory default display setting of the OTC25 N is for Actual Te mperature .
5 O TC25 L Operation OTC25 L Limit Controller Normal Operation The factory default display setting of the OTC25 L is for Actual Te mperature . The default display may be changed to setpoint temperature by selecting Limit Setpoint at the Default Display parameter selection.
6 O TC25 L Operation Parameter Descriptions Default Display This parameter determines whether the OTC25 L ’ s display shows the Limit Setpoint or the actual temperature by default. Regardless of the selection made here, the operator can observe the other value by momentarily pressing the Parameter Key .
7 O TC25 P Operation OTC25 P PID T emperature Controller Normal Operation The factory default display setting of the OTC25 P is for Actual Te mperature . The default display may be changed to setpoint temperature by selecting Setpoint at the Default Display parameter selection.
F igure 5c. Series O TC25 P Parameters and Default Settings Parameter Descriptions Default Display This parameter determines whether the OTC25 P’ s display shows the Setpoint or the actual temperature by default. Regardless of the selection made here, the operator can observe the other value by momentarily pressing the Parameter Key .
O TC25 P Operation Proportional Band Proportional Band is a PID parameter that represents the amount of deviation of the controlled variable required to move through the full range, expressed in % of span or degrees of temperature. This para- meter can also be expressed as “Gain” (the wider the band, the lower the gain).
10 Calibration Procedure 1. Prior to applying power to the unit, install the calibration jumper on the microprocessor board as shown in Figure 6. 2. With the instrument still unpowered, connect a calibration reference source to the thermocouple input terminals on the OTC25.
The maximum supply current is line voltage dependent: 60 mA for an 100-250 Vac input fuse rating: 2AG, 0.5 A Output Specifications Output 1 T ype Max current Voltage Leakage T (T riac) 2 A 400 Vpk 1 mA B (Relay) 5 A 380 V — Output 2 T ype Max current Voltage Leakage T (SSR) 0.
12 W arranty/Repair Inf ormation T wo-Y ear Limited Warranty THIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS OF MA TERIAL AND WORKMANSHIP . IT IS SOLD SUBJECT TO OUR MUTUAL AGREEMENT THA T THE LIA.
13 W arranty/Repair Inf ormation Unit Repairs It is recommended that units requiring service be returned to an authorized service center . Before a controller is returned for ser- vice, please consult the service center nearest you. In many cases, the problem can be cleared up over the telephone.
14 Mechanical Characteristics Display 7-segment LED, alphanumeric: 3 digits Display Height 0.56" (14.22 mm) Color Orange Front-Panel Cutout 3.622" x 3.622" (92 mm x 92 mm) Bezel Outside Dimensions 3.780" x 3.780" (96 mm x 96 mm) Bezel Height 0.
15 T echnical Specif ications Input Source (T emperature Sensor) Thermocouple Range: T ype J OTC25 N/L: 6 to 926° F (-14 to 496° C) OTC25 P: 32 to 999° F (0 to 537° C) T ype K OTC25 N/L: N/A OTC25.
16 NO TES.
17 Keep This Information in a Safe Place Configured Parameters Reference Information Series OTC25 T emperature Controller Model Number: _____________________ Zone Location: _____________________ Firmware V ersion No. : _______________ (Displayed when the controller is powered up after all the segments on both lines of the display have been tested).
18 NO TES.
19 Keep This Information in a Safe Place Configured Parameters Reference Information Series OTC25 T emperature Controller Model Number: _____________________ Zone Location: _____________________ Firmware V ersion No. : _______________ (Displayed when the controller is powered up after all the segments on both lines of the display have been tested).
20 NO TES.
For technical assistance, call toll free 1-800-782-6776 (in the U .S.) or 610-828- 2490 (fr om an ywhere in the w orld), or e-mail techsupport@athenacontrols.com. Athena Controls, Inc. 5145 Campus Drive Plymouth Meeting, P A 19462 USA T oll-free: 800.
Ein wichtiger Punkt beim Kauf des Geräts Athena Technologies L (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Athena Technologies L noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Athena Technologies L - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Athena Technologies L reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Athena Technologies L erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Athena Technologies L besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Athena Technologies L verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Athena Technologies L. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Athena Technologies L gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.