Benutzeranleitung / Produktwartung FVR-C9S-2UX Drive Series des Produzenten GE
Zur Seite of 40
1 FVR-C9S-2UX Instruction Manual FVR-C9S-2UX Drive Series Three-phase 230 V AC Input T ype.
2 FVR-C9S-2UX CAUTION • Make sure that you r ead this instruction manual thoroughly before installing, wiring, operating and inspecting this drive. • Please make sure that this instruction manual accompanies the drive to the end user .
3 FVR-C9S-2UX Thank you for pur chasing the Fuji “FVR-C9S” drive, marketed by GE Fuji Drives USA, Inc. This instruction manual is included with the drive and equipment and is pr ovided for the convenience of the end user . Please be sure it accompanies the drive.
4 FVR-C9S-2UX 0. Safety Precautions Before carrying out installation, wiring, mainte- nance or inspection of the drive, read this in- struction manual thoroughly to gain a full under - standing of the correct operation pr ocedures. Make sure that you have r ead all product details, safety information, warnings and cautions before use.
5 FVR-C9S-2UX CAUTION: Do not touch the cooling fins, as they become hot during drive operation. Because it is relatively easy to set the drive to high speed operation, be sure to check the capacity of the motor and the equipment being operated before changing the drive function setting.
6 FVR-C9S-2UX UL/CSA W ARNING / A VERTISSEMENT Hazard of electrical shock. Disconnect incoming power before working on this contr ol. Risque de choc electrique. Couper l’alimentation avant le depannage de sette commande. More than one live cir cuit.
7 FVR-C9S-2UX 1. T ype 2. Phase: 3PH - thr ee-phase 3. V oltage range: 200V - 230V - AC200V Series 4. Frequency: 50/60Hz 5. Rated output capacity 6. Rated output curr ent 7. Output frequency range: 1- 120 Hz 8. Serial No. 2. Part Names 1. Drive Cover 2.
8 FVR-C9S-2UX Type (FVR _ _ _ C9S-2UX) F12 F25 F50 001 002 003 005 Applicable motor output 1 [Hp] 1/8 1/4 1/2 1 2 3 5 Rated capacity 2 [kVA] 0.28 0.56 1.0 1.6 2.8 4.0 6.6 Voltage [V] Three-phase 200-230V 50/60 Hz (Output voltage is proportional to input voltage) Output Rating Rated current [A] 0.
9 FVR-C9S-2UX Type (FVR _ _ _ C9S-2UX) F12 F25 F50 001 002 003 005 Applicable motor output 1 [Hp] 1/8 1/4 1/2 1 2 3 5 Frequency setting Key operation: Setting with UP/DOWN keys Potentiometer: Terminal for 1-5K ohm VR is provided Analog signal: 0-5 VDC 0-10 VDC (input resistance = 22k ohm) Display Run mode Output frequency is displayed.
10 FVR-C9S-2UX 5. External Dimensions 3.15 (80) 2.64 (67) 2 - 0.20 X 0.24 (2 - 5 X 6.2) 0.26 (6.5) .06 (1.5) 0.26 (6.5) 4.72 (120) 1.97 (50) 2.76 (70) DWG 1: FVRF12C9S-2UX to FVROO1C9S-2UX 0.20 (5) 0.39 (10) 4.33 (110) 3.94 (100) 0.20 (5) 0.39 (10) 2.
11 FVR-C9S-2UX 3.86 (98) 2 - dia. 0.20 (2 - dia. 5) 0.24 (6.2) 0.18 (4.5) 0.24 (6.2) DWG 2: FVR002C9S to FVR003C9S-2UX 0.24 (6) 0.45 (11.5) TERMINAL M3.5 D1 0.24 (6.2) 0.24 (6.2) D D2 0.24 (6.2) 4.65 (118) 4.21 (107) 4.33 (110) 5.12 (130) 0.20 (5) 1.97 (50) 3.
12 FVR-C9S-2UX 5.04 (128) 2 - dia. 0.20 (2 - dia. 5) 0.24 (6.2) 0.71 (18) 0.24 (6.2) FVR005C9S-2UX 0.24 (6.2) 0.45 (11.5) TERMINAL M4 3.37 (85.5) 0.24 (6.2) 0.24 (6.2) 5.45 (138.5) 2.87 (73) 0.24 (6.2) 5.61 (168) 5.18 (157) 5.51 (140) 7.09 (180) 0.20 (5) 2.
13 FVR-C9S-2UX 6. Installation Instructions Installation Conditions Install the drive in a location which meets the following requir ements: • The ambient temperature should be be- tween -10 ° C and +50 ° C. • The humidity should be between 20 and 90% RH.
14 FVR-C9S-2UX CN 1 8. 8. 8. Connect CN 2 CN 2 Guide Pin 1 2 Side view of inverter 4) Arrange the main cir cuit and the control circuit wiring as follows. 1. Motor coast-to-stop 2. Reset signal 3. Reverse-direction operation command 4. Forwar d-direction operation command 5.
15 FVR-C9S-2UX 1) Keypad Panel Operation From the factory , the drive is set for fr equency control by means of the potentiometer contr ol knob on the keypad panel. The RUN/STOP function of the drive is contr olled by the RUN/ STOP keys on the keypad panel.
16 FVR-C9S-2UX 2) External Signal Operation Ensure that the connection is as shown below when operating the drive by means of an exter - nal frequency setting potentiometer or contact signal.
17 FVR-C9S-2UX Applicable motor output [Hp] 1/8 1/4 1/2 1235 Drive type FVRF12 FVRF25 FVRF50 FVRF001 FVRF002 FVRF003 FVRF005 C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX C9S-2UX Output rated capacity [kVA] 0.
18 FVR-C9S-2UX Terminal Function Explanation Classi- fication Terminal Code Terminal Name Explanation of Function Main Circuit L1, L2, L3 Commercial power supply input terminals For connection of 3-Ph.
19 FVR-C9S-2UX Terminal Function Explanation Classi- fication Terminal Code Terminal Name Explanation of Function Output for Motor FM Analog Monitor Outputs + 10VDC between FM and CM terminals. When frquency setting is equal to the maximum frequency setting, outputs + 10VDC at 150% current when monitoring output current.
20 FVR-C9S-2UX RUN STOP T ime Frequency Forward Reverse FWD-CM REV-CM ON ON Frequency 11. Operation Pre-Operation Inspection • Check for wiring errors. • Check that all loose wire stands, metal chips and unnecessary scr ews, etc. have been removed.
21 FVR-C9S-2UX Selecting Operation Method With the FVR-C9S Series, the following methods can be selected to input the RUN/STOP signals and for fr equency setting.
22 FVR-C9S-2UX 12. Keypad Panel Part Names and Functions Digital monitor: In program mode, the key- pad displays the various function codes and data values. During operation, it displays the output fre- quency , curr ent, voltage, etc. If a fault occurs, the causes of the problem will be dis- played as a code.
23 FVR-C9S-2UX 4) Function setting method Method Operation Procedure Display 1 PRG/RESET Press this key to switch to the program setting mode. 60 . 0 F0 0 2 UP/DOWN Press UP key or DOWN key to select function code F0 1 3 FUNC/DATA Press this key to display function code.
24 FVR-C9S-2UX Function Code Tables Function Code Function Date Code Range Unit Min. Set. Factory Setting Change During Operation F00 Data protection 0: Data change possible 1: Data change not possibl.
25 FVR-C9S-2UX Function Code Tables Function Code Function Date Code Range Unit Min. Set. Factory Setting Change During Operation F15 Motor Running Sound 0 - 5 (code) — — 5 Yes F16 Fault Memory Th.
26 FVR-C9S-2UX F 0 0 Data Protection The set data can be locked so that it will not be changed by mistake. 0 Data change possible 1 Data change not possible To change data simultaneously press the STOP key and either the UP/DOWN key. F 0 1 Frequency Command Either of the following two frequency setting methods can be selected.
27 FVR-C9S-2UX F 0 7 Torque Boost Can be set from among 32 different levels in accordance with the type of load, the characteristics of the motor, etc. 0 1 2 Low 3 1 High 8 Set to match this when using a Fuji FV motor designed for use with a drive. F 0 8 Electronic Thermal Overload Relay Either of the following two can be selected.
28 FVR-C9S-2UX Derating characteristics for the continuously allowable current 1) For a standard 4-pole motor _ _ 1 2) for a forced-air cooled motor _ _ 2 110 - 100 - 90 - 80 - 70 - 60 - 50 - 40 - 30 .
29 FVR-C9S-2UX F 1 0 Restart After Momentary Power Failure It is possible to select whether or not to restart operation when power supply is resumed after momentary power failure. 0 Inactive While stopped: Stopped condition is maintained even after power supply has been restored.
30 FVR-C9S-2UX F 1 4 Starting Frequency The starting frequency can be set in increments of 1 Hz within a range of 1 to 6 Hz. Note that stopping will also occur at the frequency set by this function. 1 1 Hz 6 6 Hz Set to 2 Hz when using a high speed motor.
31 FVR-C9S-2UX F 1 7 Data Initialization Reset the data for all of the functions to the value set at the factory. 0 Inactive 1 Resets to the value set at the factory. From the _ _ 0 display, by simultaneously pressing STOP and UP, the display will change to _ _ 1.
32 FVR-C9S-2UX F 2 4 High Limiter F 2 5 Low Limiter The upper and lower and lower limits of the output frequency can be set. 0 Set as a percentage of the maximum frequency in increments of 1% within a.
33 FVR-C9S-2UX F 2 9 Multistep Speed Setting 1 (Speed 1) F 3 0 Multistep Speed Setting 2 (Speed 2) F 3 1 Multistep Speed Setting 3 (Speed 3) Multistep speeds can be set within a range of 0 to 120 Hz only by changing the contact signal from outside. (X1-CM X2-CM).
34 FVR-C9S-2UX F 3 2 FM Terminal Output Level Calibration Adjust the level of the voltage output to terminal FM for the frequency meter. 0 Approximate DC 6.5V at full scale 99 Approximate DC 10.3V at full scale Note: The FM terminal output is a pulse output of which frequency is constant (38.
35 FVR-C9S-2UX Function Explanation Display Alarm Output Momentary Overcurrent Protection OC1 OC2 OC3 Yes Overvoltage Protection Detects overvoltage of DC intermediate circuit and stops drive. OU Yes Undervoltage Protection Detects undervoltage of DC intermediate circuit and stops drive.
36 FVR-C9S-2UX 15. W arranty Parts and Service The purpose of the following section to provide specific instructions to the user of the FVR-C9S-7UX drive r egarding warranty administration and how to obtain assistance on both in-warranty and out-of-warranty equipment.
37 FVR-C9S-2UX In-Warranty Failure Checklist To assist with warranty troubleshooting, the following information is required. This data is needed to evaluate the cause in an effort to eliminate any further failures.
38 FVR-C9S-2UX Notes:.
39 FVR-C9S-2UX Notes:.
40 FVR-C9S-2UX INR-Si47-0461 b-E Printed in Japan GE Fuji Drives USA, Inc. 1501 Roanoke Blvd. Suite 435 Salem, V A 24153 1-800-543-6196 Internet Address: http://www .
Ein wichtiger Punkt beim Kauf des Geräts GE FVR-C9S-2UX Drive Series (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie GE FVR-C9S-2UX Drive Series noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für GE FVR-C9S-2UX Drive Series - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von GE FVR-C9S-2UX Drive Series reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über GE FVR-C9S-2UX Drive Series erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon GE FVR-C9S-2UX Drive Series besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von GE FVR-C9S-2UX Drive Series verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit GE FVR-C9S-2UX Drive Series. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei GE FVR-C9S-2UX Drive Series gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.