1. General Information and Features 2 2. Applicable Standards 3 3. Installation and Removal 4 4. Input and Output Connections 8 5. Specifications 9 5.1 PS T ype Labeling 5.2 Size & W eight 5.3 Mounting 5.4 T emperature Ranges 5.5 Input Range 5.6 Input Current Surge Protection 5.
The compact DRN power supplies are designed to supply well-regulated 21.5 volt DC power to sensors, signal conditioners, data acquisition systems and high level logic equipment.
2.1 Input Voltage Tolerances Exceeds IEC 38 range 2.2 Input / Output Isolation 4KV rms 60Hz 1 minute test 630V conductor spacing, IEC 348 Exceeds VDE551 / IEC 742 separation spacing Exceeds VDE106 protective separation Exceeds VDE 160 clearance distances Exceeds VDE160 creepage distances 2.
The DRN power supplies are heavy enough to cause damage and or injury if dropped during installation. Assure firm rail mounting before releasing grip on the unit. If a rail assembly is to be transported, then disconnection, dismounting and separate packing of the power supply is recommended.
T o change voltage jumpers: 1. Remove cover from case by carefully prying up two side tabs using a screwdriver . Remove two screws from bottom of case. Slide unit out of case. 2. Locate the main board assembly and position it in front of you the same way as shown in Figure 3.
Figure 3.1 Ñ Main Board Power Jumpers MAIN BOARD T1 115VAC WIRING SHOWN WITH W1 W3 TRANSFORMER MOUNTING PLATE W2 115VAC JUMPER WIRING W1 W3 W2 230VAC JUMPER WIRING W2 W3 W1 I NST ALLA TION AND R EMOV.
Figure 3.2 Ñ 35mm "Top Hat" Installation: Hook in the module with the mounting rail guide on the top edge of the mounting rail and lower it to lock it into position. Removal: Release the spring catch with a screwdriver while raising the module to disengage it.
Figure 4.1 Ñ Front Panel Connection Labels shown without regulator cover AC Line AC Neutral Ground RETURN NO CONNECTION +21.5V IN AC N PWR +V N/C OUT DC I NPUT AND O UTPUT C ONNECTIONS 4 8 DRN-PS Ñ .
5.1 PS Type Labeling DRNÐPSÐ750, where 750 equals mA rating. DRNÐPSÐ750 5.2 Size & Weight Height: 2.76" (70mm) Width: 2.95" (75mm) Depth: 5.95" (151mm) Weight: 2.0 lbs. (0.9 kg) 5.3 Mounting 35mm "top hat" DIN EN 50022 5.
5.5 Input Range 115 or 230V, 49Ð61Hz DRNÐPSÐ750 ± 10% 5.6 Input Current Surge Protection 6kA/275V Varistor 5.7 Output Voltage 21.5V ± 2% - IR, where I = output current amperes and R = 0.
5.10 Temperature Derating None below 50 degrees C DRNÐPSÐ750, 15mA per degree C above 50¡C 5.11 Power-on Indicator Front Panel red LED lamp 5.12 Short-circuit and overload protection DRNÐPSÐ750 foldback current limiting with automatic high temperature shutdown no fuses required 5.
Figure 6.1 Ñ Derating Graph Figure 7.1 Ñ Block Diagram 49-61Hz 115/230vac INPUT: (+V) Ground AC Line AC Neutral V A R I S T O R L C F I L T E R B R I D G E ( ) 21.5V R E G U L A T O R Return 75mA 50 DRN-PS-750 ¡ C Ambient 0 1000 800 600 400 200 60 45 35 25 15 5 -5 I max.
Figure 8.1 Ñ Dimensions SPACED AS SHOWN. POWER SUPPLY WITH [151.1] 5.95 2.76 2.95 3.15 TWO SCREWS FASTEN RAIL UNDER MAX [70.0] [75.0] [80.0] D IMENSIONS D RA WING 8 13 DRN-PS Ñ DIN Rail Power Suppli.
S AFETY C ONSIDERA TIONS 14 DNR-PS Ñ DIN Rail Power Supplies Unpacking & Inspection Unpack the instrument and inspect for obvious shipping damage. Do not attempt to operate the unit if damage is found. This instrument is a panel mount device protected in accordance with Class I of EN 61010 (115/230 AC power connections).
WARRANTY / DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time.
Where Do I Find Everything I Need for Process Measurement and Control? OM EGAÉOf Course! TEMPERATURE M U Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies M U Wire: Therm.
Ein wichtiger Punkt beim Kauf des Geräts Omega Engineering DRN-PS-750 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Omega Engineering DRN-PS-750 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Omega Engineering DRN-PS-750 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Omega Engineering DRN-PS-750 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Omega Engineering DRN-PS-750 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Omega Engineering DRN-PS-750 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Omega Engineering DRN-PS-750 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Omega Engineering DRN-PS-750. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Omega Engineering DRN-PS-750 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.