GE Consumer & Industrial Power Protection L P S 3 3 U _ 0 3 0 - 0 4 0 _ U P S _ G E _ 0 1 D i g i t a l E n e r g y T M L P S e r ie s Operating Manual Uninterruptible Power supply Digital Energy.
Modif icati ons rese rved Page 2/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Model: LP 33 Series / 30 & 40 kVA / Series 0 Date of issue: 01/01/2005 File name: OPM_LPS_3UO_30K_ 40K_0US_ V010 Revision: 1.0 Identification No.
Modif icati ons rese rved Page 3/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Dear Customer , We thank you for select ing our products and are please d to count you a mongst our very valued cust omers at GE .
Modif icati ons rese rved Page 4/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Preface Congratu lations on your choice of a LP 33 Series Uninterruptible Power Supply (UPS). It will help eliminate load disturbances due to unexpected power problem.
Modif icati ons rese rved Page 5/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Table of contents Page 1 SAFETY RULES .............. ............... .................. .............. .................. .............
Modif icati ons rese rved Page 6/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 1 SAFETY RULES With this document, GE gives to the user all the necessary inf orm ation about the correct use of the UPS. We recommend that this manual be k ept next to the UP S for future refe rences.
Modif icati ons rese rved Page 7/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA SAVE THESE INSTRUCTIONS This manual contains important instructions for model s L P 3 3 S e r i e s / 1 0 & 2 0 k V A that should be followed during installa tion and maintenance of the UPS and bat tery.
Modif icati ons rese rved Page 8/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Safety symbols and warnings Safety warnin gs The text of this manual contains some warnings to avoid risk to the persons and to avo id damages to the UPS system and the supplied critical loads.
Modif icati ons rese rved Page 9/ 57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 2 INTRODUCTION 2.1 GENERAL DESCRIPTION The LP 3 3 Series Uninterruptible Power Suppl.
Modif icati ons rese rved Page 10/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3 DESCRIPTION 3.1 BLOCK DIAGRAM AND MAIN ELEMENTS DESCRIPTION Fig.
Modif icati ons rese rved Page 11/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3.2 OPERATION MODES This section describes the different possib le operatio n modes of the UPS explaining the funct ion of the main modules of the UPS.
Modif icati ons rese rved Page 12/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Automatic bypass opera tion In VFI (Voltage Freq uency Indepe ndent) operation mode,.
Modif icati ons rese rved Page 13/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Manual bypass operation The manual bypass circuit consisti ng of Q1 and Q2 manual switches, permits the transfer of the load directly to the mai ns without interruption, leaving the UPS galvanically se parated from the output load .
Modif icati ons rese rved Page 14/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3.3 RPA PARALLEL SYSTEM The RPA (Redundant Paralle l Architectur e) allows to extend.
Modif icati ons rese rved Page 15/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3.4 UPS PARALLELED ON THE SAME BATTERY NOTE ! A parallel system with a Common Batter.
Modif icati ons rese rved Page 16/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3.5 SERVICE AND TECHNICAL SUPPORT For any request of technical support please contact the supplier who provided the syste m.
Modif icati ons rese rved Page 17/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3.6 RECYCLING AT THE END OF SERVICE LIFE NOTE ! This product has been designed to respect the environment, using ma terials and components respecting eco-design rules.
Modif icati ons rese rved Page 18/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 4 LAYOUT 4.1 LAYOUT LP 33 Series / 30 & 40 kVA Fig. 4.1-3 Control panel L P S 3 3 U _ 0 3 0 - 0 4 0 _ U P S _ G E _ 0 1 D i g i t a l E n e r g y T M L P S e r i e s Fig.
Modif icati ons rese rved Page 19/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 5 SYSTEM HANDLING 5.1 CONTROL PANE L Fig.
Modif icati ons rese rved Page 20/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 5.2 COMMAND PUSH BUTTONS AND SWITCHES total off Press simultane ously the keys “ Alarm ” and “ - ” on the panel.
Modif icati ons rese rved Page 21/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6 LCD SCREEN Shows the U PS sys tem d ata , even ts messages and UPS setting.
Modif icati ons rese rved Page 22/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA MAINS f=60.0Hz U1=120V U2=119V U3=121V 1. Mains input voltage information screen. 2. Mains input frequency. 3. Mains line voltage L1 (A) and L2 (B)phases.
Modif icati ons rese rved Page 23/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6.2 EVENT SCREENS (Alarm) Each o f the fo llo wing listed alarms or messages can be displayed on the L CD screen or transmitted to a PC through the serial port RS232 or the SNM P card (opt ional).
Modif icati ons rese rved Page 24/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Code Alarm Meaning 4118 BATTERY FAULT During battery test the DC voltage falls under the critical level. If the boost voltage has not been reached within 24 hours, then the charge voltage re turns to floating voltage .
Modif icati ons rese rved Page 25/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Code Alarm Meaning 4520 NO INVERTER POWER The load supplied by utility is over 100%. The load remains blocked on utility as long as alarm overload is active.
Modif icati ons rese rved Page 26/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6.2.2 Messages list Are define d messages : all the recorded events which are referred to the operation status coherent with the normal sit uation of t he UPS.
Modif icati ons rese rved Page 27/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Code Message Meaning 4362 INVERTER OFF The command to switch OFF the inver ter has been done by the control panel or automatically for alarm detection.
Modif icati ons rese rved Page 28/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Code Message Meaning 4602 Q1 OPEN The auxiliary contact indicates th at the output switch Q1 has been open ed. 4603 Q1 CLOSED The auxiliary contact indicate s that the output sw itch Q1 has been clo sed.
Modif icati ons rese rved Page 29/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6.2.3 Event report LP 33 Series In case of failure or malfuncti on, before calling the nearest Service Centre please note the most important identification data of your UPS and the most recent events di splayed.
Modif icati ons rese rved Page 30/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6.3 MENU SCREENS (Menu) Pressing the menu keypad a series of screens will be display.
Modif icati ons rese rved Page 31/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6.3.1 User parameters screen This screen allows the user to modify some parame ters permitting to adapt some functions of the UPS to his/her needs, descr ibed as follows.
Modif icati ons rese rved Page 32/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3. Telephone numbers set-up Tel1: Tel1 enabled: N Tel2: Tel2 enabled: N Tel1 : This parameter specifies a first tel. number to be used for modem dial-out.
Modif icati ons rese rved Page 33/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 2. d1 ÷ d7: Enabling time in function of weekdays . For the weekdays from d1 to d7 ( Saturday to Friday ) the edit mode (edit day) allows to define time intervals when the UPS i s operating in ECO Mode .
Modif icati ons rese rved Page 34/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA Example 4 : If the ECO Mo de must be enabled on Monday ( d3 ) and Tuesday ( d4 ) bet.
Modif icati ons rese rved Page 35/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7 OPERATION 7.1 PROCEDURES FOR SINGLE LP 33 Series 7.
Modif icati ons rese rved Page 36/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3. Switch On the output switch Q1 (Pos.
Modif icati ons rese rved Page 37/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.1.2 UPS shutdown with load transfer on manual bypass (Q2) The purpose of this procedure is to su pply the load directl y by mains through ma nual bypass Q2 .
Modif icati ons rese rved Page 38/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6. In order to d ischarge the DC link capacitors, start once more the inverter throu.
Modif icati ons rese rved Page 39/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.1.3 Start-up following the operation on manual bypass (Q2) This procedure presupposes that the load is powered by the manual bypass switch: • The inverter is switched OFF; • The manual bypas s switch Q2 is switched ON (pos.
Modif icati ons rese rved Page 40/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.1.4 Complete shutdown As a result of t his procedure the UP S is completely switched OFF and not powere d. NOTE ! This procedur e involves al l equipment power ed by UPS, to be shut down.
Modif icati ons rese rved Page 41/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.1.5 Restore to normal ope ration after “to tal off” NOTE ! Make sure the U PS to be statu s of the activa tion of “ total off” , i.
Modif icati ons rese rved Page 42/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.1.6 Restore to normal ope ration after “EPO – Emergency Power Off” NOTE ! M ak e s u r e t h e U P S t o b e s t a t u s o f t h e a c ti v a t i on o f “ EPO ” , i.
Modif icati ons rese rved Page 43/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2 PROCEDURES FOR PA RALLEL SYSTEM LP 33 Series 7.
Modif icati ons rese rved Page 44/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 3. Switch ON the output s wit ch Q1 (Pos. I) on each unit . When the last Q1 will be closed, the output will b e supplied by the mains through all bypass .
Modif icati ons rese rved Page 45/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2.2 Parallel UPS shutdown with lo ad transfer on manual bypass (Q2) The purpose of this procedure is to su pply the load directl y by mains through ma nual bypass Q2 .
Modif icati ons rese rved Page 46/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 6. In order to discharge the DC link cap acitors, start once more the inverter on ea.
Modif icati ons rese rved Page 47/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2.3 Star t-up following th e operation on maint enance bypass (Q2) This procedure .
Modif icati ons rese rved Page 48/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2.4 Shutdown of a single unit in a parallel system With purpose to separate one unit from the parallel system.
Modif icati ons rese rved Page 49/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2.5 Start-up an additional unit in a parallel system Before connecting hazar dous .
Modif icati ons rese rved Page 50/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2.6 Complete shutdown of a parallel system As a result of this procedure the parallel system is completely switched OFF and not powered.
Modif icati ons rese rved Page 51/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2.7 Restore to normal ope ration after “to tal off” NOTE ! Make sure the all units of the parallel system to be status of the activation of “ total off” , i.
Modif icati ons rese rved Page 52/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 7.2.8 Restore to normal ope ration after “EPO – Emergency Power Off” NOTE ! Make sure the all units of the paralle l system to be status of the activation of EP O , i.
Modif icati ons rese rved Page 53/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 8 OPTIONS 8.1 OPTI ONS GENERAL VI EW LPS33U_030-0 40_RPA system _GE_01 LP 33 Series .
Modif icati ons rese rved Page 54/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 9 MAINTENANCE WARNING ! All mainten ance and serv ice works m ust be performed by QUALIFIED SERVICE PER SON. 9.1 GENERAL MAINTENANCE When used properly, t he LP 33 Series UPS is virtually maintenance free.
Modif icati ons rese rved Page 55/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 9.4 SERVICE REQUIRED LP 33 40 kVA APPLICATION ON UPS = 70% SERVICE REQUIRED If this .
Modif icati ons rese rved Page 56/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA 10 NOTES 10.1 NOTES FORM It is recommended to note in this section Notes , with date and short de scription all the operations performed on the UPS, as: maintenance, compon ents replacement, abnormal situations, etc.
Modif icati ons rese rved Page 57/57 OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA RIDER FOR WARRANTY FOR SALE OF SitePro TM , DIG ITAL ENERGY TM SG Serie s and LP Series UPS.
Ein wichtiger Punkt beim Kauf des Geräts GE LP 33 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie GE LP 33 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für GE LP 33 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von GE LP 33 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über GE LP 33 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon GE LP 33 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von GE LP 33 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit GE LP 33. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei GE LP 33 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.