SER VICE TECHNICAL GUIDE CONTENTS 1. MS MICROPROCESSOR CONTROL ·················· 4 2. MSZ, MSY MICROPROCESSOR CONTROL ······ 7 3. MXZ MICROPROCESSOR CONTROL ·············· 21 4. MFZ MICROPROCESSOR CONTROL ·············· 35 SPLIT -TYPE AIR CONDITIONERS No.
2 Revision A: • MXZ-3A30NA- 1 has been added. Revision B: • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD, MSZ-D and MSY -D have been added. Revision C: • MXZ-2A20NA- 2 has been added. Revision D: • MSZ-GA•NA and MSY -GA•NA have been added. Revision E: • MSZ-FE•NA, MSZ-GE•NA, MSY -GE•NA and MXZ-B•NA have been added.
3 1. MS MICROPROCESSOR CONTROL ·································································································· ················· 4 Indoor unit models Outdoor unit models MS-A09/12W A MU-A09/12W A 1-1.
4 1-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.
5 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 2. Indoor fan speed control Indoor fan operates at the set speed by F AN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes V ery Low .
6 1-3. AUTO V ANE OPERA TION 1. Horizontal vane ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.
7 2-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature.
8 2-2. DR Y ( ) OPERA TION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit.
9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GE When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66°F (19°C), the fan stops.
10 set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V . coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane V ery Low (temperature of indoor.
11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEA T mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) below the set temperature.
12 <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided.
13 MUZ-A24 MUY -A24 MUZ-D MUY -D MUZ-FE18 MUZ-GA MUY -GA MUZ-GE24 MUY -GE24 POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies 3-phase AC power to compressor .
14 3. Purpose of P AM adoption P AM (Pulse Amplitude Modulation) has been adopted for the ef fi ciency improvement and the adaptation to IEC harmonic cur- rent emission standard Outline of simple par.
15 4. Intelligent power module IPM consists of the following components · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors.
16 2-7-4. Characteristics of sine wave control in case of brushless DC motor ● Although ordinary 3-phase induction motor requires energy to excite the magnetic fi eld of rotor , brushless DC motor does not need it. So, higher ef fi ciency and torque are provided.
17 2-8. OPERA TIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tempera- ture.
18 (2) T ime chart OFF T ime Ti m e ON Operational frequency of the compressor Commanded to open Standard opening degree Opening degree is corrected according to discharge temperature. (Refer to (3)) Positioning Air conditioner ON Air conditioner OFF (thermostat off) LEV opening degree About 15 minutes 2-9.
19 (3) Control data F E D C B A T arget discharge temperature Operational frequency of the compressor 30 50 70 90 1 10 130 23 38 53 69 84 99 (Hz) (Hz) ( Other models ) ( MUZ-FE18 MUZ-GE24 MUY -GE24 ) .
20 2. Pre-heat control ON condition (1) Pre-heat control is turned ON for 15 or 30 minutes after the breaker is turned ON. (2) 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF .
21 3-1. INVERTER SYSTEM CONTROL POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + 3-1-1. Inverter main power supply circuit Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies 3-phase AC power to compressor .
22 3. Power factor improvement Booster coil reactor and PFC rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi- lize the voltage of DC supplied to inverter circuit and make its waveform smooth.
23 3-2. EXP ANSION V AL VE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit. Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulses in 15 minutes When outdoor unit is operating, some indoor units stop and some operate.
24 In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger , and when temperature difference develops, the indoor coil thermistors adjust LEV opening to diminish the super heat.
25 23 54 69 84 100 1 15 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A/2B MXZ-3A/4A 23 Compressor operating frequency (Hz) 4Hz 01 02 03 04 05 06 07 08 09 10 LEV Opening (code) Determination of LEV standard.
26 MXZ-3A30NA- 1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA Exclusive LEV Standard opening (pulse) LEV Opening (code) 123456789 1 0 COOL 126 130 134 138 150 160 170 180 190 200 HEA T 248 248 258 266 .
27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor .
28 Correct the LEV opening according to the difference between target discharge temperature and discharge temperature. (2) Separate correction (COOL,DRY) (Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all.
29 3-3. OPERA TIONAL FREQUENCY RANGE b) Correct the LEV separately by temperature difference “ ∆ R T” between main/sub indoor coil thermistor . ∆ RT LEV opening correction (pulse) 10.8 ∆ RT 2 7.2 ∆ RT < 10.8 1 ∆ RT < 7.2 1 In addition, decrease the target discharge temperature corresponding ∆ RT .
30 MXZ-3A30NA- 1 MXZ-4A36NA Number of operating unit Capacity code COOL (Hz) DRY (Hz) HEA T (Hz) Min. Max. Min. Max. Defrost 1 4 2 55 82 52 07 05 8 7 2 55 82 52 07 05 8 9,10 25 71 25 20 80 58 12 25 80.
31 3-4. HEA T DEFROSTING CONTROL (1) Starting conditions of defrosting When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads 26.6°F or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min- utes).
32 COOL Fan speed changes so that the condensing temperature stays within the target range. Fan speed Revolution per minutes (rpm) MXZ-2B20NA- 1 MXZ-3B MXZ-4B 1 100 100 2 150 150 3 200 200 4 250 250 5.
33 1. Pre-heat control is turned ON for 15 or 30 minutes, after the breaker is turned ON. 2. 30 minutes after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF .
34 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 3-9. DR Y OPERA TION 3-10. HEA T OPERA TION 2. High pressure protection In HEA T operation the indoor coil thermistor detects the temperature of the indoor heat exchanger .
35 4 MFZ MICROPROCESSOR CONTROL 3. Coil frost prevention Refer to MXZ MICROPROCESSOR CONTROL, COOL OPERA TION (3-8.2.). 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON.
36 1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, HEA T OPERA TION (3-10.1.). 4-3. HEA T ( ) OPERA TION 2. Indoor fan speed control (1) Indoor fan operates at the set speed by F AN SPEED CONTROL button. In Auto the fan speed is as follows.
37 4-5. INDOOR F AN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor , and outputs signal to the microprocessor to feed- back the rotational frequency . Comparing the current rotational frequency with the target rotational frequency (Super High, High, Med.
38 4-6. AUTO V ANE OPERA TION Horizontal vane (1) Cold air prevention in HEA T operation When any of the following conditions occurs in HEA T operation, the vane angle changes to V ertical position automati- cally to prevent cold air blowing on users.
39.
New publication, effective Sep. 2010. Specifications subject to change without notice. HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2006 MITSUBISHI ELECTRIC CO.,L TD Distributed in Sep. 2010. No. OBT16 REVISED EDITION-G 6 Distributed in Mar .
Ein wichtiger Punkt beim Kauf des Geräts Mitsubishi Electronics MSZ-D30/36NA (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Mitsubishi Electronics MSZ-D30/36NA noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Mitsubishi Electronics MSZ-D30/36NA - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Mitsubishi Electronics MSZ-D30/36NA reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Mitsubishi Electronics MSZ-D30/36NA erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Mitsubishi Electronics MSZ-D30/36NA besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Mitsubishi Electronics MSZ-D30/36NA verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Mitsubishi Electronics MSZ-D30/36NA. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Mitsubishi Electronics MSZ-D30/36NA gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.