Page 1 of 2 2' x 2' Recessed Fluorescent, High Performance Louver Static or Air Supply/Return, 2 Lamp T8 or 2U

G
exposed T-grid ceiling. T
exposed slot T-grid ceiling.



1/4" max.
1-1/2" max. 1-7/8" max.
9/16", 15/16" or 1" 24"
drywall kit.

Air supply slots (GOA only)
Drywall Kit (See Options)
2" x 2-1/2" access plate with two K.O.s (7/8" dia.) Order Catalog Number: FK92X4.
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:

Page 2 of 2 2' x 2' Recessed Fluorescent, High Performance Louver Static or Air Supply/Return, 2 Lamp T8 or 2U
Model No. GOS2G217UNVC2 LER = FP - 65.5 IW - 30.28 BF - 0.88 Comparative yearly lighting energy cost per
Model No. GOS2G22UUNVC5 LER = FP - 73.9 IW - 46.0 BF - 0.77 Comparative yearly lighting energy cost per
1000 lumens = $3.66 Report Number: G2008145 Catalog Number: GOS2G217UNVC2 Lamp: (2) F17/TL835/ALTO/PLUS Luminaire: GO2 2'X2' with 6 cell louver. Ballast: Advance IOP-2P-32-SC Report is based on 1400 Lumens per lamp. Efficiency: 80.5% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.7 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 21.000 21.000
1000 lumens = $3.25? Report Number: G2008126 Catalog Number: GOS2G22UUNVC5 Lamp: (2) FBO/835XP/ECO Luminaire: GO2 2'X2' with 6 cell louver. Ballast: Advance IOP-2P-32-LW-SC Report is based on 2775 Lumens per lamp. Efficiency: 79.5% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.1 1.6 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 21.000 21.000


0.0 45.0 90.0 FLUX
0 755 755 755
0 1646 1646 1646
5 761 765 768 73
5 1644 1691 1720 162
15 719 825 950 236
15 1528 1721 1814 481
25 640 915 1094 408
25 1341 1628 1864 750
35 536 857 979 503
35 1111 1477 1833 925
45 403 663 657 466
45 838 1239 1355 899
55 271 383 283 307
55 561 779 775 651
65 157 153 106 149
65 322 359 202 318
75 80 86 75 85
75 165 172 156 174
85 22 24 21 26
85 46 47 47 53
90 3 3 2
90 8 7 4
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.200
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.200
ZONAL LUMEN SUMMARY
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
ZONE LUMENS % LAMP % FIXT 00-030 717 25.6 31.8 00-040 1220 43.6 54.2 00-060 1993 71.2 88.4 00-090 2253 80.5 100.0 90-180 0000 0.0 000.0 00-180 2253 80.5 100.0
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
ZONE LUMENS % LAMP % FIXT 00-030 1391 25.1 31.6 00-040 2317 41.8 52.5 00-060 3867 69.7 87.7 00-090 4411 79.5 100.0 90-180 0000 0.0 000.0 00-180 4411 79.5 100.0
1 89 85 82 80 78 76 77 75 74 2 82 76 71 71 68 64 69 66 63 3 75 67 61 64 59 55 62 58 54 4 69 60 52 57 52 48 55 51 47 5 64 54 47 52 46 42 50 45 41 6 59 49 42 47 41 37 46 40 37 7 55 45 38 43 37 33 42 36 33 8 51 41 34 39 33 29 38 33 29 9 48 37 31 36 30 27 35 30 26 10 45 34 28 33 28 24 33 27 24
1 88 84 81 79 77 75 76 74 72 2 80 75 70 70 66 63 68 65 62 3 74 66 60 63 58 54 61 57 53 4 68 59 53 56 51 47 54 50 46 5 63 53 47 51 45 41 49 44 41 6 58 48 41 46 40 36 45 40 36 7 54 44 37 42 36 32 41 36 32 8 50 40 34 38 33 29 37 32 29 9 47 37 30 35 30 26 35 30 26 10 44 34 28 33 27 24 32 27 24
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 2002. 3294. 3265. 55 1660. 2346. 1734. 65 1305. 1272. 881. 75 1086. 1167. 1018. 85 887. 968. 847.
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 4164. 6156. 6733. 55 3436. 4772. 4747. 65 2677. 2985. 1679. 75 2240. 2335. 2118. 85 1854. 1895. 1895.
(lay-in T bar) T= Slot grid or
two-directional concealed T (see options)
Lamp Type/ Fixture Length:
Ballast Type:
17= 2' T8 2U= 2' U T8 (Nominal 24") GO Standard GO2
Ballast
GN For NYC Code – Local 3 Manufactured
Options/Accessories Plaster Frame: Catalog Number: PF22. Radio Interference Filter: To order one RIF per fixture; SUFFIX: R.
Specifications (continued) Materials: Chassis parts are die-formed code gauge cold rolled steel. Side rails hemmed over and housing ends turned-in for safe handling. Reflector is 94% reflective aluminum. Finish: Chassis exterior–black baked polyester enamel. Cavity–white baked polyester enamel. Rust preven- tative undercoating. Louver–94% reflective flat white powder coat. Electrical: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. Labels: I.B.E.W. UL and ULc Listed. This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org
To order one RIF per ballast; SUFFIX: B. Fusing: Internal fast-blow fusing. SUFFIX A. Internal slow-blow fusing. SUFFIX C. Electrical Wiring Options: Consult factory. Air Closure Strip: SUFFIX: ACS4 (factory installed). Drywall Kit: Order Catalog Number: FK92X2. (Request Folio OA30-10 Rev. A). Chicago Plenum: SUFFIX: C.
Specifications Performance: In an installation of 2 lamp T8U luminaries in a room cavity ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .84. Air Handling (GOA only) side air passages for air supply or air return. Optional side closure strips. Air return is also provided through the lamp compartment through fixture body ends.