Quick Start Guide 00825-0100-4774, Rev FA June 2014 Note Bef ore installing the transmitte r , con firm the correct device drive r is loaded on the host systems.
June 2014 2 Quick Start Guide NO TICE This installation guide provides basic guidelines for R osemount 3051 transmitters. It does no t provide instructions f or confi guration, di agnostics, main tenance , ser vice , troubleshoo ting, Explosion-Proof , Flame-Proof, or intrinsically saf e (I.
Quick Start Guide 3 June 2014 System re adiness Confirm correct device driv er V erif y the correct device drive r (DD/DTM ™ ) is loaded on your syst ems to ens ur e p ro p er co mmu n ic at io ns . Download the correc t device driver a t your host ve ndor download site, www .
June 2014 4 Quick Start Guide Figure 1. Installation Flowchart Start 1. T ransmitter installation 2 . Commissioning tag 6 . Configuration Done Locate device 7 . Zero tri m th e transmitter 5. Grounding, wiring and power up 3 . Housing rot at io n 4 . Set switches and softwar e write lock 00825-0100-4774_RevFA.
Quick Start Guide 5 June 2014 T ransmitter installation St ep 1: Mount the transmitter Liquid applications Coplanar In-Line 1. Place taps to the side of the line. 2. Mount be side or be low the tap s. 3. Mount the trans mitte r so that the drain/ven t valves are oriented up ward.
June 2014 6 Quick Start Guide Figure 2. Panel and Pipe Mounting Bolting consider ations If the transmi tter installat ion requires assem bly of the proce ss flanges, man ifolds, or flange adapters, fo llow the assembly guideline s to ensure a tight seal for optimal performa nce charact eristics of the t ransmitters.
Quick Start Guide 7 June 2014 Figure 3. Common T ransmitte r Assemblies A. T ransmitter with C oplanar Flange B. T ransmitter with Coplanar Flan ge and Optional Flange Adapters C.
June 2014 8 Quick Start Guide T able 2. T orque V alues for the Flange and Flange Ad apter Bolts O-rings with fl ange adapte rs Bolt materi al Head markings Initial torque Final torque Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs. Sta in le ss St eel (S ST ) 150 in.
Quick Start Guide 9 June 2014 Whenever the fl anges or adapte rs are removed, visually inspe ct the o-rings. Replace them if t here are any signs of d amage, such as nic ks or cuts. If you replace the o-rings, re-torque t he flange bolts an d alignment scre ws after installa tion to compensate for seating of the PTFE o-ring.
June 2014 10 Quick Start Guide Figure 6. Commissioning T ag A. Device revision Note The device de scription loaded in the host system mu st be at the same re vision as this device. The devic e description can be downloaded from the host system we bsite or www .
Quick Start Guide 11 June 2014 Step 4: Set the switc hes Set Simulate an d Security switch configuration be fore installat ion as shown in Figure 8 . The simulate switch en ables or disables simulated ale r ts and simulated AI Block status and values.
June 2014 12 Quick Start Guide St ep 5: Wire, ground, and power up Use of copper wire of sufficient size to ensure th at the voltage across the transmitter power t erminals does not drop below 9 vdc. P ower supply volta ge can be varia ble, especi ally under ab normal conditions suc h as when ope rating on battery backup.
Quick Start Guide 13 June 2014 a. T rim the cable shie ld as short as practical and insu lat e from to uching the transmitter housing. Note Do NO T ground the cable shield a t the transmitter; if the cable shie ld touches the transmitte r housing, it can cre ate gro und loops and int erfere with c ommunica tions.
June 2014 14 Quick Start Guide When the user exits the “Locate Device” meth od, the device LCD d isplay automatically ret urns to normal ope ration.
Quick Start Guide 15 June 2014 Figure 11. Basic Configur ation Menu T ree Before y ou begin See Figu re 10 to graphically view th e step by step process for basic device configuration. Be fore beginning configurat ion you may need to v erify the Device Tag or deactivat e hardware and softwa re write prote ction on the transm itter.
June 2014 16 Quick Start Guide a. Navig ation : from the ove r view scree n, select “Devic e Inf orma tion ” and the n se lect the “Security and Simul ation” tab . b. P erform “Write Lock Setup ” to disable Soft ware Write Lock. Note Place the c ontrol loop in “Manual” mode bef o re beginning Analog Input Block configuration.
Quick Start Guide 17 June 2014 Note If the L_TYPE selected in Step 3 is “Direc t”, Step 4 , St ep 5 and Step 6 are not needed. If the L_T YPE selected is “Indi rect”, Step 6 is not needed. If guided setup is used any unneeded steps will aut omatically be skipped.
June 2014 18 Quick Start Guide 8. Configure optional L CD di splay (if installed). a. T o use guided setup : Naviga te to Con figure, Guided Setup , and select “Local Display Setup”. Note Guided setup will automatically go through each step in the proper orde r .
Quick Start Guide 19 June 2014 AI block conf igur ation pa ramet ers Use the Pressure, DP Fl ow, and DP Level examples for guides. Pressure example DP Flow example Param ete rs Enter data Channe l 1=P.
June 2014 20 Quick Start Guide DP Leve l example Displ ay pre ssure on the L CD displ ay Select the 'pre ssure' check bo x on the display con figuration sc reen. St ep 7: Zero trim the transmitt er Note T ransmitters are shipped fully calibrated per request or by the factor y default of full scale (s pan = uppe r range limit).
March 2014 Quick Start Guide 3051 Product Certifications Rev 1.0 European Directive Information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.
Quick Start Gui de March 2014 Markings: Explosionproof for Class I, Division 1, Groups B, C and D; Suitable for Class I, Zone 1, Group IIB+H2, T5; Dust-I gnitionproof Class II, Division 1, Groups .
March 2014 Quick Start Guide Special Conditions for Safe Us e (X): 1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11.
Quick Start Gui de March 2014 2. For information on the dimensions of t he flameproo f joints the manufacturer shall be contacted. 3. The capacitance of the wrap around label, bei ng 1. 6 nF, exceeds th e limit in Table 9 of EN60079-0. The user shall determine suit ability for the specific applic ation.
March 2014 Quick Start Guide Brazil E2 INMETRO Flameproof Certificate: UL-BR 13.0643X Standards: ABNT NBR IEC60079-0:2008 + Errat a 1:2011, ABNT NBR IEC60079- 1:2009 + Errata 1:2011, ABNT NBR IEC60 07.
Quick Start Gui de March 2014 China E3 China Flameproof Certificate: GYJ14.1041X; GYJ10.1313X [Flowmeters] Standards: GB3836.1-2000, GB38 36.2-2010, GB12476-2000 Markings: Ex d IIC T6/T5, T6(-50°C ≤ Ta ≤ +65°C), T5(-50° C ≤ Ta ≤ +80°C) Special Conditions of Us e (X): 1.
March 2014 Quick Start Guide Power P i 0.9 W 1.3 W 5.32 W Capacitance C i 0.012 µF 0 µF <5 nF Inductance L i 0 mH 0mH <10 µH Note 1: FISCO paramete rs apply to both Group IIC and IIB.
Quick Start Gui de March 2014 GB3836.15-2000 “Electrical apparatus for explos ive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.
Quick Start Guide June 2014 00825-0100-4774_RevFA.fm Pag e 21 Friday, June 6, 2014 2:21 PM.
June 2014 Quick Start Guide 00825-0100-4774_RevFA.fm Pag e 22 Friday, June 6, 2014 2:21 PM.
Quick Start Guide June 2014 00825-0100-4774_RevFA.fm Pag e 23 Friday, June 6, 2014 2:21 PM.
June 2014 Quick Start Guide 00825-0100-4774_RevFA.fm Pag e 24 Friday, June 6, 2014 2:21 PM.
Quick Start Guide June 2014 00825-0100-4774_RevFA.fm Pag e 25 Friday, June 6, 2014 2:21 PM.
Device revision (1) 1. 1. F OUNDATION fieldbus devic e revision can be read using a F OUNDATION fieldbus capable con figuration tool. Host De vice d rive r (DD) (2) 2.
Ein wichtiger Punkt beim Kauf des Geräts Emerson Rosemount 3051CF (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Emerson Rosemount 3051CF noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Emerson Rosemount 3051CF - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Emerson Rosemount 3051CF reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Emerson Rosemount 3051CF erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Emerson Rosemount 3051CF besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Emerson Rosemount 3051CF verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Emerson Rosemount 3051CF. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Emerson Rosemount 3051CF gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.