Benutzeranleitung / Produktwartung ST des Produzenten Hubbell
Zur Seite of 31
OPERATING AND MAINTENANCE MANUAL FOR STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL “ ST and STH ”.
2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: htt p://www.hubbellhe ate rs.co m/ -- IMPORTANT -- Always reference the f ull model num ber and serial number when calling the factory.
3 TABLE OF C ONTENTS SECTION TITLE PAG E # I GENERAL DESCRI PTION AND CONSTRUCTI ON 9 I I INSTAL L ATION AND OPERATI ON 13 III S C H E D U LE D M A IN TE NANC E AND SERVICI NG 18 I V ADJUSTMENT OF TEM.
4.
5.
6 NOMENCLATURE FOR PARTS.
7 NOMENCLATURE FOR ACCE SSORY PARTS.
8.
9 SECTION I - GENERAL DESCRIPTION AND CONST RUCTION GENERAL DESCRIPTION This book describes a packaged steam powered water heater that is a stationary , self-contained unit.
10 3. Stainless Steel – Stainless steel (ty pe 304, 316, or 316L) is well suited for high purity applications requiring a corrosion resistant tank with minimal leaching of impurities into the water. Well suited for process, RO, and DI water sy stems in the pharmaceutical, food, and electronic industries.
11 STEAM OPERATING CONTROLS The steam operating controls are factory selected, sized, piped, and tested to ensure reliable operation. Steam controls can be shipped loose, upon request, for in the field installation by others. All steam components are factory plumbed with schedule 40 black iron pipe and ready for steam and condensate connections.
12 OPTIONS The following optional features may be included in your water heater. Reference the drawing specific to y our heater for further details. Single Solenoid Safet y System A single solenoid safety system closes the steam supply to the control valve should the temperature in the tank reach the high limit set point.
13 SECTION II – INSTALLATION AND OPERATION WARNING / CAUTION DO NOT TURN ON THE STEAM SUPPL Y to this unit until hea ter is completely filled with water and all air has been released. If the heater is NOT filled with water when the steam supply is turned on, damage to the heating coil may result.
14 3. I nstall the combination temperature and pressure safety relief valve in the tapping provided. Note that this is required by law for safety considerations. Outlet to floor drain I n s t a l l i n t o p r o v i d e d t a p p i n g Manual Release Lev e r T e m p e r a t u r e P r o b e 4.
15 Typical Piping Diagram ELECTRICAL IN STALLATION 1. If the unit is furnished with a pilot or self contained control valve, no external source of power is required for the valve. (See enclosed operation and maintenance manual for specific valves). 2.
16 FILLING THE HEATER 1. Begin with all steam, condensate, and water valves closed. 2. Open the isolation valves on the integral circulator line ,if supplied. 3. Open cold water valve, fill unit with cold wate r. L ift lever on relie f valve to relieve trapped air.
17 SHUTDOWN 1. Close valve to heating medium and air supply valve, if air operated controls are furnished 2. Disconnect all el ectrical power to uni t. 3. Close hot water outlet valve. 4. Close building recirculation inlet valve, and shut down building circulation pump.
18 SECTION III - SCHEDULED MAINTE NANCE AND SERVICING WARNING / CAUTION Before performing any maintenance procedure, make certain steam supply and electrical power supply is OFF and cannot accidentally be turned on. QUARTERLY INSPECTION 1. Monitor thermostat a.
19 11. Convection packages may be equipped with an integ ral circulator. This circulator should be serviced per the enclosed pump O&M manual. 12. The unit as well as all strainers should be blown down regularly to remove any trash, and sediment that may have accumulated.
20 occur at this point, but a s the gasket se ats, leaking will g radually stop). After leak ing has stopped, turn the nut approximately 1 revolution. At this point there may be some miner seepage, wait a few minutes to see if this seepage stops.
21.
22.
23 SINGLE SAF ETY SOLENOID SYSTEM (if inst alled).
24 DOUBLE SAF ETY SOLENOID SYSTEM (if installe d).
25 SECTION IV – ADJUSTMENT OF TEMPERATURE RE GULATORS 1. The spring tension on temperature regulators is adjusted at the factory to meet design conditions. However, design conditions may vary from actual operating conditions and re- adjustment might be required on this job.
26 f. Apply air pressure to valve diaphragm so that stem halves are aligned and re-connect stem halves. g. If valve will not open with air on the diaphrag m, spring tension should be decreased. h. Adjustment is essentially the same as if spring tension wer e increase d except the adjustment screw is turned in the opposite direction.
27 c. Spence Valv es : There is no main spring adjustment on Spence Valves. To set temper ature on the water heater: (1) Turn pilot spring a djustment “A” cloc kwise until all tension is off the spring. (2) Refer to unit sta rt-up section a nd start unit except for the rmostat setting .
28 SECTION V – TROUBLESHOOTING (See separate component O &M for add itional d etails.) Symptom Probable Cause Corrective Action / Remedy T u b es a r e f o u l e d . C l e a n t u b e s p er S e c t i o n III, a nnual scheduled maintenance. Excess silt in bottom of tank.
29 High rate of flow bey ond design conditions. Consult factory . Excessive vibration. Under sized piping to the unit. Re-pipe lines to unit using proper sized lines. Defective steam t rap. Repair or replace per separate O&M. Undersized condensate lines.
30 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI L I CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.
31 METRIC CONVERSIONS.
Ein wichtiger Punkt beim Kauf des Geräts Hubbell ST (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Hubbell ST noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Hubbell ST - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Hubbell ST reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Hubbell ST erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Hubbell ST besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Hubbell ST verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Hubbell ST. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Hubbell ST gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.