System 9100 Technical Manual 636.4 Configuration Guides Section Configuration Guide Issue Date 0896 © 1996 Johnson Cont rols, I nc. 1 Code No. LIT-6364050 XT-9100 Extension Module/ XP-910x Expansion .
2 Configuration Guides— XT-9100 Configur ation Guide.
Configuration Guides— XT-9100 Configur ation Guide 3 XT-9100 Extension Module/ XP-910x Expansion Modules The XT-9100 Extension Module and its expansion modules have been designed to provide additional input and output capacity within Metasys Networks and specifically for the DX-9100 Extended Digital Controller.
4 Configuration Guides— XT-9100 Configur ation Guide For full details of the hardware configuration, refer to the XT-9100 Technical Bulletin (LIT-6364040) .
Configuration Guides— XT-9100 Configur ation Guide 5 XP9103 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 XP9102 ADDRESS A B C A B C RD TD Power RS485 FUS E HOT GND NEUT EXP EXP FUS E min max XT9100 TR9100 EXP EX.
6 Configuration Guides— XT-9100 Configur ation Guide.
Configuration Guides— XT-9100 Configur ation Guide 7 Software Configuration Software configuration involves the setting of all the Items of the extension module to values which correspond to the intended application. Typically, use the GX Tool to configure a system, and the SX Tool to troubleshoot.
8 Configuration Guides— XT-9100 Configur ation Guide Via the SX Tool The “Output Hold/Reset on Communication Failure” flag is set at Bit X2 of Item XTS (RI.
Configuration Guides— XT-9100 Configur ation Guide 9 Via the GX Tool The I/O type and map details are automatically generated by the GX-9100 Graphic Configuration Software when all I/O data for extension modules has been entered. It is then downloaded into the XT-9100 directly or via the DX-9100 and XT-Bus.
10 Configuration Guides— XT-9100 Configur ation Guide Note: The data base in the XT-9100 has been designed to accept most configuration of inputs and outputs. All inputs and outputs which are physically connected through expansion modules must be configured, and only those points.
Configuration Guides— XT-9100 Configur ation Guide 11 Via the SX Tool The input type for the eight possible inputs (n = 1 to 8) can be configured in Item AITn (RI.
12 Configuration Guides— XT-9100 Configur ation Guide An alarm from the High Limit (HIAn) and Low Limit Alarm (LOAn) will be generated from the unfiltered or filtered input.
Configuration Guides— XT-9100 Configur ation Guide 13 Via the SX Tool Input Type: X7 = 0 0-10 volts X7 = 1 0-20 mA X8 = 1 20% suppression 2-10V or 4-20 mA) Linearization and Sensor Type: X11 X10 X9 .
14 Configuration Guides— XT-9100 Configur ation Guide Via the SX Tool The high limit is at Item HIAn (RI.91, RI.99, RI.107, RI.115, RI.123, RI.131, RI.139, and RI.147), the low limit is at Item LOAn (RI.92, RI.100, RI.108, RI.116, RI.124, RI.132, RI.
Configuration Guides— XT-9100 Configur ation Guide 15 An XT-9100 can accept up to 16 digital inputs, which will be considered active when driven to a common digital ground. The first eight digital inputs are connected to XP1 and the next eight digital inputs to XP2.
16 Configuration Guides— XT-9100 Configur ation Guide The digital input transitions of XP1 are counted as follows: Digital Input DIn Prescale PCn Count Transition Pulse Counter CNTRn (RI.
Configuration Guides— XT-9100 Configur ation Guide 17 Via the GX Tool Select XTn, ANALOG, XTn, AOn, and Data, then enter the output code: 0 = disabled 1 = 0 to 10 VDC 2 = 0 to 20 mA 3 = 4 to 20 mA Via the SX Tool The output type can be configured in Item AOT (RI.
18 Configuration Guides— XT-9100 Configur ation Guide The source of the analog output signal is defined in the DX-9100 Controller. Via the GX Tool Select XTn, AOn, Data, and the “Source Point” field. Enter * and select the required source variable.
Configuration Guides— XT-9100 Configur ation Guide 19 Each digital output is defined and configured by the following parameters: • Tag name (GX-9100 only) • Output type • Pulse time When the X.
20 Configuration Guides— XT-9100 Configur ation Guide The source of the digital output signal is defined in the DX-9100 Controller. Via the GX Tool Select XTn or (EXP), DOn, Data, and then the “Source Point” field. Enter * and select the required source variable.
Configuration Guides— XT-9100 Configur ation Guide 21 Download via DX-9100 Controll er and N2 Bus Connect an RS-232-C/RS-485 converter (type MM-CVT101-x in North America and type IU-9100-810x in Europe) to one of the serial communication ports (COM1 or COM2) of the personal computer on which the GX Tool is running.
22 Configuration Guides— XT-9100 Configur ation Guide Upload via a DX-9100 Controll er Only complete DX-9100/XT-9100 configurations should be uploaded from the DX-9100. Select DX-9100 and NEW to clear the PC screen. Select DX-9100, UPLOAD, and DX&XT.
Configuration Guides— XT-9100 Configur ation Guide 23 Appendix 1: SX Tool Item Description and Tables The following information is important when commissioning with the SX Service Module. Each constant, variable, or value in an XT-9100 Extension Module can be addressed via an Item code.
24 Configuration Guides— XT-9100 Configur ation Guide 3. Totalized Numerical Items are actual positive numbers. They refer to totalized values of pulse counters. They are displayed and entered as whole numbers, without a sign or decimal point. These Items are shown in the Item List with “4 Bytes” in the Type column.
Configuration Guides— XT-9100 Configur ation Guide 25 A DX-9100 floating point number consists of two bytes with following format: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 E3 E2 E1 E0 S M10 M9 M8 M7 M6.
26 Configuration Guides— XT-9100 Configur ation Guide Table 3: Item List RI. HI. Type R/W Tag Description 00 00 1 Byte R MODL Device Model : 08H 01 01 1 Bytes R/W OPMO Operation Mode (status) X8 X7 .
Configuration Guides— XT-9100 Configur ation Guide 27 RI. HI. Type R/W Tag Description 07 07 1 Byte R/W DOS1 Digital Output Status XP1 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 XP1 : Output 1 is On X2 = 1 XP1 .
28 Configuration Guides— XT-9100 Configur ation Guide RI. HI. Type R/W Tag Description 10 0A 1 Byte R DIS2 Digital Input Status XP2 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 1 XP2 : Digital Input 1 is On X2 = 1 .
Configuration Guides— XT-9100 Configur ation Guide 29 RI. HI. Type R/W Tag Description 12 0C Number R AI1 Analog Input Value 1 13 0D Number R AI2 Analog Input Value 2 14 0E Number R AI3 Analog Input.
30 Configuration Guides— XT-9100 Configur ation Guide RI. HI. Type R/W Tag Description 48 30 1 Byte Int CNF PC1 Prescaler DI1 Counter 49 31 1 Byte Int CNF PC2 Prescaler DI2 Counter 50 32 1 Byte Int .
Configuration Guides— XT-9100 Configur ation Guide 31 RI. HI. Type R/W Tag Description 65 41 1 Byte CNF DIT2 Digital Input Type XP2 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 0 XP2 : DI1 = Maintained Contact X1 =.
32 Configuration Guides— XT-9100 Configur ation Guide RI. HI. Type R/W Tag Description 67 43 1 Byte CNF DOT2 Digital Output Type XP2 X8 X7 X6 X5 X4 X3 X2 X1 X1 = 0 XP2 : DO1 = ON/OFF Type X1 = 1 XP2.
Configuration Guides— XT-9100 Configur ation Guide 33 RI. HI. Type R/W Tag Description 77 4D 1 Byte CNF IOMAP Extension Module I/O Map X8 X7 X6 X5 X4 X3 X2 X1 X1 = 0 XP1 : I/O1 and I/O2 Not Used X1 .
34 Configuration Guides— XT-9100 Configur ation Guide RI. HI. Type R/W Tag Description 79 4F 1 Byte CNF IOMO D Extension M odule I/O Mode X8 X7 X6 X5 X4 X3 X2 X1 X1 = 0 XP1 : I/O1 and I/O2 Input X1 .
Configuration Guides— XT-9100 Configur ation Guide 35 RI. HI. Type R/W Tag Description 88 58 2 Bytes CNF AIT1 Input Type of Analog Input 1 0 0 0 0 0 X1 1 X1 0 X9 X8 X7 X6 X5 X4 X3 X2 X1 X4 X3 X2 X1 .
36 Configuration Guides— XT-9100 Configur ation Guide RI. HI. Type R/W Tag Description 104 68 2 Bytes CNF AIT3 Input Type of Analog Input 3 (bits as AIT1) 105 69 Number CNF HR3 High Range Analog Inp.
Configuration Guides— XT-9100 Configur ation Guide 37 RI. HI. Type R/W Tag Description 128 80 2 Bytes CNF AIT6 Input Type of Analog Input 6 (bits as AIT1) 129 81 Number CNF HR6 High Range Analog Inp.
38 Configuration Guides— XT-9100 Configur ation Guide Notes.
Configuration Guides— XT-9100 Configur ation Guide 39 Notes.
40 Configuration Guides— XT-9100 Configur ation Guide Notes Controls Group FAN 636.4 507 E. Mi chigan St reet Sys tem 9100 Techni cal Manual P.O. Box 42 3 Printed in U.
Ein wichtiger Punkt beim Kauf des Geräts Johnson Controls XT-9100 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Johnson Controls XT-9100 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Johnson Controls XT-9100 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Johnson Controls XT-9100 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Johnson Controls XT-9100 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Johnson Controls XT-9100 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Johnson Controls XT-9100 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Johnson Controls XT-9100. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Johnson Controls XT-9100 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.