CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPROVALS .
341426-BIM-A-0108 2 Johnson Controls Unitary Products T A BLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 RENEWAL PARTS .
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 3 GENERAL Model DY A units are cooling/hea ting air conditioners designed for outdoor installation. Only gas pipi ng, electric power and duct connection s are required at th e point of installation.
341426-BIM-A-0108 4 Johnson Controls Unitary Products INST ALLA TION LIMIT A TIONS These units must be installed in accordance with the follow- ing national and loca l safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadi an Electrical Code Part 1, C22.
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 5 CLEARANCES All units require certain clearances for proper operation an d service. Refer to T able 10 for the clearances required for combustion, construction, serv icin g and proper unit opera- tion.
341426-BIM-A-0108 6 Johnson Controls Unitary Products THERMOST A T The room thermostat should be locate d on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances.
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 7 T ABLE 3: NA TURAL GAS APPLICA TION DA T A A V AILABLE ON MODELS INPUT CAPACITY (MBH) 1 OUTPUT CAPACITY (MBH) GAS RATE 2 FT.
341426-BIM-A-0108 8 Johnson Controls Unitary Products GAS PIPING Proper sizing of gas piping d epends on the cubic feet per hour of gas flow required, spec ific gravity of the gas and the length of run. National Fuel Gas Code Z223.1 o r CAN/CGA B149.1 or .
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 9 i 4. All piping should be cleaned of dirt and scale by ham- mering on the outside of the pipe and blowi ng out the loose dirt and scale. Before initial start-up, be sure that all of the gas l ines external to the u nit have been purged of air .
341426-BIM-A-0108 10 Johnson Controls Unitary Products T ABLE 7: PHYSICAL DA T A MODEL DY A 036 042 048 060 EV APOR A TOR BLOWER CENTRIFUGAL BLOWER (Dia. x W . in.) 1 1 x 10 1 1 x 10 12 x 1 1 12 x 1 1 F AN MOTOR HP (3 S p eed) 3/4 3/4 1 1 EV APOR A TOR COIL ROWS DEEP 2 3 3 3 FINS PER INCH 15 13 13 13 F ACE AREA (Sq.
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 11 FIGURE 7 - UNIT DIMEN SIONS - FRONT All dimensions are in inches. They are subject to change with- out notice.
341426-BIM-A-0108 12 Johnson Controls Unitary Products FIGURE 8 - UNIT DIMENSIONS - FRONT & BOTTOM 2 6 - 3 / 4 6 4 - 5 / 8 8 - 7 / 8 1 1 - 7 / 8 1 9 - 1 / 4 H I G H V O L T A G E C O N N . 1 - 3 / 3 2 " D I A . K N O C K O U T F R O N T C O N D E N S A T E D R A I N 3 / 4 " ' N P T I G A S S U P P L Y 1 - 5 / 8 " D I A .
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 13 SEQUENCE OF OPERA TION The unit is controlled b y a c onventional heating/cooling ther- mostat common to this class of equipment. HEA TING The control board begins a call for he at when W1 is ener- gized (connected to R).
341426-BIM-A-0108 14 Johnson Controls Unitary Products The control recognize s a call for 2nd stage heat when W2 is energized (connected to "R").
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 15 2. Pressure Switch (PS) - If the draft moto r should fail, the pressure switch prevents the ignition controls and gas valves from being energi zed. 3. Flame Sensor - The flame sensor and controls are located per Proper Fla me Adjustment, Figure 12 .
341426-BIM-A-0108 16 Johnson Controls Unitary Products 2. T urn off all electric power to the appliance if service is to be performed. 3. Remove the control access panel. 4. T urn the gas valve switch to the OFF position. DO NOT FORCE. 5. Replace the control access panel.
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 17 T o adjust the pilot flame: 1. Remove the pilot adjustment cover screw . 2. Adjust the pilot adjustment screw to achieve the p roper pilot flame. 3. Replace the pilot adjustment cover screw after the pilot flame is set.
341426-BIM-A-0108 18 Johnson Controls Unitary Products CHECKING SUPPLY AIR CFM To check the supply ai r CFM after the initial balancin g has been complete d: 1.
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 19 FIGURE 13 - DY A C OIL DELT A P VS. AIRFLOW 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 400 600 800 1000 1200 1400 1600 1800 2000 2200 Ai r f l o w ( .
341426-BIM-A-0108 20 Johnson Controls Unitary Products T ABLE 14: SUPERHEA T CHARGING T ABLE FOR DY A042 OUTDOOR TEMP . °F SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM INDOOR WB TEMP . (°F) 55 57 59 61 63 65 67 69 71 73 75 65 18.0 19.7 21.
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 21 FIGURE 14 - TYPICAL WIRING DIAGRAM DY A 036, 042, 048, 060 (208/2 3 0- 3-60 POWER SUPP L Y).
341426-BIM-A-0108 22 Johnson Controls Unitary Products FIGURE 15 - TYPICAL WIRING DIAGRAM DY A 03 6, 042, 048, 060 (460-3-60 POWER SUPPL Y).
341426-BIM-A-0108 Johnson Controls Unitary Produ cts 23 TYPICAL WIRING DIAGRAM NOTES (SEE FIGURES 14 AND 15) 1. All field wiring to be accomplished following ci ty , local and/or national codes in effect at time of installation of this unit. 2. Caution: Label all wires prior to disconnection when ser- vicing controls.
Subject to change without notice. Pr inted in U.S.A. 341426-BIM-A-0108 Copyright © 2008 b y Johnson Controls, Inc. All rig hts reserved. Supersedes: 284590-BIM-B-0807 Johnson Controls Unita ry Produc.
Ein wichtiger Punkt beim Kauf des Geräts Johnson Controls 341426-BIM-A-0108 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Johnson Controls 341426-BIM-A-0108 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Johnson Controls 341426-BIM-A-0108 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Johnson Controls 341426-BIM-A-0108 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Johnson Controls 341426-BIM-A-0108 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Johnson Controls 341426-BIM-A-0108 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Johnson Controls 341426-BIM-A-0108 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Johnson Controls 341426-BIM-A-0108. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Johnson Controls 341426-BIM-A-0108 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.