Benutzeranleitung / Produktwartung HBH 072 - 120 des Produzenten Heat Controller
Zur Seite of 30
W a ter Sour ce Hea t Pump Systems SUBMITT AL DA T A Unit Designation Job Name Architect Engineer Contractor PERFORMANCE DA T A Cooling Capacity BTUH EER Heating Capacity BTUH COP Ambient Air o F Ente.
.
Submittal Data HBH SerieS Heat Contr oller , Inc. 1 Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 1 Selection Procedure .....................................................................................................................
Heat Contr oller , Inc. HBH SerieS Submittal Data 2 Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 2 LW T = EW T - HE GPM x 500 LA T = EA T + HC CFM x1.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 3 Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 4 Model Nomenclature Heat Controller OEM Price List HBH Large Com pact Hor izonta l Units Entering W ater Temperature Range: 20 - 120° F (-6.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 5 P er formance Data AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 6 F or operation in the shaded area when wat er is used in lieu of an anti-freeze solution, the L W T (Leaving Water T emperatur e) must be calculated.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 7 P er formance Data: HBH072 Performance capacities shown in thousands of Btuh 2400 CFM Nominal Airow Heating & Cooling W A TER/BRINE Cooling - EA T 80/67°F Heating - EA T 70°F EWT °F FL OW gpm PD psi PD ft.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 8 P er formance Data: HBH096 Performance capacities shown in thousands of Btuh 3200 CFM Nominal Airow Heating & Cooling W A TER/BRINE Cooling - EA T 80/67°F Heating - EA T 70°F EWT °F FL OW gpm PD psi PD ft.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 9 P er formance Data: HBH120 Performance capacities shown in thousands of Btuh 4000 CFM Nominal Airow Heating & Cooling W A TER/BRINE Cooling - EA T 80/67°F Heating - EA T 70°F EWT °F FL OW gpm PD psi PD ft.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 10 Air Flow C orrection T able Entering Air Correction T able HBH P er formance Data Corre.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 11 Antifreez e Correction T able Antifreeze T ype Antifreeze % Cooling Heating WPD Corr . F ct. EW T 30°F EW T 90°F EW T 30°F T otal Cap Sens Cap Po we r Htg Cap Powe r Wat e r 0 1.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 12 Blower P er formance Data HBH072 - Standard Unit All Data is Wet Coil SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 13 Blower P er formance Data HBH096 - Standard Unit All Data is Wet Coil SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 14 Blower P er formance Data HBH096 - Standard Unit SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 3300 BHP 1.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 15 Blower P er formance Data HBH120 - Standard Unit All Data is Wet Coil SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 16 Blower P er formance Data HBH120 - Standard Unit All Data is Wet Coil T able Continued from Pr evious Page SCFM ESP 0.00 0.10 0.20 0.30 0.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 17 HBH Phy sical Data Model 072 096 120 Compressor Quantity Scroll Number of Circuits (C ompressors) 2 F actory Charge R-410a (oz) [kg] per circuit 60 [1.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 18 HBH072-120 Dimensional Data DIMENSIONAL DA T A T ABLE ON NEXT P AGE LEFT RETURN STRAIGH.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 19 HBH072-120 Dimensional Data Model Overall Cabinet Discharge Connections Duct Flange Wat.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 20 HBH Electrical Data Standard HB Model V oltage Code Rated V oltage V oltage Min Max Blower Option Compressor Fan Motor FLA T otal Unit FLA Min Circuit Amp Max F use/ HACR QT Y RLA LRA 072 H 208-3-60 197/254 A, B, C 2 10.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 21 T ypical W iring Diagram Three P hase HBH072-120 With CXM C ontroller.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 22 Th is pro du c t s pe ci fic a tio n d oc ume nt is fur ni she d as a m ea ns to co py an d pa s te Cl ima te Ma s te r p rod uc t i n forma tio n i nto a proje c t spec i fic a tio n.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 23 HBH Series 60H z Engineering Specications Page 2 General: Furnish and install the HBH Series as indicated on the plans. Equipment shall be completely assembled, piped and internally wired.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 24 HBH Series 60H z Engineering Specications Page 3 Fan and Motor Assembly: All units shall have belt-driven single centrifugal fan. Fan motor shall be permanently lubricated with thermal overload protection.
Submittal Data HBH SerieS Heat Contr oller , Inc. Engineering Design Guide HBH SERIES Heat Contr oller , Inc. 25 HBH Series 60H z Engineering Specications Page 4 Option: The unit shall be supplied with stainless steel drain pan.
Heat Contr oller , Inc. HBH SerieS Submittal Data Heat Contr oller , Inc. HBH SERIES Engineering Design Guide 26 Hose Kit Assemblies: The following assemblies ship with the valves already assembled to the hose described: a. Supply and return hoses having ball valve with PT port.
.
06/2012 04/2009 1 1/2010.
Ein wichtiger Punkt beim Kauf des Geräts Heat Controller HBH 072 - 120 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Heat Controller HBH 072 - 120 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Heat Controller HBH 072 - 120 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Heat Controller HBH 072 - 120 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Heat Controller HBH 072 - 120 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Heat Controller HBH 072 - 120 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Heat Controller HBH 072 - 120 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Heat Controller HBH 072 - 120. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Heat Controller HBH 072 - 120 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.