Benutzeranleitung / Produktwartung AC6B des Produzenten Johnson Controls
Zur Seite of 18
562156-UIM-A-0610 R-410A OUTDOOR SPLIT -SYSTEM AIR CONDITIONING MODELS: 16 SEER - CZF / AC6B / AL6B SERIES 2 TO 5 T ONS INSTALLATION MANUAL LISTED ISO 9001 Certified Quality Management System T ABLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . .
562156-UIM-A-0610 2 Johnson Controls Unitary Products INSPECTION As soon as a unit is r eceived, it should be inspected for possible dam- age during transit. If damage is evident, th e extent of the damage should be noted on the carrier ’s delivery receipt.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 3 GROUND IN ST ALLA TION The unit may be installed at ground level on a solid b ase that will not shift or settle, causing strain on t he refrigerant lines and possible leaks.
562156-UIM-A-0610 4 Johnson Controls Unitary Products The outdoor condensing unit must be connected to the indoor evapora - tor coil using field supplied refrigerant grade copper tubing that is inter- nally clean and dry . Units should be installed only with the tubing sizes for approved system combinations as specified in tabular data sheet.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 5 2. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at th e outdoor unit. Connect low pressure nitrogen to the liquid line service port. 3. Braze the liquid line to the liquid valve at the outdoor unit.
562156-UIM-A-0610 6 Johnson Controls Unitary Products FIELD CONNECTIONS POWER WIRING 1. Install the proper size weather proof disconnect switch outdoors and within sight of the unit. 2. Remove the screws at the bottom of the corner cover . Slide corner cover down and remove from unit.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 7 CFM SELECTION BOARD SETTINGS For proper system operation the CFM Selection Board jumpers must be set properly . Refer to the T ech Guide for the recommende d air flow settings for each size condensing unit and matchu p.
562156-UIM-A-0610 8 Johnson Controls Unitary Products For additional connection diagrams for a ll UPG equipment refer to “Low V olt age System Wiring” document available online at www .
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 9 FIGURE 1 1: Thermostat Wiring – Single S tage Air Conditioner (with AC control) – VS Air Handler 09 $9 ,'02'(/ 6 -XPSHU.
562156-UIM-A-0610 10 Johnson Controls Unitary Products FIGURE 12: Thermostat Wiring – Single S tage Air Conditi oner (with AC control) – Modulating F urnace </&/&.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 11 SECTION VI: SY STEM CHARGE 1. The factory charge in the outdoor unit includes enough charge for the unit, a 15 ft. line set and the smallest rated indoor coil match-up. Some indoor coil matches may r equire additional charge.
562156-UIM-A-0610 12 Johnson Controls Unitary Products 3. If the coil needs to be cleaned , use clean water to wash dust, dir t, and debris from outdoor condensing coil. 4. Refer to the furnace or air handler instructions for filter a nd blower motor maintenance.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 13 LED DIAGN OSTIC INDICA TORS The control includes two LED’s that display diagnostic information. LED1 is red and LED2 is green. These LED’s are used to display oper- ational mode, fault information.
562156-UIM-A-0610 14 Johnson Controls Unitary Products F AUL T CODE DISPLA Y The control will display any fault cod e that is currently active using the LED’s.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 15 COOLING OPERA TION First-St age Cooling Operation During first-stage cooling operation, the con trol will receive a thermostat signal at the Y1 terminal. The contr ol will energize the M compressor output terminal.
562156-UIM-A-0610 16 Johnson Controls Unitary Products SECTION IX: WIRING DIAGRAM FIGURE 13: Wiring Diagram (2 - 4 T on).
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 17 FIGURE 14: Wiring Diagram (5 T on).
Subject to change without not ice. Published in U.S.A. 562156-UIM-A-0610 Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Contro ls Unitar y Prod uc t s 500.
Ein wichtiger Punkt beim Kauf des Geräts Johnson Controls AC6B (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Johnson Controls AC6B noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Johnson Controls AC6B - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Johnson Controls AC6B reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Johnson Controls AC6B erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Johnson Controls AC6B besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Johnson Controls AC6B verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Johnson Controls AC6B. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Johnson Controls AC6B gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.