All information contained herein is subject to change without notice. I NST ALLA TION I NSTRUCTIONS F OR L IGHT C OMMERCIAL S ELF -C ONT AINED P ACKAGED H EA TING & C OOLING U NIT 15 & 20 T ON CPC RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
2 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering rep air part s, give the complete unit model and serial numbers as stamped on the unit’ s nameplate. Replacement parts for this appliance are available through your contractor or local distributor .
3 WARNIN G T O PREVE NT THE RISK OF PROPERT Y DAMAGE, PERSONAL INJUR Y , OR DEATH, DO NOT STORE COMB USTIBLE MATERI ALS OR USE GASOLI NE OR OTHER FLAM MA BLE LIQ U I DS O R VA PO RS I N TH E V ICIN ITY OF THIS APP LIAN CE.
4 UNIT LOCA TION T O PRE VENT PO SSIBL E EQ UIPMEN T DAMAGE , PROP ERT Y DAMAG E , PERSO NAL INJURY OR DEATH , THE FOLLOW I NG BULLET PO INTS MU ST BE OBSE RVED WHEN INSTALLING THE UNIT . W ARNING IMPORT ANT NOTE: Remove wood shipping rails prior to installation of the unit.
5 • Do not skid or slide on any surface as this may damage unit base. The unit must be stored on a flat, level surface. Protect the condenser coil because it is easily damaged.
6 A LL CURBS LOOK SIM ILAR . T O AVOID INCO RRECT CURB PO SITI ONING , CHECK JOB PLANS CAREFU LLY AND VER IFY MARKIN GS ON CURB ASSEM BLY . I NSTRUC TIO NS MAY VARY IN CURB STY LES AND SUP ERSED ES INFORM ATION SHOW N . CAUTION See the manual shipped with the roof curb for assembly and installation instructions.
7 RIGGING DET AILS WARN I NG T O PREVENT PROPERTY DAMAGE, THE UNI T SHOULD REMAIN IN AN UPRIGHT POSITION DURI NG ALL RIGGING AN D MOV ING OPERATIONS. T O FACILITATE LIFTING AND MOVING WHEN A CRANE IS USE D, PLACE THE UNIT IN AN ADEQUATE CABLE SL ING. D O NOT LIFT UNIT S TWO AT A TIME .
8 CP C W e i g ht s (lbs ) CP C W eigh t s (l b s ) 1 5 T o ns 2 0 To n s Corner W eigh t - A 580 655 Corner W eigh t - B 540 535 Corner W eigh t - C 475 510 Corner W eigh t - D 440 420 Unit Shi ppi n.
9 CAUTIO N T O AVOI D PROPERTY DAMAGE O R PERSO NAL INJURY DUE TO FIRE , USE ONLY COPPER CO NDUCTORS. L ABEL ALL WIRES PRI OR TO DISCONN ECTI ON WHEN SER VIC ING CONTR OLS . W IRING ERRORS CAN CAUSE IMP ROPER AND DANG EROU S OPERATION . V ERI FY PR OPER OPERATION AFTER SER VIC ING .
10 3. Use #18 A WG wire for 24V control wiring runs not exceeding 75 feet. Use #16 A WG wire for 24V control wiring runs not exceeding 125 feet. Use #14 AWG wire for 24V control wiring runs not exceeding 200 feet. Low voltage wiring may be National Electrical Code (NEC) Class 2 where permitted by local codes.
11 P RE -S TARTUP I NSTRUCTIONS T O PRE VENT PROP ERT Y DAMAG E OR PERSO NAL INJURY , D O NOT START THE UNIT UNTI L ALL NECE SSARY PRE - CHECK S AND TESTS HAVE BEEN PER FORM ED . CAUTION Prior to the beginning of S t artup, Adjustments, and Checks procedures, the following steps should be completed in the building.
12 System V oltage - That nominal volt age value assigned to a circuit or system for the purpose of designating its volt age class. Nameplate V olt age - That voltage assigned to a piece of equipment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate.
13 R EFRIGERATION S YSTEM C HECKS Ensure the hold-down bolts on the compressor are secure and have not vibrated loose during shipment. Check that vi- bration grommets have been inst alled. Visually check all pip- ing and clamps. The entire refrigeration system has been factory charged and tested, making it unnecessary to field charge.
14 MOTOR SHEA VE ADJUSTMENTS V L , V M & 2 VP V ARIABLE P ITCH K EY T YPE M OTOR S HEAVES The driving and driven motor sheaves should be in align- ment with each other and the shafts p arallel. V L & V M S HEAVES A DJUSTMENT 1. Loosen set screw “B” using a 5/32" Allen key .
15 C LEAN O UTSIDE C OIL (Q UALIFIED S ERVICER O NLY ) The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris.
16 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - ST ANDARD NOTES: High static airflow requires installation of high st atic kit (HSKT240), or factory-built High S t atic model. Unit factory shipped with sheave set at 2.5 turns open. Air flow table represent dry coil with filters inst alled; SCFM correction factor for wet coil is 4%.
17 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - HIGH ST A TIC NOTES: High static airflow requires inst allation of high static kit (HSKT240), or factory-built High S t atic model. Unit factory shipped with sheave set at 2.5 turns open. Air flow table represent dry coil with filters inst alled; SCFM correction factor for wet coil is 4%.
18 APPENDIX B ELECTRICAL DA T A A TTENTION INST ALLING PERSONNEL Use only the heater kit specified for each model as dict ated by the t able above. MI N MAX Q ty R L A L R A Qt y H P R L A HP FL A 20 8/ 230 -60-3 1 87 253 2 33 . 3 23 9. 0 3 1 / 3 2. 40 BD S T D STAT IC 5 .
19 APPENDIX C UNIT DIMENSIONS VERTICAL DISCHARGE (TOP VIEW) 21” 60 ” 7” 48” 22” B C D A B C D A Mo d el A BCD 15 T o n 20 T o n 133- 1/2" 88 - 7 / 3 2" 50 - 9 / 3 2" 5 - 5/ 32.
20 © 2010 Goodman Manufacturing Company , L.P . 5151 San Felipe, Suite 500 Houston, TX 77056 www .goodmanmfg.com www .amana-hac.com.
Ein wichtiger Punkt beim Kauf des Geräts Goodman IO-367B (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Goodman IO-367B noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Goodman IO-367B - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Goodman IO-367B reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Goodman IO-367B erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Goodman IO-367B besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Goodman IO-367B verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Goodman IO-367B. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Goodman IO-367B gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.