* Gas data on gross value ** Gas consumption at 15°C and 1013.25 mbar *** 3P (G31)

A 1390 1910 1910 1910 2060 2060 C - 530 530 D 705 850 850 E - 1000 1000 F - 900 900 G 80/125 100/150 100/150 100/150 130/200 130/200 H 1365 1905 1905 1905 2015 2015 Hx 265 310 310 Hy 375 440 440 K 1270 1800 1800 1800 1855 1855 M 170 160 160 160 225 225 N 1390 1910 1910 1910 2060 2060 Ny 205 P 170 175 175 175 290 290 R 85 75 75 75 225 225 S 900 1410 1410 1410 1425 1425 W 125 145 145 145 240 240
1 Cold water (external) R11/2 2 Hot water (external) R11/2 3 Gas control (internal) Rp3/4 4 Tank drain valve (internal) 3/4 5 T&P valve (internal) 1-11.5 NPT 6 Cleaning and inspection opening 95x70 7 Condensation drainage (internal) Ø40 (BFC 28) Rp 1 (BFC 30-100)
Dimensions in mm. All Cyclone BFC water heaters receive a three years warranty on the tank and one year on parts.





1 Pressure reducing valve 3 T&P valve 4 Stop valve 5 Non-return valve 6 Circulation pump 9 Drain valve 10 Gas cock 11 Isolating valve 12 Temperature gauge 13 Condense drain 14 Hot water outlets 15 Expansion relief valve 16 Expansion vessel 17 Three way valve 18 Water tank 19 Float valve
A Cold water B Hot water C Return circulation D Gas supply E Overfl ow pipe H Expansion vent pipe
A.O. Smith unvented system kits utilise combination valves.
Further installation and connection details can be found in the Installation & Commissioning Manual.


TERMINAL STRIP CONNECTIONS Earth N Neutral L1 Phase input of controller L2 Phase input of isolating transformer (primary side) L3 Phase output of isolating transformer (secondary side) L4 Phase input of program-controlled pump L5 Phase input of continuous pump
CONTROLLER CONNECTIONS J1 Connector for display to controller J2 Connector for power supply to controller J19 Connector for extra error signal J20 Connector for gas control J21 Connector for program- controlled pump J24 Connector for fan JP2 Connector for ionisation rod and glow igniter JP3 Connector for temperature sensor T2 JP4 Connector for dummy JP5 Connector for temperature sensor T1 JP6 Connector for selection resistor and pressure switch JP8 Connector for extra ON mode switch
COMPONENTS A Controller B Ionisation rod C Glow igniter D Gas control E Burner earth connection F Extra ON mode switch G Continuous pump H Program-controlled pump J Extra error signal K Isolating transformer L Double-pole mains switch M ON/OFF switch control N Display/Flat cable O Fan P Temperature sensor (T2 - bottom of tank) Q Dummy R Temperature sensor (T1 - top of tank) S Selection resistor T Pressure switch
F1 Fuse F2 Fuse
Colour cables 1 = brown 2 = blue 3 = yellow/green 4 = black 5 = white (flat cable) 6 = grey/beige
TERMINAL STRIP CONNECTIONS Earth N Neutral L Phase input of controller L1 Phase output of isolating transformer ( secundary side) L2 Phase input of isolating transformer ( primary side) L3 Phase input of program- controlled pump L4 Phase input of frequency controller L5 Phase input of continuous pump
CONTROLLER CONNECTIONS J2 Connector for power supply to controller J19 Connector for external error-signal J20 Connector for gas-control J21 Connector for program controlled pump J36 Connector for display to controller J39 Connector for fan controlled signal JP2 Connector for ionisation rod and glow ignitor JP3 Connector for temperature sensor T2 JP4 Connector for dummy JP5 Connector for temperature sensor T1 JP6 Connector for selection resistor, pressure switch and anode signaling JP8 Connector for extra ON-mode switch
COMPONENTS A Controller B Ionisation rod C Glow ignitor D Gas control E Burner earth connection F External ON-mode switch G Program-controlled pump H External error-signal J Isolating transformer K Double-pole mains switch L Controller 0/1 switch M Display/Flat cable N Fan O Temperaturesensor (T2-bottom of tank) P Dummy Q Temperaturesensor (T1-top of tank) R Selection resistor S Pressure switch T Potentiostat U Frequency controller V Argus-link interface W Electric anodes X Signaling for electric anodes Y Mains choke and EMC filter
F1 Fuse F3 Fuse
Colour cables 1 = brown 2 = blue 3 = yellow/green 4 = black 5 = white (flat cable) 6 = grey/beige 7 = red 8 = green

A Cyclone BFC water heater should be installed according category B23, C13, C33, C43 or C53*.
Diameter (mm) 80/125 100/150 100/150 100/150 130/200 130/200
Max. length (m) 40 40 40 15 15 15
Max. 45/90° bends 7 7 7 4 3 3
Diameter (mm) 80 100 100 100 130 130
Max. length (m) 25 80 45 25 115 60
Lequivalent/bend 90° (m) 3,9 4,6 4,6 4,6 2,4 2,4
Lequivalent/bend 45º (m) 1,1 1,2 1,2 1,2 1,4 1,4
Parallel (larger diameter for more length)
Diameter (mm) 100 130 130 130 150 150
Max. length (m) 100
Lequivalent/bend 90º (m) 4,6 2,4 2,4 2,4 2,6 2,6
Lequivalent/bend 45º (m) 1,2 1,4 1,4 1,4 1,6 1,6
* All Cyclone BFC are also approved for installations where the unit is supplied
without venting materials (C63).
Concentric flues It is not permitted to use more than the specified number of bends, even when the duct is shorter than the maximum length. A 45° bend is equivalent to a 90° bend.
Parallel flues - The maximum permissible length should be reduced by the equivalent length of each bend. (Note: for a parallel installation this means that 3 changes in direction amount to 6 bends (3 in the supply duct and 3 in the flue). - The maximum length also applies if a parallel installation has different supply and flue duct lengths (B23, C53). - Combined flues (C43) shall be fitted with a condensate drain.
Minimal space for wall duct (mm)
W 725 790 790 790 940 940
X 1535 2075 2075 2075 2230 2230
Y 1460 1480 1480 1480 1620 1620
Terms and conditions apply, please refer to our website
Data subject to change INT/1108/BFC/04
Minimal space for roof duct (mm)
W 680 1035 1035 1035 1120 1120
X 2965 3325 3325 3325 3620 3620
X ** 2015 2375 2375 2375 2670 2670
Y 1575 1415 1415 1415 1560 1560
Y ** 625 465 465 465 610 610
For the parts numbers of components and flue gas ducts, etc. please refer to the “Maintenance and accessories” chapter.
* Distance without concentric pipe between bend and wall duct. ** Distance without concentric pipe between appliance and roof duct.
Concentric · Parallel (standard diameter)