Benutzeranleitung / Produktwartung DFS2H318J2A des Produzenten ICP DAS USA
Zur Seite of 15
1 CONTENTS Page 5130261891 9 - A 0606 SAFETY CONSIDERA TIONS ................................ 1 GENERAL ........................................................... 1-4 INST ALLA TION ................................................ 4-1 1 Indoor Unit Installation .
2 T able 1 — Parts List — High W all Units ITEM QTY DIAGRAM Mounting Bracket 2 X 1 DFF2A/DFF2H 09, 12 Long Screws 2 X 8 Outdoor Sensor Connecting Cable 2 X 1 (Available for HEA T PUMP ONL Y) Absor.
3 T able 2 - Physical Data - Cooling Only INDOOR UNIT 2 X DFF2AH09J1A 2 X DFF2AH12J1A COOLING CAP ACITY (Btuh) 2 X 9,000 2 X 1 1,400 SEER 13.0 13.0 SYSTEM CHARGE (Ib)* 2 X 2.4 2 X 3.1 MOISTURE REMOV AL (pt/hr) 2 X 2.6 2 X 4.5 AIRFLOW (3 Speeds) High / Med.
4 2.5-IN. Fig. 2 — Indoor Unit Clearances INST ALLA TION Plan the installation carefully to avoid component failures and make installation easier . Indoor Unit Installation REFRIGERANT LINE ROUTING — The refrigerant lines may be routed in any of the four directions shown in Fig.
5 CAUTION REASSEMBLE 1. Connect the display connector to the display panel printed circuit board. 2. Put the control box cover and grille frame back on using the appropriate screws (Steps 3 and 4 of W ire the Indoor Unit section). Put the grille insert back on.
6 A TT ACH THE REMOTE CONTROLLER MOUNTING BRACKET 1. Use the two screws supplied with the controller to attach the mounting bracket to the wall in the location selected by the customer (see Fig. 10 ). 2. Install batteries in the remote control. 3. Place remote control into remote control mounting bracket.
7 FLARING AND CONNECTING REFRIGERANT LINES 1. Remove the protective cap from the flare fitting. 2. Remove the protective cap from the tubing and cut to the required length. Be sure that the cut is perpendicular and clean, without burrs. 3. Slip the flare nut on the tubing and flare the tube end using standard flaring tools.
8 318J2A 1 15 V AC 19.8 25 18.0 1.00 7.2 42 324J2A 1 15 V AC 2 4.6 3 0 2 2.2 1.00 9.3 58 3095897 3095897 09J1A 30VDC N/A N/A 1.8 1.1 N/A N/A 12J1A 30VDC N/A N/A 1.
9 51302523981-A Models 2 X 09 / 2 X 12 Wiring Diagram Heat pump TB 1 G R / Y E L B L K W H T HL TV BLK * BLUE * BR *GR/YEL FAN J1 K4 K3 K2 K1 DC RTN FAN FUSE 6A W H T RVS BLK RVS B R N FC COMP 1 TB * .
10 51302523982-A Models 2 X 09 / 2 X 12 Wiring Diagram Cooling Only TB 1 G R / Y E L B L K W H T HL TV BLK * BLUE * BR *GR/YEL FAN J1 K4 K3 K2 K1 DC RTN FAN FUSE 6A W H T RVS BLK RVS B R N FC COMP 1 T.
11 ST ART -UP System Checks 1. Conceal the tubing where possible. 2. Make sure that the drainage tube slopes downward along its entire length. 3. Ensure all tubing and connections are properly insulated. 4. Fasten tubes to the outside wall. 5. Seal the hole through which the cables and tubing pass.
12 TROUBLESHOOTING (T ables 6-8, and Fig. 19) T able 6 — Service Indicators LAMP ST A TUS INDICA TION CORRECTION ACTION Check the TH1 thermistor for correct resistance. 1 Flash Faulty TH1 Sensor Check for proper connection. Replace thermistor if necessary .
13 ,, p NO TE: Resistance tolerance ± 3%. TEMPEA TURE ( 0 F) TEMPERA TURE ( 0 C) TEMPERA TURE T OLERANCE ( 0 F) TEMPERA TURE T O LERANCE ( 0 C) MIN IMUM RESI ST AN CE (K ) MEAN RESIST ANCE (K ) MAXIMUM RESIST ANCE (K ) 4.0 20 ±2.0 ±1.1 30.89 32.
14 NO TE: Resistance tolerance ± 3%. TEMPEA TURE ( 0 F) TEMPERA TURE ( 0 C) TEMPERA TURE T OLERANCE ( 0 F) TEMPERA TURE T O LERANCE ( 0 C) MIN IMUM RESI ST AN CE (K ) MEAN RESIST ANCE (K ) MAXIMUM RESIST ANCE (K ) 100.4 38 ±2.0 ±1.1 3.058 3.167 3.277 102.
15 T able 8 — General System T roubleshooting Guide SYM PTOM PROBABLE CAUSE CORRECTIVE ACTION Power supply from outdoor unit to indoor Check for proper connection of power at disconnect. unit is not connected. Power supply to unit not connected Unit Fails to Start.
Ein wichtiger Punkt beim Kauf des Geräts ICP DAS USA DFS2H318J2A (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie ICP DAS USA DFS2H318J2A noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für ICP DAS USA DFS2H318J2A - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von ICP DAS USA DFS2H318J2A reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über ICP DAS USA DFS2H318J2A erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon ICP DAS USA DFS2H318J2A besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von ICP DAS USA DFS2H318J2A verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit ICP DAS USA DFS2H318J2A. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei ICP DAS USA DFS2H318J2A gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.