Benutzeranleitung / Produktwartung (2 des Produzenten Allied Air Enterprises
Zur Seite of 14
506248-01 Page 1 of 14 Issue 0902 Save these instructions for future reference INST ALLA TION AND MAINTENANCE INSTRUCTIONS (2,4)PHP(13,15) Series Self-Contained Heat Pump Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage.
Page 2 of 14 506248-01 Issue 0902 INST ALLA TION These instructions explain the recommended method of installation of the PHP heat pump unit and associated electrical wiring. This unit is designed and approved for use as a self- contained air-to-air outdoor heat pump system.
506248-01 Page 3 of 14 Issue 0902 Using Accessory Lif t Kit Figure 1 Units may also be moved or lifted with a forklif t while still in the factory-supplied packaging.
Page 4 of 14 506248-01 Issue 0902 Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA). A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake.
506248-01 Page 5 of 14 Issue 0902 Power supply to the unit must comply with all applicable codes and the National Electical Code (NEC) or Canadian Electrical Code (CEC). A fused disconnect switch should be field provided for the unit. The switch must be sep arate from all other circuit s.
Page 6 of 14 506248-01 Issue 0902 Thermostat The room thermostat should be located on an inside wall where it will not be subject to draft s, sun exposure, or heat from electrical fixtures or appliances. Follow the manufacturer ’ s instructions enclosed with thermostat for general installation procedure.
506248-01 Page 7 of 14 Issue 0902 OPERA TION Sequence of Operation Cooling When the thermostat is in the cooling mode, the O circuit is powered which energizes the reversing valve. Upon cooling demand, the thermostat closes circuit R and Y . Closing R and Y closes the unit cont actor , starting the compressor and outdoor fan.
Page 8 of 14 506248-01 Issue 0902 jumper is not in place, the control defaults to a 90-minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted. A test option is provided for troubleshooting. The test mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered.
506248-01 Page 9 of 14 Issue 0902 There is no blower “on” delay after a call for heating or cooling. Blower “off” delay is 90 seconds af ter the thermostat is satisfied. V ariable Speed Motor Units equipped with a variable speed circulation air blower motor will deliver a constant airflow within a wide range of external static pressures.
Page 10 of 14 506248-01 Issue 0902 Owner Record Model # _________________________________ Serial # _________________________________ Installation Date ___________________________ Installed by: Dealer .
506248-01 Page 11 of 14 Issue 0902 Figure 9 208/230V -1-60 G W1 CR O BLK RED YEL RED CONT ACT OR THERMOST A T HIGH PRESSURE SWITCH (IF USED) L1 T1 T2 L2 C H F CONDENSER F AN MO TOR COMPRESSOR CONT ACT.
Page 12 of 14 506248-01 Issue 0902 Connection Diagram Single Phase – V ariable Speed Motor P/N 48374-001 Figure 10 DIAGNOSTIC DISPLA Y Note: Because the pressure switches are monitored only when "Y1" (Input) is activ e, the code for pressure s witch open will not be seen when "Y1" is off .
506248-01 Page 13 of 14 Issue 0902 ALLIED AIR ENTERPRISES EQUIPMENT LIMITED W ARRANTY APPLIES IN U.S.A. AND CANADA ONL Y F AILURE T O MAINT AIN YOUR EQUIPMENT WILL VOID THIS W ARRANTY COVERED EQUIPMEN.
Page 14 of 14 506248-01 Issue 0902 Allied Air Enterprises Inc. (“Allied Air”) provides its air conditioning and heating product s with a S tandard Limited Parts W a rranty for five (5) years.
Ein wichtiger Punkt beim Kauf des Geräts Allied Air Enterprises (2 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Allied Air Enterprises (2 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Allied Air Enterprises (2 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Allied Air Enterprises (2 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Allied Air Enterprises (2 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Allied Air Enterprises (2 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Allied Air Enterprises (2 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Allied Air Enterprises (2. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Allied Air Enterprises (2 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.