TECHNICAL & SER VICE MANU AL <Indoor unit> PDFY-P06NMU-E,PDFY-P08NMU-E PDFY-P12NMU-E,PDFY-P15NMU-E PDFY-P18NMU-E,PDFY-P24NMU-E PDFY-P27NMU-E,PDFY-P30NMU-E PDFY-P36NMU-E,PDFY-P48NMU-E 2005 Models Ceiling Concealed Built-in Ser ies PDFY CONTENTS SAFETY PRECA UTIONS ························· 1.
1 - Inadequate connection and fastening ma y generate heat and cause a fire. • Prepare for typhoons and other str ong winds and ear thquakes and install the unit at the specified place. - Improper installation may cause the unit to topple and result in injury .
2 2 . Precautions for de vices that use Caution: • Do not use the existing refrigerant piping. - The old refr igerant and refrigerator oil in the e xisting piping con- tains a large amount of chlor ine which ma y cause the refrigerator oil of the new unit to deteriorate .
3 PDFY-P06NMU-E PDFY-P08NMU-E PDFY-P12NMU-E PDFY-P15NMU-E PDFY-P18NMU-E PDFY-P24NMU-E PDFY-P27NMU-E PDFY-P30NMU-E PDFY-P36NMU-E PDFY-P48NMU-E 1.8 / 2.0 2.
4 ● ● ● Remote Indoor (Main) Unit controller ● Operation buttons [P AR-21MAA] Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF b utton.
5 [Display] C C ON/OFF CENTRALL Y CONTROLLED ERROR CODE CLOCK ON OFF CHECK CHECK MODE FIL TER TEST RUN FUNCTION 1Hr . NOT A V AILABLE ST AND BY DEFROST TEMP .
6 3-1. Specification PDFY-P-NMU-E PDFY-P-NMU-E Notes: *1 Cooling/Heating capacity indicates the maxim um value at operation under the f ollowing condition. Cooling: Indoor: 26.7 ˚ C [80 ˚ F] DB/19.4 ˚ C [67 ˚ F] WB Outdoor: 35 ˚ C [95 ˚ F] DB Heating: Indoor: 21.
7 LEV C1 3.0 µ F X 440V 5.0 µ F X 440V 5.0 µ F X 440V 8.0 µ F X 440V 6.0 µ F X 440V MF1 PDFY- P06,08,12 NMU-E PDFY- P30 NMU-E PDFY- P36 NMU-E PDFY- P48 NMU-E PDFY- P24,27 NMU-E PDFY- P15,18 NMU-E 3-2. Electrical parts specifications Model Pa r t s name T ranrsformer T (Primary) 240V 60Hz (Secondary) (23.
8 123 mm(in.) mm(in.) F 10 E 65 When installing the drain water lifting-up mech(option). (option) 1 3 Suspension bolt hole 2 1 Fresh air intake ø 150(5-29/32)knock out hole 4- ø 3(1/8) Mounting hole Water filling port Control box ø 172 Drain hose Liquid pipe <flare> Gas pipe <flare> 2 1 1 :R410A outdoor unit 2 :R22 outdoor unit 2.
9 PDFY-P36 · 48NMU-E 12(1/2) 1:R410A outdoor unit 2:R22 outdoor unit mm(in.) mm(in.) 30(1-3/16) 52 (2-1/16) 300X4=1200(11-3/16X4=47-1/4) 5- ø 3(1/8)hole 65X20=1300(2-9/16X20=51-3/16) 21X2- ø 3(1/8)hole 35(1-13/32) 1440(56-23/32) 35(1-13/32) 105 65 (2-9/16) 214 33 3 When installing the drain water lifting-up mech(option).
10 WIRING DIA GRAM 5 CN2M ( ) ( ) CN3T NOTE 1 NOTE 1 S(SHIELD) G PARTS LOCATION AC250V 5A F (Green) (Red) (White) (Yellow) (Green) (Yellow) (Green) (Yellow) (White) (White) (White) (Blue) (White) (Blu.
11 PDFY-P36 · 48NMU-E PARTS LOCATION Varistor ZNR1,ZNR901 G 543 2 1 (Green) CN22 (Yellow) CN24 (White) CN25 NOTE1 (Blue) (Red) (White) DP T1 T2 T3 AC250V 5A F ( ) ( ) AC250V 6.3A T S(SHIELD) TB15 (TRANSMISSION TERMINAL BED) TB5 (TRANSMISSION TERMINAL BED) TB2 F2 L2 L1 ZNR901 901 CN2M (Blue) C 1 2 4 2 1 4 2 1 MF CND(Red) 5 3 1 X07 I.
12 Strainer (#100mesh) Strainer (#100mesh) Heat exchanger Room temparature thermistor TH21 Gas pipe thermistor TH23 Liquid pipe thermistor TH22 Linear expansion v alve Gas pipe Flare connection Gas pipe PDFY -P06,08,12,15NMU-E PDFY -P18NMU-E Capacity Item ø 12.
13 Room temparature thermistor (TH21) Liquid pipe thermistor (TH22) Gas pipe thermistor (TH23) T ransformer F an motor Linear e xpansion v alve Disconnect the connector , then measure the resistance using a tester . (Sorrounding temperature 10 ˚ C~30 ˚ C[50 ˚ F~86 ˚ F]) Disconnect the connector and measure the resistance using a tester .
14 0 10 20 30 40 50 -20 -10 0 10 20 30 40 50 < Ther mistor f or lower temperature > T emperature ( ˚ C) -4 14 32 50 68 86 104 122 [ ˚ F] Resistance (k Ω ) 4 ø 4 3 6 5 ø 3 2 ø 2 1 ø 1 ø .
15 Output (Phase) Output ø 1 1 ON ø 2 ON ø 3 OFF ø 4 OFF 2 OFF ON ON OFF 3 OFF OFF ON ON 4 ON OFF OFF ON <Output pulse signal and the valve operation> ➁ Linear e xpansion valve oper ation .
16 1 2 3 4 5 6 7 8 9 10 1~6 1~10 1~4 Thermistor<Intake temperature detection>position ON OFF Filter crogging detection Provided Not provided Filter lif e 2,500hr 100hr Air intake Eff ective Not .
17 0 5 9 4 8 3 7 2 6 1 SW12 10 0 5 9 4 8 3 7 2 6 1 SW1 1 1 0 8 F 7 E 6 D 5 C 4 B 3 A 2 9 1 SW14 3 2 1 0 5 9 4 8 3 7 2 6 1 SW12 0 5 9 4 8 3 7 2 6 1 SW1 1 0 8 F 7 E 6 D 5 C 4 B 3 A 2 9 1 SW14 Address bo.
18 (A) Fig.1 OPERA TING PROCEDURE PHO T OS DISASSEMBL Y PR OCEDURE 8 8-1 CONTROL BO X Be careful removing hea vy par ts. 1.Removing the contr ol box co ver (1)Remov e the fixing screws(two) of the cov er(A) and remov e the cover . (C) (D),(E) Fig.1 Fig.
19 (F),(G) Fig.1 8-3 THERMIST OR (Intake air temperature detection) OPERA TING PROCEDURE PHO T OS 1.Removing the thermistor and thermistor holder (1)Pull out the thermistor holder(F) and ther mistor (G) which are fix ed the control box. (H) 1 2 Fig.1 Fig.
20 (J) Fig.1 Fig.2 (K),(L) OPERA TING PROCEDURE PHO T OS 8-5 THERMIST OR (Gus piping temperature detection) 1.Removing the co ver (1)Remov e the fixing screw of the cov er(J) and remov e the cover . 2.Removing the thermistor (1)Remov e the ther mistor(K), from the ther mistor holder(L), which are installed on the copper tube.
21 (M) (N) (R) fan motor shaft fixing screw Fig.1 Fig.2 Fig.3 1 2 2 3 3 (P) (Q) OPERA TING PROCEDURE PHO T OS 8-6 F AN and F AN MO T OR 1.Removing the filter (1)Press the tabs of the filter and remov e the filter in the direction of the arrow 1 .
22 Fig.1 Fig.2 (S) OPERA TING PROCEDURE PHO T OS 8-7 HEA T EXCHANGER 1.Removing the drainpan with pr ocedure 8-4 2.Removing the co ver(J) with procedure 8-5 3.Removing the Heat e xchanger (1)Remov e the fixing screws of the heat e xchang- er(S) and remov e the heat exchanger .
Issued in Aug. 2005 HWE05160 New publication, effective Aug. 2005 Specifications subject to change without notice.
3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications are subject to ch ange without notice.
Ein wichtiger Punkt beim Kauf des Geräts Mitsubishi Electronics PDFY-P30NMU-E (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Mitsubishi Electronics PDFY-P30NMU-E noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Mitsubishi Electronics PDFY-P30NMU-E - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Mitsubishi Electronics PDFY-P30NMU-E reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Mitsubishi Electronics PDFY-P30NMU-E erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Mitsubishi Electronics PDFY-P30NMU-E besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Mitsubishi Electronics PDFY-P30NMU-E verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Mitsubishi Electronics PDFY-P30NMU-E. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Mitsubishi Electronics PDFY-P30NMU-E gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.