Benutzeranleitung / Produktwartung OM5-C des Produzenten Omega Engineering
Zur Seite of 56
.
OMEGAnet SM On-Line Service http://www.omega.com Internet e-mail info@omega.com Servicing North America: USA: One Omega Drive, Box 4047 Stamford, CT 06907-0047 Tel: (203) 359-1660 e-mail: info@omega.com FAX: (203) 359-7700 Canada: 976 Berger Laval (Quebec) H7L 5A1 Tel: (514) 856-6928 e-mail: canada@omega.
1 GENERAL DESCRIPTION ............................................................................................................ .. 2 OM5 SELECTION GUIDE ...............................................................................................
22 OM5-WMV/WV Analog V oltage Input Modules, Wide Bandwidth FEA TURES ● ACCEPTS MILLIVOLT AND VOLTAGE LEVEL SIGNALS ● HIGH LEVEL VOLTAGE OUTPUTS ● 1500Vrms TRANSFORMER ISOLATION ● ANSI/IEEE C37.90.1-1989 TRANSIENT PROTECTION ● INPUT PROTECTED TO 240VAC CONTINUOUS ● 100dB CMR ● 10kHz SIGNAL BANDWIDTH ● ± 0.
23 Module OM5-WMV OM5-WV Input Range ± 10mV to ± 100mV ± 1V to ± 40V Input Bias Current ± 0.5nA ± 0.05nA Input Resistance Normal 200M Ω 650k Ω (minimum) Power Off 40k Ω 650k Ω (minimum) Overload 40k Ω 650k Ω (minimum) Input Protection Continuous 240Vrms Max * Transient ANSI/IEEE C37.
24 OM5-TX 2-Wire T ransmitter Interface Modules ter. This allows a 2-wire loop powered transmitter to be directly connected to the module without requiring an external power supply. The regulated supply will provide a nominal +20VDC at a loop current of 4mA to 20mA.
25 SPECIFICA TIONS Typical at T A = +25 ° C and +5V power . ORDERING INFORMA TION MODEL I NPUT RANGE OUTPUT RANGE OM5-TX-1-C 4mA to 20mA +1V to +5V OM5-TX-2-C 4mA to 20mA +2V to +10V NOTES: (1) Includes nonlinearity, hysteresis and repeatability. (2) RTI = Referenced to input.
26 OM5-DT General Purpose Input Modules, with DC Excitation controlled, which allows these modules to share a common analog bus without the requirement of external multiplexers. The modules are designed with a completely isolated computer side circuit which can be floated to ± 50V from Power Common, pin 16.
27 Module OM5-DT Input Range ± 1V to ± 10V Input Bias Current ± 0.05nA Input Resistance Normal 2M Ω (minimum) Power Off 2M Ω (minimum) Overload 2M Ω (minimum) Input Protection Continuous 240Vrms max Transient ANSI/IEEE C37.90.1-1989 (formerly IEEE-472) Excitation Voltage, V EXC +10.
28 OM5-IFI Frequency Input Modules FEA TURES ● ACCEPTS FREQUENCY INPUTS OF 0 to 100kHz ● PROVIDES HIGH LEVEL VOLTAGE OUTPUTS ● TTL LEVEL INPUTS ● 1500 VOLT TRANSFORMER ISOLATION ● ANSI/IEEE C37.90.1-1989 TRANSIENT PROTECTION ● INPUT PROTECTED TO 240VAC CONTINUOUS ● ± 0.
29 Module OM5-IFI Input Range 0 to 100KHz Input Threshold Zero Crossing Minimum Input 60mVp-p Maximum Input 350Vp-p Minimum Pulse Width 4 µ s TTL Input Low 0.
30 OM5-L TC Linearized Thermocouple Input Modules FEA TURES ● INTERFACES TO TYPES J, K, T, E, R, S, N, AND B THERMOCOUPLES ● LINEARIZES THERMOCOUPLE SIGNAL ● HIGH LEVEL VOLTAGE OUTPUTS ● 1500Vrms TRANSFORMER ISOLATION ● ANSI/IEEE C37.
31 SPECIFICA TIONS Typical at T A = +25 ° C and +5V power . Module OM5-LTC Input Range –0.1V to +0.5V Input Bias Current –25nA Input Resistance Normal 50M Ω Power Off 40k Ω Overload 40k Ω Input Protection Continuous 240Vrms max Transient ANSI/IEEE C37.
32 FEA TURES ● ACCEPTS HIGH LEVEL VOLTAGE INPUTS TO ± 10V ● PROVIDES HIGH LEVEL VOLTAGE OUTPUTS TO ± 10V ● 1500 VOLT TRANSFORMER ISOLATION ● ANSI/IEEE C37.90.1e-1989 TRANSIENT PROTECTION ● 5 POLES OF FILTERING ● 110dB CMR ● 400Hz SIGNAL BANDWIDTH ● ± 0.
33 Module OM5-AV Input Voltage Range ± 5V, 0 to +5V, ± 10V, 0 to +10V Input Voltage Maximum ± 36V (no damage) Input Resistance 50M Ω Output Voltage Range ± 5V, 0 to +5V, ± 10V, 0 to +10V Over Range Capability 5% @ 10V output Output Drive 50mA max Output Resistance 0.
34 number 50865-5. The captive nut for the 3mm mounting screw can be obtained from PEM (Penn Engineering and Manufacturing), part number KFS2-M3. The following mechanical drawing is useful if designing circuit boards to mount the OM5 modules. Many sockets are available which accept the mounting pins.
35 Accessories for OM5 Analog Modules FEA TURES ● SINGLE, DUAL, 8-, AND 16-POSITION BACKPANELS ● DIN RAIL MOUNT BACKPANELS ● 19-INCH MOUNTING RACK FOR BACKPANELS ● MULTIPLEXED AND NON-MULTIPLE.
36 FIGURE 2. OM5-BP-16-C Schematic. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 6 4 2 5 3 1 –EXC +EXC –In +In TB1 TB17 PCOM LED +In +EXC +SEN OMX-1362-C OMX-CJC-C –In –EXC –SEN Channel 1 12 3 4 Fuse (4A) F1 PCOM +5 +5 DZ1 5.
37 ELECTRICAL P1 AND P2 CONNECTOR Connection to the host system is made at connectors P1 and P2. These connectors are electrically equivalent. Two connectors are provided to allow both analog input and analog output from host systems having individual input and output connectors.
38 DESCRIPTION The OM5-BP-16-MUX-C 16 channel backpanel (Figure 5) can accept any of the OM5 analog modules in any mixture. It can be mounted on the OMX-1363-C 19-inch metal rack. The OM5-BP-16-MUX-C has two analog buses; one for analog input and one for analog output.
39 FIGURE 6. OM5-BP-16-MUX-C Schematic. SCM5B 22 20 18 16 6 4 2 5 3 1 23 21 19 17 PCOM I/O COM –EXC +EXC –In +In +5 TB1 TB17 PCOM RD EN V OUT V IN +In +EXC +SEN –In –EXC –SEN Channel 1 WR EN.
40 ELECTRICAL P1 CONNECTOR The 26 pin P1 connector provides the signal interface between the OM5-BP- 16-MUX-C backpanel and the host measurement system. Two separate analog bus connections are provided; one for analog input signals and one for analog output signals.
41 OM5-BP-SKT -C /-2-C ONE / TWO POSITION ANALOG I/O BACKP ANELS DESCRIPTION The OM5-BP-SKT-C is a single channel mounting panel for the OM5 modules. The OM5-BP-2-C is a dual channel mounting panel for the OM5 modules. They both are DIN rail compatible.
42 FIGURE 12. OM5-BP-2-C Schematic. FIGURE 11. OM5-BP-SKT-C Schematic. * NOTE: OMX-1362-C resistors are not installed at factory. OMX-CJC-C 22 RD EN 20 V OUT 18 V IN 16 PCOM 6 4 2 5 3 1 23 21 19 17 .
43 OM5-BP-8-C 8 POSITION ANALOG I/O BACKP ANEL, NON-MUL TIPLEXED A temperature sensor is mounted on each channel to provide cold junction compensation for thermocouple input modules (See Figure 14 for Schematic- DESCRIPTION The OM5-BP-8-C analog module mounting board has a capacity of eight analog input and/or output modules in any combination.
44 FIGURE 14. OM5-BP-8-C Schematic. I/O 1 I/O 2 I/O 3 I/O 4 I/O 5 I/O 6 I/O 7 I/O 8 I/O 9 I/O 10 I/O 11 I/O 12 I/O 13 I/O 14 I/O 15 I/O 16 1 5 7 11 13 17 19 23 2 4 8 10 14 16 20 22 25 3 6 9 12 15 18 2.
45 OM5-BP-8-MUX-C 8 POSITION ANALOG I/O BACKP ANEL, MUL TIPLEXED DESCRIPTION The OM5-BP-8-MUX-C backpanel (Figure 15) can accept up to eight OM5 modules in any combination. It can be mounted on the OMX-1363-C 19-inch metal rack. The OM5-BP-8-MUX-C has two analog buses; one for analog input and one for analog output.
46 FIGURE 16. OM5-BP-8-MUX-C Schematic. VREAD ACOM SNS LO ACOM ACOM RD EN R5 R4 R3 R2 R1 R0 WR EN W5 W4 W3 W2 W1 W0 Data DCOM DCOM P1 7 6 5 4 Y3 Y2 Y1 Y0 G B A 1 3 2 Data NC NC 1 2 3 4 5 1 2 3 4 5 6 1.
47 DESCRIPTION The OMX-1324-C is a universal interface board which converts a 26-pin ribbon cable input to 26 screw terminals for discrete wire. It can be mounted on the back of the OMX-1363-C mounting rack or on a DIN rail. Required mounting hardware is included.
48 OM5-BP-SKT -C ANALOG MODULE EV ALUA TION BOARD FIGURE 19. OM5-BP-SKT-C Evaluation Board Dimensions And Pin Layout. FIGURE 20. OM5-BP-SKT-C Evaluation Board Schematic. DESCRIPTION The OM5-BP-SKT-C is a single channel board with a test socket for OM5 module evaluation (Figure 19).
49 OM5-1315-XX-C, OMX-CAB-01-C INTERF ACE CABLES OMX-CAB-01-C Daisy-chain cable provides interconnection between a maximum of four OM5-BP-16-MUX-C and eight OM5-BP-8-MUX-C backpanels (See Figure 22). FIGURE 21. OMX-1315-XX-C System Interface Cable. FIGURE 22.
50 OMX-CJC-C ENCAPSULA TED COLD JUNCTION COMPENSA TION DESCRIPTION The OMX-CJC-C is the identical circuit used on the OM5-BP backpanels except it is packaged as a component for use in customer designed mounting boards (Figure 24).
51 OMX-955-C, OMX-955-220-C POWER SUPPLIES FIGURE 25. OMX-955/955-220-C Physical Dimensions. DESCRIPTION The OMX-955-C encapsulated power supplies are available in 120VAC or 220VAC input voltage ranges and provide 5VDC outputs suitable for all OM5 modules.
52 OMX-977-C, OMX-977-220-C POWER SUPPLIES FIGURE 26. OMX-977/977-220-C Physical Dimensions. DESCRIPTION The OMX-977 Linear Power Supplies are available in 120VAC or 220VAC input. They have sufficient output current capacity to supply any combination of OM5 modules.
2 SCM5B OMEGA® OM5 Series Isolated Signal Conditioning Modules are low cost, high performance, plug-in signal conditioners. Each OM5 module provides a single channel of isolated analog input or output. Input modules interface to all types of external sensors.
3 VOLTAGE OUTPUT MODULES, 50mA DRIVE CAPACITY (400 Hz BW) MODEL INPUT RANGE OUTPUT RANGE OM5-AV-1-C 0 to +5V ± 5V OM5-AV-2-C ± 5V ± 5V OM5-AV-3-C ± 5V 0 to +5V OM5-AV-4-C 0 to +10V ± 10V OM5-AV-5.
4 OM5-IMV/IV Analog V oltage Input Modules, Narrow Bandwidth FEATURES ● ACCEPTS MILLIVOLT AND VOLTAGE LEVEL SIGNALS ● HIGH LEVEL VOLTAGE OUTPUTS ● 1500Vrms TRANSFORMER ISOLATION ● ANSI/IEEE C37.90.1-1989 TRANSIENT PROTECTION ● INPUT PROTECTED TO 240VAC CONTINUOUS ● 160dB CMR ● 95dB NMR AT 60Hz, 90dB at 50Hz ● ± 0.
5 SPECIFICA TIONS Typical at T A = +25 ° C and +5V power. MODEL INPUT RANGE OUTPUT RANGE OM5-IMV-10A-C –10mV to +10mV –5V to +5V OM5-IMV-50A-C –50mV to +50mV –5V to +5V OM5-IMV-100A-C –100m.
6 OM5-II Analog Current Input Modules FEA TURES ● ACCEPTS MILLIAMP LEVEL SIGNALS ● HIGH LEVEL VOLTAGE OUTPUTS ● 1500Vrms TRANSFORMER ISOLATION ● ANSI/IEEE C37.90.1-1989 TRANSIENT PROTECTION ● INPUT PROTECTED TO 240VAC CONTINUOUS ● 160dB CMR ● 95dB NMR AT 60Hz, 90dB AT 50Hz ● ± 0.
7 Input Range 0mA to 20mA or 4mA to 20mA Input Resistor Value 20.00 Ω Accuracy ± 0.1% Stability ± 10ppm/ ° C Input Protection Continuous 240Vrms max Transient ANSI/IEEE C37.90.1-1989 CMV, Input to Output Continuous 1500Vrms max Transient ANSI/IEEE C37.
8 FEA TURES ● INTERFACES RMS VOLTAGE (0 – 300V) OR RMS CURRENT (0 – 5A) ● DESIGNED FOR STANDARD OPERATION WITH FREQUENCIES OF 45HZ TO 1000HZ (EXTENDED RANGE TO 20Khz) ● COMPATIBLE WITH STANDARD CURRENT AND POTENTIAL TRANSFORMERS ● INDUSTRY STANDARD 0-5V OUTPUT ● ± 0.
9 MODEL INPUT* (rms) OUTPUT* (dc) OM5-IAC-100B-C 0-100mV 0-5V OM5-IAC-1B-C 0-1V 0-5V OM5-IAC-10B-C 0-10V 0-5V * Modules can be ordered with other input/output ranges.
10 OM5-IP/IC/IN Linearized 2- or 3-Wire R TD Input Modules FIGURE 1. OM5-IP/IC/IN Block Diagram. circuit which can be floated to ± 50V from Power Common, pin 16. This complete isolation means that no connection is required between I/O Common and Power Common for proper operation of the output switch.
11 Module OM5-IP/IC/IN Input Range Limits –200 ° C to +850 ° C (100 Ω Pt) –80 ° C to 320 ° C (120 Ω Ni) –100 ° C to 260 ° C (10 Ω Cu) Input Resistance Normal 50M Ω Power Off 40k Ω Overload 40k Ω Input Protection Continuous 240Vrms max Transient ANSI/IEEE C37.
12 Each OM5 4-wire RTD input module provides a single channel of RTD input which is filtered, isolated, amplified, linearized, and converted to a high level analog voltage output. This voltage output is logic switch controlled, which allows these modules to share a common analog bus without the requirement of external multiplexers.
13 Input Range Limits –200 ° C to +850 ° C (100 Ω Pt) –80 ° C to +320 ° C (120 Ω Ni) –100 ° C to +260 ° C (10 Ω Cu) Input Resistance Normal 50M Ω Power Off 40k Ω Overload 40k Ω Input Protection Continuous 240Vrms max Transient ANSI/IEEE C37.
14 FEA TURES ● INTERFACES TO POTENTIOMETERS UP TO 10,000 OHMS ● HIGH LEVEL VOLTAGE OUTPUTS ● 1500 VOLT TRANSFORMER ISOLATION ● ANSI/IEEE C37.90.
15 Input Range 0 to 10K Ω Input Resistance Normal 50M Ω Power Off 40K Ω Overload 40K Ω Input Protection Continuous 240Vrms max Transient ANSI/IEEE C37.90.1-1989 Sensor Excitation Current 0.25mA; 100 Ω , 500 Ω , 1K Ω sensor 0.10mA; 10K Ω sensor Lead Resistance Effect ± 0.
16 OM5-ITC Thermocouple Input Modules The OM5-ITC modules are designed with a completely isolated computer side circuit which can be floated to ± 50V from Power Common, pin 16. This complete isolation means that no connection is required between I/O Common and Power Common for proper operation of the output switch.
17 Module OM5-ITC Input Range -0.1V to +0.5V Input Bias Current -25nA Input Resistance Normal 50M Ω Power Off 40k Ω Overload 40k Ω Input Protection Continuous 240Vrms max Transient ANSI/IEEE C37.90.1-1989 CMV, Input to Output Continuous 1500Vrms max Transient ANSI/IEEE C37.
18 OM5-WBS Strain Gage Input Modules, Wide Bandwidth FEA TURES ● INTERFACES TO 100 Ω THRU 10k Ω , FULL-BRIDGE, HALF-BRIDGE, OR QUARTER-BRIDGE STRAIN GAGES ● HIGH LEVEL VOLTAGE OUTPUTS ● 1500Vrms TRANSFORMER ISOLATION ● ANSI/IEEE C37.
19 Full Bridge Half Bridge Module OM5-WBS38-01-C, -WBS-1/-2/-4/-5-C OM5-WBS38-03-C,-WBS-3-C Input Range ± 10mV to ± 100mV * Input Bias Current ± 0.3nA * Input Resistance Normal 50M Ω * Power Off 40k Ω * Overload 40k Ω * Signal Input Protection Continuous 240Vrms max * Transient ANSI/IEEE C37.
20 FEA TURES ● ACCEPTS HIGH LEVEL VOLTAGE OR PROCESS CURRENT INPUT ● UNIPOLAR OR BIPOLAR CURRENT OUTPUT ● 1500Vrms TRANSFORMER ISOLATION ● ANSI/IEEE C37.90.1-1989 TRANSIENT PROTECTION ● OUTPUT PROTECTED TO 240VAC CONTINUOUS ● 110dB CMR ● 400Hz SIGNAL BANDWIDTH ● ± 0.
21 Unipolar Output Current Module OM5-IVI Input Voltage Range ± 5V or 0V to +5V Input Current Range (–05) 0 to 20mA Input Voltage Maximum ± 36V (no damage) Input Current, Maximum (–05) 75mA (no .
WARRANTY/DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty one (1) year product warranty to cover handling and shipping time.
TEMPERATURE þ Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies þ Wire: Thermocouple, RTD & Thermistor þ Calibrators & Ice Point References þ Recorders, Contro.
Ein wichtiger Punkt beim Kauf des Geräts Omega Engineering OM5-C (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Omega Engineering OM5-C noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Omega Engineering OM5-C - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Omega Engineering OM5-C reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Omega Engineering OM5-C erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Omega Engineering OM5-C besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Omega Engineering OM5-C verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Omega Engineering OM5-C. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Omega Engineering OM5-C gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.