OpenComms - 485 Modbus Reference Guide





Connectivity to OpenComms-485 using Modbus This design specification describes the Modbus communications protocol as supported by the OC-485 interface card. It includes information on how to pass information to and from the OC-485 card via Modbus. It is also intended to help facilitate answering questions regarding supported types, frame format, function code support etc.
Implementation Basics Protocol controls the language structure or message format between devices in other words, the rules for communication. The rules for communication include how master and slave devices initiate communications, as well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of the query and response cycles between master and slave devices. The OC-485 card is configured to act as a slave device on a common network. This common network can be a multi-drop configuration over EIA-485, where multiple slaves reside on a common wire or loop.
Transmission Format The OC-485 interface card supports Modbus RTU (Remote Terminal Unit) transmission modes. . See chart below.

Device Address: The address field immediately follows the beginning of the frame and consists of 8-bits (RTU). This bit indicates the user assigned address of the slave device that is to receive the message sent by the attached master device. Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its address.

16 Write multiple Registers
Write values into a block of contiguous registers (1 to 120)
Data Field(s): The data field varies in length depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to pass back data to the master device.
Error Check Field: The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted with transmission errors.
The example below shows a typical Q/R from a OC-485 interface card. In common terms, the master device initiates a query asking slave device 2 for holding registers starting at holding register 40051 (decimal 50) and including next 2 Registers (3 total).
Slave address 2 responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.
Register values:40051 = 158(hex) = 344(decimal)
40052 = FA (hex) = 250 (decimal) 40053 = 54 (hex) = 84 (decimal)
Query Sample · Response Sample

Supported Modbus Points




Supported Modbus Points
Data Point Status Coil # of Reg. Scale Notes / Units Economode 10005 5 DC-To-DC Converter On 10042 Battery Charge Compensation 10046 Inverter Ready 10047 Power Factor Correction State 10050 Battery Charge Mode 10051 Load On Inverter 10073 Bypass Active 10074 Battery Under Test 10082 Load On Battery 10128 Overload Transfer To Bypass 10131 Input Switch Open 10137 Generator Disconnected 10141 Bypass Transfer Count Block 10147 Static Bypass Switch Disabled 10148 Low Battery - Shutdown Imminent 10152 Output Overload 10154 UPS Load Joint Mode 10156 Output Off 10158 Inverter Unsynchronized 10160 Main Neutral Lost 10161 Fan Failure 10169
Ambient Over Temperature 10173 Rectifier Over Temperature 10174 Rectifier Inductor Over Temperature 10175 Inverter Over Temperature 10176 Inverter Inductor Over Temperature 10177 Battery Converter 10179

Over Temperature DC Bus Balancer Over Temperature 10180 Input Power Supply Fail 10186 Input BrownOut 10189 Bad Input Frequency 10190 Bypass Phase Rotation Error 10191 Bypass Phase Loss 10201 Bypass Input Voltage/Frequency Fault 10202 Output Fuse Blown 10217 Output Over Voltage 10219 Charger Failed 10234 Battery Fault 10235 Battery Contact Fail 10236 Battery Converter Over Current 10237 Battery Converter Fail 10238 DC Bus Balancer Over Current 10239 DC Bus Balancer Fault 10240 DC Bus 1 Power Supply Fail 10251 Rectifier Fuse Fail 10257 Rectifier Startup Failure 10258 Rectifier Fault 10259 Rectifier Current Limit 10260 Inverter DC Voltage Low Shutdown 10262 Inverter Fault 10263 Inverter DC Offset Overload 10264 Inverter Contactor Fail 10265 Inverter Current Limit 10266 Parallel Low Battery Warning 10267 Load Share Fault 10268 Parallel System Fault 10269 Parallel Connection Error 10270 Parallel System Overload 10271 Parallel Transfer To 10272


Nominal Battery Float Voltage 30038 40038 1 V Load Bus Sync Mode 30040 40040 1 Auto Restart Delay 30051 40051 1 1 Seconds Device Low Battery Time 30053 40053 1 Minutes Input Frequency 30107 1 10 Hz
Output Frequency 30108 1 10 Hz Bypass Frequency 30109 1 10 Hz
Battery Charge Status 30112 1
Data Point Register Coil # of Reg. Scale Notes / Units
Battery Time Remaining 30115 1 Minutes Battery Charge Percentage 30116 1 % Battery Temperature 30117 1 C Ambient Temperature 30119 1 C Parallel Load Source 30128 1 Rotary Breaker 30129 1
1 - Unknown 2 - Passed 3 - Failed 4 - In Progress 5 - System Failure 6 - Inhibited Input Voltage L1-L2 30151 2 W Input Voltage L1 30153 1 V Input Current L1 30154 1 A Input Power Factor L1 30155 1 100 Bypass Voltage L1 30159 1 V Output Voltage L1 30163 1 V Output Current L1 30164 1 A Output Load L1 30165 1 1 Output Power Factor L1 30166 1 100 Apparent Output Power L1 30168 2 VAR Reactive Output 30170 1 %
Battery Test Result 30130 1

Output Power L1 30172 2 VA Output Current Crest Factor L1 30186 1 V Input Voltage L2-L3 30201 2 W Input Voltage L2 30203 1 V Input Current L2 30204 1 A Input Power Factor L2 30205 1 100 Bypass Voltage L2 30209 1 V Output Voltage L2 30213 1 V Output Current L2 30214 1 A Output Load L2 30215 1 1 Output Power Factor L2 30216 1 100 Apparent Output Power L2 30218 2 VAR Reactive Output Power L2 30220 1 % Output Power L2 30222 2 VA Output Current Crest Factor L2 30236 1 V Input Voltage L3-L1 30251 2 W Input Voltage L3 30253 1 V Input Current L3 30254 1 A Input Power Factor L3 30255 1 100
Bypass Voltage L3 30259 1 V Output Voltage L3 30263 1 V Output Current L3 30264 1 A Output Load L3 30265 1 1 Output Power Factor L3 30266 1 100 Apparent Output Power L3 30268 2 VAR Reactive Output Power L3 30270 1 % Output Power L3 30272 2 VA Output Current Crest Factor L3 30286 1 V
Power L1

Supported Modbus Points
Data Point Status Coil # of Reg. Scale Notes /Units Audible Alarm Enabled 10002 2 1 1 Automatic Battery Test Enabled 10003 3 1 1 Battery Charge Compensation 10046 1 1 Inverter Ready 10047 1 1 Load Circuit 1 State 10057 1 1 Load Circuit 2 State 10058 1 1 Load Circuit 3 State 10059 1 1 Load Circuit 4 State 10060 1 1 Load Circuit 5 State 10061 1 1 Load Circuit 6 State 10062 1 1 Load Circuit 7 State 10063 1 1 Load Circuit 8 State 10064 1 1 Load Circuit 9 State 10065 1 1 Load Circuit 10 State 10066 1 1 Load Circuit 11 State 10067 1 1 Load Circuit 12 State 10068 1 1 Load Circuit 13 State 10069 1 1 Load Circuit 14 State 10070 1 1 Load Circuit 15 State 10071 1 1 Load Circuit 16 State 10072 1 1 Load On Inverter 10073 1 1 Boost Mode On 10075 1 1 Buck Mode On 10076 1 1 Battery Under Test 10082 1 1 Shutdown Reason - Over Temperature 10086 1 1 Shutdown Reason - Overload 10087 1 1 Shutdown - Output Short 10089 1 1 Shutdown Reason - Remote Shutdown 10093 1 1 Load On Battery 10128 1 1 Output Off Pending 10151 1 1 Low Battery - Shutdown Imminent 10152 1 1 Output Overload 10154 1 1 Over Temperature Warning 10171 1 1 Battery Over Temperature CB Trip 10172 1 1

Input Power Supply Fail 10186 1 1 Input Over Voltage 10187 1 1 Input Under Voltage 10188 1 1 Bad Input Frequency 10190 1 1 Output Under Voltage 10218 1 1 Output Over Voltage 10219 1 1
Holding Register # of Reg. Scale Notes /Units
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15 Number Of Bypass Lines 30004 40004 1 1 Bits 4 - 7 Number Of Output Lines 30004 40004 1 1 Bits 8 - 11 Number Of SubModules 30009 40009 1 1
There are 16 possible Load Circuits. So each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1 then the Load Circuit is supported. Nominal Power Rating 30021 40021 2 1 VA Nominal Input Voltage 30027 40027 1 1 V Nominal Output Voltage 30028 40028 1 1 V Nominal Input Current 30030 40030 1 1 A Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 Nominal Battery Voltage 30034 40034 1 1 V Auto Restart Delay 30051 40051 1 1 seconds Device Low Battery Time 30053 40053 1 1 min Load (Apparent Power) 30102 2 1 VA Load / Capacity 30106 1 1 % Input Frequency 30107 1 10 Hz Output Frequency 30108 1 10 Hz
Load Circuit Present 30013 40013 1
Battery Charge Status 30112 1
Battery Test Result 30130 1 1
Input Register · Data Point


Output Voltage L1 30163 1 1 V Output Current L1 30164 1 1 A Input Maximum Voltage L1 30180 1 1 V Input Minimum Voltage L1 30181 1 1 V Output Maximum Voltage L1 30182 1 1 V Output Minimum Voltage L1 30183 1 1 V Black Out Count 30301 1 1 Brown Out Count 30302 1 1

Supported Modbus Points
Status Coil # of Reg. Scale Notes / Units Audible Alarm Enabled 10002 2 1 1 Automatic Battery Test Enabled 10003 3 1 1 DC-To-DC Converter On 10042 1 1 Battery Charger On 10044 1 1 Load Circuit 1 State 10057 1 1 Load Circuit 2 State 10058 1 1 Load Circuit 3 State 10059 1 1 Load Circuit 4 State 10060 1 1 Load Circuit 5 State 10061 1 1 Load Circuit 6 State 10062 1 1 Load Circuit 7 State 10063 1 1 Load Circuit 9 State 10065 1 1 Load Circuit 10 State 10066 1 1 Load Circuit 11 State 10067 1 1 Load Circuit 12 State 10068 1 1 Load Circuit 13 State 10069 1 1 Load Circuit 14 State 10070 1 1 Load Circuit 15 State 10071 1 1 Load Circuit 16 State 10072 1 1 Load On Inverter 10073 1 1 Boost Mode On 10075 1 1 Buck Mode On 10076 1 1 Replace Battery 10081 1 1 Battery Under Test 10082 1 1 Shutdown Reason - Over Temperature 10086 1 1 Shutdown Reason - Overload 10087 1 1 Shutdown Reason - Output Short 10089 1 1 Shutdown Reason - Line Neutral Swap 10090 1 1 Shutdown Reason - Low Battery 10092 1 1 Shutdown Reason - Remote Shutdown 10093 1 1 Shutdown Reason - Input Under Voltage 10094 1 1 Shutdown Reason - 10096 1 1
Data Point

Hardware Load On Battery 10128 1 1 Output Off Pending 10151 1 1 Low Battery - Shutdown Imminent 10152 1 1 Output Overload 10154 1 1 Over Temperature Warning 10171 1 1 Input Power Supply Fail 10186 1 1 Input Over Voltage 10187 1 1 Input Under Voltage 10188 1 1 Input BrownOut 10189 1 1 Bad Input Frequency 10190 1 1 Output Under Voltage 10218 1 1 Output Over Voltage 10219 1 1 Charger Failed 10234 1 1 Battery Under Voltage 10241 1 1 Battery Over Voltage 10242 1 1 Data Point
Input Register Holding Register # of Reg. Scale Notes / Units
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15 Number Of Output Lines 30004 40004 1 1 Bits 8 - 11 Number Of SubModules 30009 40009 1 1 Load Circuit Present
There are 16 possible Load Circuits. So each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1 then the Load Circuit is supported. Nominal Power Rating 30021 40021 2 1 VA Nominal Input Voltage 30027 40027 1 1 V Nominal Output Voltage 30028 40028 1 1 V Nominal Input Current 30030 40030 1 1 A Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 Nominal Battery Voltage 30034 40034 1 1 V Nominal Battery Capacity 30037 40037 1 1 minutes Nominal Battery Float Voltage 30038 40038 1 1 V Auto Restart Delay 30051 40051 1 1 seconds Device Low Battery Time 30053 40053 1 1 min
30013 40013 1

Ambient Temperature Warning Point 30069 40069 1 1 deg C Over Temperature Limit Point 30072 40072 1 1 deg C Load (Apparent Power) 30102 2 1 VA Load (Real Power) 30104 2 1 W Load / Capacity 30106 1 1 % Input Frequency 30107 1 10 Hz Output Frequency 30108 1 10 Hz Battery Charge Status
1 - 100% Charged 2 - Less than 100% Charged 3 - Charging 4 - Discharging 5 - Float Charging 6 - Equalize Charging Battery Voltage 30113 1 1 V Battery Time Remaining 30115 1 1 min Battery Charge Percentage 30116 1 1 % Ambient Temperature 30119 1 1 deg C Battery Test Result 30130 1 1 Input Voltage L1 30153 1 1 V Input Current L1 30154 1 1 A Output Voltage L1 30163 1 1 V Output Current L1 30164 1 1 A Input Maximum Voltage L1 30180 1 1 V Input Minimum Voltage L1 30181 1 1 V Output Maximum Voltage L1 30182 1 1 V Output Minimum Voltage L1 30183 1 1 V Black Out Count 30301 1 1 Brown Out Count 30302 1 1
30112 1

Supported Modbus Points

Data Point Status Coil # of Reg. Scale Notes / Units Audible Alarm Enabled 10002 2 1 1
Inverter Ready 10047 1 1 Power Factor Correction State 10050 1 1
Load On Inverter 10073 1 1 Bypass Active 10074 1 1


Replace Battery 10081 1 1 Battery Under Test 10082 1 1 Shutdown Reason - Over Temperature 10086 1 1
Shutdown Reason - Link Over Voltage 10088 1 1
Shutdown Reason - Line Neutral Swap 10090 1 1
Shutdown Reason - Input Under Voltage 10094 1 1
Load On Battery 10128 1 1 Output Off Pending 10151 1 1
Output Overload 10154 1 1 Over Temperature Warning 10171 1 1
Input Over Voltage 10187 1 1 Input Under Voltage 10188 1 1

Data Point Input Register Holding Register # of Reg. Scale Notes / Units
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15
Number Of Bypass Lines 30004 40004 1 1 Bits 4 - 7
Number Of Output Lines 30004 40004 1 1 Bits 8 - 11
Number Of SubModules 30009 40009 1 1
There are 16 possible Load Circuits. So each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1 then the Load Circuit is supported. Battery Cabinet Type 30018 40018 2 1
Battery Cabinet Number 30019 40019 1 1
Battery AmpHour 30020 40020 1 1 AH Nominal Power Rating 30021 40021 2 1 VA
Nominal Input Voltage 30027 40027 1 1 V
Nominal Output Voltage 30028 40028 1 1 V
Nominal Static Bypass Switch Voltage 30029 40029 1 1
Nominal Input Current 30030 40030 1 1 A
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100
Nominal Battery Voltage 30034 40034 1 1 V
Auto Restart Delay 30051 40051 1 1 seconds Device Low Battery Time 30053 40053 1 1 min
Load (Apparent Power) 30102 2 1 VA
Load (Real Power) 30104 2 1 W Load / Capacity 30106 1 1 % Input Frequency 30107 1 10 Hz Output Frequency 30108 1 10 Hz Bypass Frequency 30109 1 10 Hz
Voltage · Load Circuit Present · 30013 40013 1


Battery Voltage 30113 1 1 V Battery Time Remaining 30115 1 1 min
Input Voltage L1 30153 1 1 V Bypass Voltage L1 30159 1 1 V Output Voltage L1 30163 1 1 V Output Current L1 30164 1 1 A Input Maximum Voltage L1 30180 1 1 V
Black Out Count 30301 1 1 Brown Out Count 30302 1 1

Supported Modbus Points
Coil # of Reg. Scale Notes / Units DC-To-DC Converter On 10042 1 1 Load On Inverter 10073 1 1 Bypass Active 10074 1 1 Load On Battery 10128 1 1 Permanently On Bypass 10133 1 1 Bypass SCR Open Circuit 10149 1 1 Low Battery - Shutdown Imminent 10152
Output Overload 10154 1 1 Inverter Unsynchronized 10160 1 1 Input Power Supply Fail 10186 1 1 Bypass Input Voltage/Frequency Fault 10202
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15 Number Of Bypass Lines 30004 40004 1 1 Bits 4 - 7 Number Of Output Lines 30004 40004 1 1 Bits 8 - 11 Number Of SubModules 30009 40009 1 1 Number Of Battery Cells 30012 40012 1 1 Load Circuit Present
There are 16 possible Load Circuits. So each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1 then the Load Circuit is supported. Load (Apparent Power) 30102 2 1 VA Load (Real Power) 30104 2 1 W Input Frequency 30107 1 10 Hz Output Frequency 30108 1 10 Hz Battery Voltage 30113 1 1 V Battery Current (Charge/Discharge) 30114
Battery Charge Percentage 30116 1 1 % Ambient Temperature 30119 1 1 deg C Input Voltage L1 30153 1 1 V Input Current L1 30154 1 1 A Output Voltage L1 30163 1 1 V Output Current L1 30164 1 1 A Input Voltage L2 30203 1 1 V


Input Current L2 30204 1 1 A Input Voltage L3 30253 1 1 V Input Current L3 30254 1 1 A Liebert UPS Series 600

Battery Charger On 10044 1 1 Battery Charge Compensation
Load On Inverter 10073 1 1 Load On Bypass 10074 1 1 Buck On 10076 1 1 Battery data Buffer Full 10084 1 1 Shutdown Reason – Hardware
Load On Battery 10128 1 1 Manual Reset Transfer 10130 1 1 Load On Bypass Permanent
Battery Switch Open 10136 1 1 Input Switch Open 10137 1 1 Output Switch open 10138 1 1 Emergency Load Transfer to Inverter
SBS SCR Open 10149 1 1 SBS SCR Short 10150 1 1 Low Battery - Shutdown Imminent
Input Under Voltage 10188 1 1 Input Brown Out 10189 1 1

Input Phase Rotation Error
Bypass Phase Missing 10201 1 1 Bypass Input Voltage Fail
Bypass Under Voltage Fail
Bypass Under Voltage Warning
Bypass Over Voltage Fail
Bypass Over Voltage Warning
Output Under Voltage 10218 1 1 Output Over Voltage 10219 1 1 Output Short Circuit 10220 1 1 Module with Active Alarm
Scale Notes / Units
# of Reg.
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15 Number Of Bypass Lines
30004 40004 1 1 Bits 4 - 7
Number Of Output Lines
30004 40004 1 1 Bits 8 - 11
30009 40009 1 1
Nominal Power Rating 30021 40021 2 1 VA Nominal Input Voltage 30027 40027 1 1 V Nominal Output Voltage
Nominal Static Bypass Switch Voltage
Nominal Input Current 30030 40030 1 1 A Nominal Output Frequency
30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 Nominal Battery Voltage
30102 2 1 VA
Load (Real Power) 30104 2 1 W Load / Capacity 30106 1 1 % Output Frequency 30108 1 10 Hz Bypass Frequency 30109 1 10 Hz Battery Charge Status 30112 1 1 - 100% Charged 2 - Less than 100% Charged
Battery Voltage 30113 1 1 V Battery Current 30114 1 1 A Battery Time Remaining
30115 1 1 min
30116 1 1 %

Supported Modbus Points
Data Point Status Coil # of Reg.
Scale Notes / Units
10001
Inverter Ready 10047 1 1 Load Circuit 1 State 10057 1 1 Load Circuit 2 State 10058 1 1 Load Circuit 3 State 10059 1 1 Load Circuit 4 State 10060 1 1 Load Circuit 5 State 10061 1 1 Load Circuit 6 State 10062 1 1 Load Circuit 7 State 10063 1 1 Load Circuit 8 State 10064 1 1 Load Circuit 9 State 10065 1 1 Load Circuit 10 State 10066 1 1 Load Circuit 11 State 10067 1 1 Load Circuit 12 State 10068 1 1 Load Circuit 13 State 10069 1 1 Load Circuit 14 State 10070 1 1 Load Circuit 15 State 10071 1 1 Load Circuit 16 State 10072 1 1 Load On Inverter 10073 1 1 Bypass Active 10074 1 1 Buck On 10076 1 1 Replace Battery 10081 1 1 Battery Under Test 10082 1 1 Load On Battery 10128 1 1 Low Battery - Shutdown Imminent
Output Overload 10154 1 1 Over Temperature Warning
Battery Over Temperature CB Trip
Input Power Supply Fail
Input Over Voltage 10187 1 1 Input Under Voltage 10188 1 1 Bad Input Frequency 10190 1 1 Bypass Input Voltage/Frequency Fault
Output Under Voltage 10218 1 1 Output Over Voltage 10219 1 1

Battery Charger Fail 10234 1 1 Data Point Input Register
# of Reg.
Scale Notes / Units
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15 Number Of Bypass Lines
30004 40004 1 1 Bits 4 - 7
Number Of Output Lines
30004 40004 1 1 Bits 8 - 11
30009 40009 1 1
Load Circuit Present 30013 40013 1 There are 16 possible Load Circuits. So each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1 then the Load Circuit is supported. Nominal Power Rating 30021 40021 2 1 VA Nominal Input Voltage 30027 40027 1 1 V Nominal Output Voltage
Nominal Static Bypass Switch Voltage
Nominal Input Current 30030 40030 1 1 A Nominal Input Frequency
30031 40031 1 10 Hz
30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 Nominal Battery Voltage
Device Low Battery Time
30053 40053 1 1 min
Load (Real Power) 30104 2 1 W Load / Capacity 30106 1 1 % Input Frequency 30107 1 10 Hz Output Frequency 30108 1 10 Hz Bypass Frequency 30109 1 10 Hz Battery Charge Status 30112 1 1 1 - 100% Charged 2 - Less than 100% Charged Battery Voltage 30113 1 1 V Battery Current 30114 1 1 A Battery Time Remaining
30115 1 1 min
30116 1 1 %
Battery Test Result 30130 1 1 1 - Unknown 2 - Passed 3 - Failed 4 - In Progress 5 - System Failure 6 - Inhibited

Input Voltage L1 30153 1 1 V
Input Current 30154 1 1 A Bypass Voltage L1 30159 1 1 V Bypass Current L1 30160 1 1 A Output Voltage L1 30163 1 1 V Output Current L1 30164 1 1 A Input Voltage L2 30203 1 1 V Input Current L2 30204 1 1 A Bypass Voltage L2 30209 1 1 V Bypass Current L2 30210 1 1 A Output Voltage L2 30213 1 1 V Output Current L2 30214 1 1 A Input Voltage L3 30253 1 1 V Input Current L3 30254 1 1 A Bypass Voltage L3 30259 1 1 V Bypass Current L3 30260 1 1 A Output Voltage L3 30263 1 1 V Output Current L3 30264 1 1 A Black Out Count 30301 1 1 Brown Out Count 30302 1 1 Transient Count 30301 1 1 Silent Audible Alarm 40101 any value Battery Start 40102 1 1 1=Start, 0=Abort Open UPS Output Switch
40104 Delay time in Second, last digit will be ignored Reboot UPS Output Switch
40105 1 1 Delay time in Second, last digit will be ignored Close UPS Output Switch
40106 Delay time in Second, last digit will be ignored Transfer Load to Bypass
40107 1 1 any value
Transfer Load to Inverter
Reset UPS Statistic data
40111 1 1 any value
Turn UPS Outlets On 40112 1 1 Bitmap mask for Outlet 1-16. all bits set to 1 will be turn On Turn UPS Outlets Off 40113 1 1 Bitmap mask for Outlet 1-16. all bits set to 1 will be turn Off
40108 any value

- Notes iCOM Reference Sleep on Monday 10001 1 1 U603 Sleep on Tuesday 10002 2 1 U603 Sleep on Wednesday 10003 3 1 U603 Sleep on Thursday 10004 4 1 U603 Sleep on Friday 10005 5 1 U603 Sleep on Saturday 10006 6 1 U603 Sleep on Sunday 10007 7 1 U603 Supply Limit Enable 10008 8 1 S105 Reheat Lockout 10009 9 1 S271 Humidifier Lockout 10010 10 1 S272 Temperature Indication [1] 10011 11 1 U404 Timer Mode Type 10012 12 1 U610 Minimum Chilled Water Temp Enable
Std. Sensor Alarms Enable 10019 19 1 U202 Sensor A Alarms Enable 10020 20 1 U207 Compressor Lockout 10021 21 1 S274 VSD Fan speed 10022 22 1 S131 Unit Control - 25 1 EnvState. SysCtrl Reset Alarm - 26 1 .. EnvState. AlarmCtrl.1 Acknowledge Alarm - 27 1 .. EnvState. AlarmCtrl.2 Reset Total Run Hours Fan Motor
Reset Comp1Run Hour - 29 1 .. U503 Reset Comp2Run Hour - 30 1 .. U504 Reset Humidifier Run Hour - 31 1 .. U510 Reset Dehumidifier Run Hour - 32 1 .. U511 Reset CW/FC Run Hour - 33 1 .. U505 Reset E-Heater1RunHour - 34 1 .. U507 Reset E-heater2RunHour - 35 1 .. U508 Reset E-heater3 Run Hour - 36 1 .. U509 Reset HG/HW Run Hour - 37 1 .. U506 Fan On 10025 - 1 FanSym
Cool On 10026 - 1 CoolSym
Free Cool On 10027 - 1 FCSym
Hot Water On 10028 - 1 HWSym
Electrical Heater On 10029 - 1 HeatSym

Humidification On 10030 - 1 HumSym
Dehumidification On 10031 - 1 DehumSym
Audible Alarm On 10032 - 1 HornSym
Reserved 10033 - 1 087 MAIN FAN OVERLOAD 10034 - 1 006 LOSS OF AIRFLOW 10035 - 1 007 LOSS OF FLOW 10036 - 1 107 COMP 1 HIGH PRESSURE 10037 - 1 001 COMP 1 LOW PRESSURE 10038 - 1 002 COMP 1 OVERLOAD 10039 - 1 071 COMP 1 PUMPDOWN FAIL 10040 - 1 091 COMP 2 HIGH PRESSURE 10041 - 1 058 COMP 2 LOW PRESSURE 10042 - 1 059 COMP 2 OVERLOAD 10043 - 1 072 COMP 2 PUMPDOWN FAIL 10044 - 1 096 DIG SCROLL1 HIGH TEMP 10045 - 1 097 DIG SCROLL2 HIGH TEMP 10046 - 1 098 SMOKE DETECTED 10047 - 1 104 WATER UNDER FLOOR 10048 - 1 105 HUMIDIFIER PROBLEM 10049 - 1 086 STBY GLYCOL PUMP ON 10050 - 1 108 STANDBY UNIT ON 10051 - 1 109 COND PUMP-HIGH WATER 10052 - 1 106 ROOM SENSOR FAILURE 10053 - 1 031 LOSS COMPRESSOR POWER
10054 - 1 135
LOSS OF AIR BLOWER 1 10055 - 1 017 HUMIDIFIER LOW WATER 10058 - 1 153 HUMIDIFIER HIGH AMPS 10059 - 1 152 HIGH TEMPERATURE 10060 - 1 016 LOSS OF POWER 10061 - 1 142 UNSPECIFIED EVENT(S) [1] 10064 - 1 HIGH CW TEMP 10065 - 1 003 RESERVED 10066 - 1 005 HIGH ROOM TEMP 10067 - 1 018 LOW ROOM TEMP 10068 - 1 019 HIGH ROOM HUM 10069 - 1 020 LOW ROOM HUM 10070 - 1 021 HIGH TEMP SENSOR A 10071 - 1 022 LOW TEMP SENSOR A 10072 - 1 023 HIGH HUM SENSOR A 10073 - 1 024 LOW HUM SENSOR A 10074 - 1 025 LOSS OF CW FLOW 10075 - 1 004 CLOGGED FILTERS 10076 - 1 008 SUPPLY SENSOR FAILURE 10077 - 1 029 FREECOOL TEMP SENSOR 10078 - 1 062

SENSOR A FAILURE 10079 - 1 032 UNIT HRS EXCEEDED 10080 - 1 026 COMP 1 HRS EXCEEDED 10081 - 1 027 COMP 2 HRS EXCEEDED 10082 - 1 060 FC HRS EXCEEDED 10083 - 1 089 EL HEAT1 HRS EXCEEDED 10084 - 1 111 EL HEAT2 HRS EXCEEDED 10085 - 1 112 EL HEAT3 HRS EXCEEDED 10086 - 1 113 HW/HG HRS EXCEEDED 10087 - 1 110 HUM HRS EXCEEDED 10088 - 1 028 DEHUM HRS EXCEEDED 10089 - 1 088 NETWORK FAILURE 10091 - 1 034 NO CONNECTION W/UNIT 1 10092 - 1 .. 070 UNIT(S) DISCONNECTED 10093 - 1 (042)-(057) UNIT CODE MISSING 10094 - 114 UNIT CODE MISMATCH 10095 - 115-132 CALL SERVICE 10096 - 015 Low Memory 1 10097 - 069 RAM / Battery Failure 10098 - 068 HCB not connected 10099 - 094 (Parallel flash) MEMORY 1 FAIL
(Serial flash) MEMORY 2 FAIL 10101 - 093 CUSTOMER INPUT 1 10104 - 009 CUSTOMER INPUT 2 10105 - 010 CUSTOMER INPUT 3 10106 - 011 CUSTOMER INPUT 4 10107 - 012 DSCROLL 1 SENSOR FAIL 10108 - 030 DSCROLL 2 SENSOR FAIL 10109 - 061
10100 - 092

(A value read from an input register is the real-time data value. A value read from a holding register is the value last set to this modbus server by a user.) Reference Document: ST100I&C PA Parameters and Events, Version 18.0 Data Description Input Register Holding Reg # Regs

Scale Note iCOM Reference Vendor Id 30001 40001 1 1 - Device ID 30002 40002 1 1 - version number 30003 40003 1 1 - Ups/Env/Pwr 30004 40004 1 1 - Timer Mode[2] 30016 40016 1 1 .. U609 Type of DT Room-FC[3]
VSD Setpoint 30019 40019 1 1 % (HP) S132 Supply temperature Limit
Humidity Setpoint 30027 40027 1 1 % S113 Humidity proportional band


Timer Dead Band 30044 40044 1 X10 C° U611 Manual VSD Timer/Counter[6]
Low Temperature 30051 40051 1 X10 C° U204 High Temperature Sensor A
High Humidity 30054 40054 1 1 % U205 Low Humidity 30055 40055 1 1 % U206 High Humidity Sensor A


Fan Ramp 30103 - 1 % EnvState. FanRamp Cooling Ramp 30104 - 1 % EnvState. CoolRamp Free Cooling Ramp
Heating Ramp 30106 - 1 % EnvState. HeatRamp Humidification Ramp
30111 - x10 C° U301(ActTemp Set) Supply Temperature
FC Temperature 30115 - x10 C° U309 Sensor A Temperature
Return Humidity 30130 - 1 % EnvState.ActTe mp Actual Humidity SP
30131 - 1 % U302(ActHumS et) Sensor A Humidity
Fan Run Hour 30141 - 1 Hour S502 Compressor 1 Run Hour


[1] Any non-recognized alarm code by current firmware received from the DS control will trigger this event. [2] Timer mode: 0 = no, 1= yes. [3] Type of DT Room-Glycol: 0 = no, 1=contact, 2=value. [4] Predictive Hum Control: 0=relative, 1=compensated, 2=predictive. [5] Temp Control Algorithm: 0=proportional, 1=PD, 2=PDI; 3=intelligent; [6] When VFD is set to manual mode(coil 22), the host can control the VFD by the value of register 40019. The Manual VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information.
[7] Operating State: Bit 0-1: 00 unit off, 01 unit on, 10 unit standby Bit 2-3: 00 auto, 01 manual Bit 4-7: 0000 none, 0001 local user, 0010 alarm, 0011 schedule, 0100 remote user, 0101 external device, 0110 local display [8] Alarm state bit map: Bit0 =. Reset state bit1 = Active state ; bit2 = Acknowledge state, bit3-7 = Alarm Type,: 00000: Message 00001: Warning 00010: Alarm [9] Free-cool state: 0= Off, 1= Start, 2= On.

OpenComms - 485 Modbus Reference Guide
THE COMPANY BEHIND THE PRODUCTS With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics. While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Web Site www.liebert.com
Monitoring 800-222-5877 monitoring@liebert.com Outside the US: 614-841-6755
Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229
Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 Fax +39 049 5841 257
Asia 23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong 852.2.572.2201 Phone 852.2.831.0114 Fax 525502R5 REV.5
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. (c)2006 Emerson Electric Co.