www .rosemount-tg.com System Configuration Manual 300510EN, Rev AA December 2010 Raptor T ank Gauging System.
.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Rosemount Raptor Configuration with Rosemount T ankMaster WinSetup Cover Photo: system_config_fr ont.tif NOTICE Read this manual before working with t he produ ct.
.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com T able of Content s SECTION 1 Introduction 1.1 Manual Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.2 Technical Document ation .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor TOC -2 Table of Contents 5.3 Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16 5.3.1 Measurement Units . . . . . . . . . . . .
System Configuration Manual 300510EN, Rev AA December 2010 TOC -3 Rosemount Raptor Table of Contents SECTION 6 Device Handling 6.1 To Change Device Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 6.2 To Uninstall a Device . . . . .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor TOC -4 Table of Contents.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 1 Introduction 1.1 Manual Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 1- 1 1.2 T echnical Documentation . . . . . . . . .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 1-2 Section 1. Introducti on Section 7: Service F unctions A description of var ious functions su pported by T ankMaster WinSetup fo r service and maintenance of dif f erent Rapto r field devices.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 2 Raptor System Overview Raptor is a state-of-the art inventory and custody transfer radar t ank level gauging system.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 2-2 Section 2. Raptor System Overview Figure 2- 1. Raptor sy stem architecture 2230 Display 2240S T emperatu re T ransmitter.
System Configuration Manual 300510EN, Rev AA December 2010 2-3 Rosemount Raptor Section 2. Raptor System Overview T ankMast er HMI Software T ankMaste r is a powerful Windows-based Human Machine Interface (HMI) fo r complete tank inve ntory management.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 2-4 Section 2. Raptor System Overview Rosemount 5300 Guided W ave Radar The Rosem ount 5300 is a premium 2 -wire guided wave radar f or level measurement s on liquids, to be used in a wide range of medium accuracy applications under vario us tank cond itions.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 3 Using T ankMaster 3.1 What is T ankMaster? . . . . . . . . . . . . . . . . . . . . . . . . p age 3-1 3.2 T ankMaster Sof tware Package . . . . .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 3-2 Section 3. Using TankMaster 3.2 T ANKMASTER SOF TWARE PACKAGE Rosemount T ankMaster includes several software modules: .
System Configuration Manual 300510EN, Rev AA December 2010 3-3 Rosemount Raptor Section 3. Using TankMaster The Master Protocol Ser ver transfers configuration data and measured data between the T a nk Server and connected devices in a Rosemount T ank Gauging system.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 3-4 Section 3. Using TankMaster 3.3 INST ALLING THE T ANKMASTER SOF TWARE 3.3.1 System Requirement s The following system specification is recomme nded to run T ankMaster version 5.
System Configuration Manual 300510EN, Rev AA December 2010 3-5 Rosemount Raptor Section 3. Using TankMaster 3.3.3 Inst allation Procedure T o install the T ankMa ster soft ware package do the following: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 3-6 Section 3. Using TankMaster 3.4 INST ALLING A T ANK LEVEL GAUGING SYSTEM Setting up a T ank Level Gauging system comprises installation an d configuration of devices and tanks.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 4 The WinSetup Main W indow 4.1 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 4-3 4.2 T oolbar . . . . . . .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-2 Section 4. T he WinSet up Main Wind ow The Workspace window can be moved anywhere on the Main window . It can be docked to either side of the Main window , or it can be left floating.
System Configuration Manual 300510EN, Rev AA December 2010 4-3 Rosemount Raptor Section 4. The WinSetup Main Window 4.1 MENUS The menu bar at the to p of the screen contain s menus such as File , Vie w , Service , To o l s , and Help. Figure 4-4. The WinSetup menu Service menu o ptions are also availabl e by clicking the right mouse button.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-4 Section 4. T he WinSet up Main Wind ow 4.2 T OOLBAR The toolbar provides butto ns acting as shortcuts to certain menu options. Normally the T oolbar is visible. T o hi de it, open the View menu an d deselect the T oolbar option: Figure 4-7.
System Configuration Manual 300510EN, Rev AA December 2010 4-5 Rosemount Raptor Section 4. The WinSetup Main Window 4.3 ST ATUS BAR The status bar is located at the bo tt om of the T ankMaster main window . It provides general in formation about the current system state.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-6 Section 4. T he WinSet up Main Wind ow 4.4 WORKSP ACE - VIEWING T ANKS AND DEVICES The worksp ace displays an overview of all devices and t anks. Y ou can switch between two dif ferent views: Logical and Physical view .
System Configuration Manual 300510EN, Rev AA December 2010 4-7 Rosemount Raptor Section 4. The WinSetup Main Window 4.4.1 Worksp ace The Workspace window shows the installed tanks and devices and availa ble communication protocols. It a lso provides information about the configuration of installed devices.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-8 Section 4. T he WinSet up Main Wind ow 4.4.2 Icons In the Workspace windo w the different t anks and devices are represe.
System Configuration Manual 300510EN, Rev AA December 2010 4-9 Rosemount Raptor Section 4. The WinSetup Main Window 4.5 USER MANAGEMENT T ankMaster provides several protection levels allowing you to preven t unauthorized changes. These protection levels are categorized as User Access Levels and User Sub Access Levels .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-10 Section 4. T he WinSet up Main Wind ow 4.5.1 Logging On to T ankMaster 1. From the File menu choose Log On or click the Log On button in the WinSetup toolbar . 2. T ype your Username and Passwor d.
System Configuration Manual 300510EN, Rev AA December 2010 4-1 1 Rosemount Raptor Section 4. The WinSetup Main Window 4.5.2 T o Administrate User Account s T ankMaster allows you to setup a number of users at dif ferent levels and sub levels.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-12 Section 4. T he WinSet up Main Wind ow 6. Check that the new user appears in the User Manager window . Select the “Use first account...” box if you want a default user name to appear in the Log On dialog wh enever it is opened.
System Configuration Manual 300510EN, Rev AA December 2010 4-13 Rosemount Raptor Section 4. The WinSetup Main Window 4.5.3 T o Set Required Access Levels In T ankMaster WinSetup, you can set the acces.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-14 Section 4. T he WinSet up Main Wind ow 4.5.4 T o Change Protection Level of Sep arate Windows In T ankMaster it is possible to set a Protection Level for a specific window , e.
System Configuration Manual 300510EN, Rev AA December 2010 4-15 Rosemount Raptor Section 4. The WinSetup Main Window 4.5.5 T o Change Password T ankMaster allows you to change your password at any time: 1. From the T o ols/Admini strative T ools menu choose the Set Passwor d option.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 4-16 Section 4. T he WinSet up Main Wind ow 4.5.6 T o Change Inactivity Timeout T ankMaster WinSetup incl udes the optio n to set a timeout after which the current user is automatically logged of f.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 5 Inst alling a Raptor Level Gauging System 5.1 System Configuration Overview . . . . . . . . . . . . . . . page 5-2 5.2 Communication Protocol Setup .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-2 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.1 SYSTEM CONFIGURATION OVERVIEW 5.1.1 Prep arations Before installing a Rosemount T ank Gaug ing system you shou ld ensure that the following information is available: • A plan of all field devices and tanks.
System Configuration Manual 300510EN, Rev AA December 2010 5-3 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Figure 5-1. Raptor system installation procedu re GROUP BUS FIELD B.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-4 Section 5. Installing a Ra ptor Level Gauging Sy stem 4 Inst allation and Configuration of Ros emount 2410 T ank Hub The Rosemount 2410 sh ould be installed af ter the Rosemount 2160 Field Communication Unit.
System Configuration Manual 300510EN, Rev AA December 2010 5-5 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1.3 Using the Device Inst allation Wiza rd The device inst allation wizard guides you step-by-step through the inst allation procedure.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-6 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.2 COMMUNICATION PROTOCOL SETUP The TRL2 Modbus Master protocol is available as default protocol when Rosemount T ankMaster is installed on a T ankMaster wor k station.
System Configuration Manual 300510EN, Rev AA December 2010 5-7 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.2.1 Master Protocol Channel Configuration T o configure a communication protocol do the following: 1. Open the Protocols folder in the Workspace window .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-8 Section 5. Installing a Ra ptor Level Gauging Sy stem 7. Select the Communication tab. Parameters that control the communi cation between a T ankMaster work station and the field device s are configured in the Communication ta b.
System Configuration Manual 300510EN, Rev AA December 2010 5-9 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Modbus Master channel 1 is enabled.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-10 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.2.2 Slave Protocol Channel Configuration A Slave protocol allows you to collect dat a from the T ankMaster workstation to a host computer .
System Configuration Manual 300510EN, Rev AA December 2010 5-1 1 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Select the Communication tab.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-12 Section 5. Installing a Ra ptor Level Gauging Sy stem Advanced Configuration T o con figure dela y times and time-outs perform the following steps: 1. In the Slave Protocol Channel Configuration window , select the Communication ta b and click the Advanced butt on: 2.
System Configuration Manual 300510EN, Rev AA December 2010 5-13 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System T ank mapping configuration The slave protocol allows yo u to send data from a Rosemou nt T ank Gauging system to a host computer .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-14 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.2.3 Log File Configuration See chapter “Saving the Communication Log to File” on p age 7-39 for information on how to store a communication log on disk.
System Configuration Manual 300510EN, Rev AA December 2010 5-15 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.2.5 Protocol Server Configuration Y ou can specify which protocol serv ers that will be connected wh en starting T ankMaster WinSetup.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-16 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.3 PREFERENCES 5.3.1 Measurement Unit s S pecify units for inven tory calculations and measured variables such as level and temperature.
System Configuration Manual 300510EN, Rev AA December 2010 5-17 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.2 Ambient Air T emperature T o change the Ambient Air T emperature preference s do the following: 1. Select the desired server (e.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-18 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.3.3 Inventory Local Gravity and Ambient Air Density calculations are used for automatic density measurement s. T o change the Inventory settings do the following: 1.
System Configuration Manual 300510EN, Rev AA December 2010 5-19 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.4 Miscellaneous T o change parameters such as type of T ank Capacity T able, or Reference T emperature, do the following: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-20 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.3.5 Setting the Name Ta g P r e f i x e s T ankMaster Wi nSetup allows you to specify defaul t name tag prefixes that will appear automatically when installing new tanks a nd devices.
System Configuration Manual 300510EN, Rev AA December 2010 5-21 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.6 T ank V iew Layout The Setup T ank View tab is used to sp ecify variables to be presented in the T ank V iew window , see Section 7: Vi ewing T ank Data .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-22 Section 5. Installing a Ra ptor Level Gauging Sy stem 8. Click the Save A s button if you wish to st ore the cu rrent tank view table for future use. 9. Click the OK button to save the cur rent T ank View settings and close the window .
System Configuration Manual 300510EN, Rev AA December 2010 5-23 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.3.7 T ank V isibility The T anks Visibility tab let s you configure tanks on a remote t ank server to make them vis ible on the current W inOpi client.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-24 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.4 FIELD DEVICE INST ALLATION - OVERVIEW The Rosemount T ankMa s.
System Configuration Manual 300510EN, Rev AA December 2010 5-25 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.5 INST ALLING A ROSEMOUNT 2160 FCU 5.5.1 Introduction Installing a Rosemount 2160 Field Communication Unit (FCU) in a Rosemount Raptor system incl udes the following basic steps: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-26 Section 5. Installing a Ra ptor Level Gauging Sy stem 3. FCU 2160 communication setup. Choose the communication proto col channel which is associated with the T ankMaster workstation communicat ion po rt that is connected to the 2160 FCU.
System Configuration Manual 300510EN, Rev AA December 2010 5-27 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System NOTE! In case several FCUs are connecte d us ing th e same default ad dress (245), you will have to change th e addresses of the FCUs before the V erify command can be used.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-28 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. Configure the Group Bus (GB) and Field Bus (FB) port s on the FCU. a. Check that the correct port type is selected (1) .
System Configuration Manual 300510EN, Rev AA December 2010 5-29 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Configure the Slave Database. The FCU Slave Data base ensures th at the 2160 FCU req uests information from all the co nnected field devices.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-30 Section 5. Installing a Ra ptor Level Gauging Sy stem T o configure the FCU Slave Database: a. Select a free database position (1A, 2A ...) for the level gauge device to be configured.
System Configuration Manual 300510EN, Rev AA December 2010 5-31 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Summary of FCU Slave Dat abase entry fields Slave type 2410 Level, (pos 1A-32A) or 2410 T emp, (pos 1B-32B) Address The Modbus address used for the connected d evices.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-32 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.5.3 Examples of 2160 FCU Slav e Dat abase Configuration The fol.
System Configuration Manual 300510EN, Rev AA December 2010 5-33 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System For each level gauge the 24 10 Level address in the 2160 FCU Slave Database mu st be equal to the Level Modbus address in th e 2410 T ank Database.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-34 Section 5. Installing a Ra ptor Level Gauging Sy stem The 2410 T emp addre ss in the 2160 FCU Slave Database must be equal to the A TD Modbus address in the 2410 T ank Database .
System Configuration Manual 300510EN, Rev AA December 2010 5-35 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Example 2: several T anks connect ed to one 2410 T ank Hub This ex.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-36 Section 5. Installing a Ra ptor Level Gauging Sy stem Figure 5- 7. The same Level addresses must be co nfigured in the .
System Configuration Manual 300510EN, Rev AA December 2010 5-37 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.5.4 Summary of 2160 Inst allation and Configuration Select device type FCU 2160. Communication setup. Assign address and choose communication channe l.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-38 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.6 INST ALLING A ROSEMOUNT 2410 T ANK HUB The installation wizard covers basic configura tion of a Rosemoun t 2410 T ank Hub.
System Configuration Manual 300510EN, Rev AA December 2010 5-39 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Device T ype 3. From the Device T ype drop-down list, choose th e 2410 T ank Hub optio n. 4. T ype a name in the 2410 HUB T ag input field.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-40 Section 5. Installing a Ra ptor Level Gauging Sy stem Communication Setup 6. S pecify whether T ankMaster commun icates directly with the 2410 T ank Hub, or via a 2160 Field Communication Un it.
System Configuration Manual 300510EN, Rev AA December 2010 5-41 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 9. T o verify co mmunication with the 2410 T ank Hub, type the current Modbus address and click the V erify Communication button.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-42 Section 5. Installing a Ra ptor Level Gauging Sy stem T ank Data base Setup Each tank is re presented by a position in th e Rosemount 2410 ta nk database. Each device connected to the 2410 is mapped to a t ank position.
System Configuration Manual 300510EN, Rev AA December 2010 5-43 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 14. For each tank, specify a Modbus add ress in the Level Modbus Ad dress column to be associated with the level gauge.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-44 Section 5. Installing a Ra ptor Level Gauging Sy stem Device T ag Setup Level T ags and AT D Ta g s are configured auto.
System Configuration Manual 300510EN, Rev AA December 2010 5-45 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Local Display Setup Choose the p arameters to be displayed on the integral displa y panel on the Rosemount 2410 T ank Hub.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-46 Section 5. Installing a Ra ptor Level Gauging Sy stem 23. Enter the Display T oggle T ime . Information on the local display alternates between the selecte d items at a rate given by the Displ ay T oggle T ime value.
System Configuration Manual 300510EN, Rev AA December 2010 5-47 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Configuration Summary The 2410 T ank Hub Summary window shows information about all devices included in the 2410 T ank Dat abase for the current installation.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-48 Section 5. Installing a Ra ptor Level Gauging Sy stem Figure 5-9. The devices ap pear in the WinSet up workspace window Advanced Configuration The installation wizar d does not include all configuration options available for the 2410 T ank Hub.
System Configuration Manual 300510EN, Rev AA December 2010 5-49 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.6.2 Summary of T ank Hub Inst allation and Configuration Select device type 2410 T ank Hub Communication setup. Choose how the 2 410 connects to the T ankMaster work station.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-50 Section 5. Installing a Ra ptor Level Gauging Sy stem Local Display Setup. Choose the desired measurement unit s for the dif ferent tank p arameters. Select tanks and parameters.
System Configuration Manual 300510EN, Rev AA December 2010 5-51 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.7 INST ALLING A ROSEMOUNT 5900S RADAR LEVEL GAUGE The Rosemount 5900S Radar Le vel Gauge is typically installed in T ankMaster WinSetup as part of the Rosemoun t 2410 T ank Hub installation procedure.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-52 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.7.1 Configuration via the Properties Window This section describes the ba sic configuration procedure of a Rosemount 5900S Radar Le vel Gauge through the 5900S RLG Proper ties window .
System Configuration Manual 300510EN, Rev AA December 2010 5-53 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 3. Select the Communication tab. 4. V erify the communication settings. The Connected to HUB field indicates which tank that the 59 00S is associ ated with in the 2410 T ank Database.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-54 Section 5. Installing a Ra ptor Level Gauging Sy stem a. Enter the Un it ID . When changing the devi ce address, the Unit Id is used as an unique identifier of the device.
System Configuration Manual 300510EN, Rev AA December 2010 5-55 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System The following antenna types are available: 5900S with Horn Antenna.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-56 Section 5. Installing a Ra ptor Level Gauging Sy stem 10. In the 5900S RLG Properties window select the Geometry ta b: 1 1.
System Configuration Manual 300510EN, Rev AA December 2010 5-57 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System c. Minimum Level Dist ance (C) The Minimum Level Dist ance (C) is defined as the distance between the Zero Level (Dipping Datum Po int) and the minimum leve l (tank bottom) for th e product sur face.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-58 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.7.2 Inst alling a 5900S Using the Inst allation Wiza rd The ins.
System Configuration Manual 300510EN, Rev AA December 2010 5-59 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Using the inst allation wizard T o con figure a Ros emount 59 00S by using the WinSetup installation wizar d perform the following step s: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-60 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. In the 2410 T ank HUB T ag drop-down list choose the Rosemount 241 0 T ank Hub that the 5900S Radar Level Gauge is conne cted to.
System Configuration Manual 300510EN, Rev AA December 2010 5-61 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 12. In the 5900S RLG Summary window click the Finish button to verify the configuration and finish the inst allati on wizard.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-62 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.7.3 Advanced Configuration In addition to the bas ic configurat ion, there are advanc ed configur ation options available for the Rosemount 5900S Radar L evel Gauge.
System Configuration Manual 300510EN, Rev AA December 2010 5-63 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System T ank Environment Certain tank conditions ma y require ad ditio nal configuration of the 5900S Radar Level Gaug e in order to optimize measureme nt performance .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-64 Section 5. Installing a Ra ptor Level Gauging Sy stem The Advanced Configuration T ab The Advanced Co nfiguration tab pr ovides further configuration option s.
System Configuration Manual 300510EN, Rev AA December 2010 5-65 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.8 INSTA LLIN G AUXILIA RY T ANK DEVICES Auxiliary T ank Devices .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-66 Section 5. Installing a Ra ptor Level Gauging Sy stem 3. The 22XX A TD window includes basic and advanced configuration tabs.
System Configuration Manual 300510EN, Rev AA December 2010 5-67 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.8.2 Communication Parameter Setup The Communication t ab lets you verify the A TD communication settings. 1. In the 22xx A TD w indow selec t the Communication tab: 2.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-68 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.3 T emperature Sensor Configuration The 2240S MTT T emperature Sensor tab let s you configure a sensor connected to the Rosemount 2240S Mu lti-input T emperature T ransmitter .
System Configuration Manual 300510EN, Rev AA December 2010 5-69 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Manual Configurat ion 1. Ensure that the Use Auto Sensor Configuration check box is unchecked. 2. Choose conversion method in the Method input field.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-70 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.4 A verage T emperature Calculation This section gi ves a bri.
System Configuration Manual 300510EN, Rev AA December 2010 5-71 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 6. Y ou may exclude a certain te mperature element from the average temperature ca lculation by selecting the Exclude check box in the column next to the Position field.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-72 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.5 Auxiliary Sensor Configuration The 2240S MTT Auxiliary Sensor tab let s you configure a water level sensor connected to a Rosemount 224 0S Multi-input T emperature T ransmitter .
System Configuration Manual 300510EN, Rev AA December 2010 5-73 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 3. Enter the resulting level of fset value in the Level Offs et (X) input f ield. 4. Enter the Upper Dead Zone ( UDZ) and the Lower Dead Zone (LDZ) if needed.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-74 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.6 Advanced Parameter Source Configuration The Advanced Para m.
System Configuration Manual 300510EN, Rev AA December 2010 5-75 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 3. In the Source Device T ype/ID/No colum n, choose a me asurement device such as a pressure transmitter or any other type of instrument.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-76 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.8.7 2230 Graphical Field Display This section gives a brief description of how to configure a Rosemoun t 2230 Graphical Field Display .
System Configuration Manual 300510EN, Rev AA December 2010 5-77 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 6. If a second graphical field display is used, click the Configure T ank Display No 2 button and repeat step 1 th rough 4 above.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-78 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.9 INST ALLING A ROSEMOUNT 5400 The Rosemount 5 400 Radar Level .
System Configuration Manual 300510EN, Rev AA December 2010 5-79 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.9.1 Configuration via 5400 Properties This section describes the ba si c configuration procedure for a Rosemount 5400 series radar transmitter by using the 5400 RL T window .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-80 Section 5. Installing a Ra ptor Level Gauging Sy stem 4. V erify the tank positi on. The Connected to HUB field shows the name of the 2410 T ank Hub and the tank positi on that the 5400 is mapped to in the 2410 t ank database.
System Configuration Manual 300510EN, Rev AA December 2010 5-81 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Select the Antenna tab . 8. Chose Antenna T ype . It is possible to choose between predefine d antenna types or User Defined fo r non-standard anten nas.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-82 Section 5. Installing a Ra ptor Level Gauging Sy stem 1 1. For still pipe applications select the E nable still pipe/Bridle Measurement s check box and enter the P ipe Inner Diameter .
System Configuration Manual 300510EN, Rev AA December 2010 5-83 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System c. Minimum Level Dist ance (C) . The Minimum Level Distance (C) is defined as the dist ance between the Zero Level (Dipping Datum Point) and the minimum level for the product surface ( tank bottom).
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-84 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.9.2 Inst alling a 5400 Using the Inst allation Wiza rd The inst.
System Configuration Manual 300510EN, Rev AA December 2010 5-85 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Using the inst allation wizard T o con figure a Ros emount 54 00 by using the WinSetup installation wizar d perform the following step s: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-86 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. In the 2410 HUB T ag drop-down list choo se the Rosemount 2410 T ank Hub that the 5400 Radar Level T ransmitter is connected to.
System Configuration Manual 300510EN, Rev AA December 2010 5-87 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 13. In the 5400 RL T Summary window , click the Finish button to finish the installation wizard. If the configurat ion needs to be changed click the Back button until the desired window appears.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-88 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.9.3 Advanced Configuration In addition to the basic configu ration there are some advanced co nfiguration options available for the Rosemount 5400 transmitter.
System Configuration Manual 300510EN, Rev AA December 2010 5-89 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System T ank Environment Certain product conditions in the t ank may require special configuration options to be used in order to optimi ze measuremen t performance of the 5400 Radar Level T ransmitter .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-90 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.10 INSTALLING A ROSEMOUNT 5300 The Rosemou nt 5300 Guided W ave.
System Configuration Manual 300510EN, Rev AA December 2010 5-91 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.10.1 Configuration via 5300 Properties This section describes the ba si c configuration procedure for a Rosemount 5300 Guided W ave Radar by using the 5300 GWR window .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-92 Section 5. Installing a Ra ptor Level Gauging Sy stem 3. Select the Communication tab.
System Configuration Manual 300510EN, Rev AA December 2010 5-93 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 7. Select the Probe tab . 8. Choose a Probe T ype that corresponds to the probe that is used on the 5300. It is possible to choose a prede fined (standard) prob e, or User Defined for non-st andard probes.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-94 Section 5. Installing a Ra ptor Level Gauging Sy stem 12. Select t he Geometry tab. 13. Enter the T ank Refere nce Height (R) . The T ank Reference he ight is defined as the dist ance from the Upper Reference Point to the Zero Reference Point 14.
System Configuration Manual 300510EN, Rev AA December 2010 5-95 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.10.2 Inst alling a 5300 Using the Inst allation Wiza rd The installation wizard in T ankMaster WinSetup is a tool th at may be used to insta ll and configure a Rosemount 5300 Guided W ave Radar and other devices.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-96 Section 5. Installing a Ra ptor Level Gauging Sy stem Using the inst allation wizard T o configure a Rosemount 5 300 by using the WinSetup in stallation wizard perform the following step s: 1.
System Configuration Manual 300510EN, Rev AA December 2010 5-97 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 6. In the 2410 T a g drop-down list choose the Rosemount 2410 T a nk Hub that the 5300 radar is conne cted to. 7. Enter the Modbus address that is used for the 5300 .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-98 Section 5. Installing a Ra ptor Level Gauging Sy stem 13. In the 5300 GWR Summary win dow click the Finish button to finish the installation wizard. If the conf iguration nee ds to be ch anged click th e Back button until the desired window ap pears.
System Configuration Manual 300510EN, Rev AA December 2010 5-99 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.10.3 Advanced Configuration In addition to the b asic configuration there are advanced config uration options available for the Rosemount 5300 Gu ided Wave Ra dar .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-100 Section 5. Installing a Ra ptor Level Gauging Sy stem For Meas urement Mode Liquid Product Level enter the Product Dielectric Range . In some applications there is heavy vap or above the product surface having a significant influence on the level measurement.
System Configuration Manual 300510EN, Rev AA December 2010 5-101 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1 INST ALLING A T ANK 5.1 1.1 Overview Basically the purpose of the t ank installation procedure is to associate various devices to the right t anks.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-102 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.1 1.2 St arting the T an k Inst allation Wiza rd T o start the t ank installation wizard do the following: See also “Installing a New T ank” on page 5-103 .
System Configuration Manual 300510EN, Rev AA December 2010 5-103 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1.3 Inst alling a New T ank T o install and configure a t ank by using the WinSetup installation wizard do the following: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-104 Section 5. Installing a Ra ptor Level Gauging Sy stem 6. Assign devices to the current tank. Choose a device from the list in the A vailable Devi ces pane and click the arrow button to move the de vice to the Select ed Devices pane.
System Configuration Manual 300510EN, Rev AA December 2010 5-105 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Show 2160 FCU Slave Positions ( Advanced) The “Show Slave Positions” check bo x sh ould only be used for advanced ta nk configuration of device s which are not supporte d by the Raptor syst em.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-106 Section 5. Installing a Ra ptor Level Gauging Sy stem 8. Configure the tank.
System Configuration Manual 300510EN, Rev AA December 2010 5-107 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System Figure 5-1 1. A measur ement instrument which is mapped in the 22.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-108 Section 5. Installing a Ra ptor Level Gauging Sy stem Advanced Configuration The Advanced T ank Setup window allows you to ch ange mapping of tank measurement variables to gauge outpu t.
System Configuration Manual 300510EN, Rev AA December 2010 5-109 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 10. S pecify parameter value range to be used in various windows for present ation of measurement data. Also choose whether to use measurement values (Automatic) fr om the available instrumen ts or manual values.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 10 Section 5. Installing a Ra ptor Level Gauging System The Va l u e R a n g e parameters ( Minimum and Maximum) let s you to scale bar graphs in the T ank View window and other windows (in Winsetup as well as WinOpi) where bar graphs are used to display product levels.
System Configuration Manual 300510EN, Rev AA December 2010 5-1 1 1 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1.4 Summary of T ank Inst allation and Configuration Ta n k Ty p e Choose the tan k type option that corresponds to the actual tan k.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 12 Section 5. Installing a Ra ptor Level Gauging System 5.1 1.5 T o Change T ank Configuration When the t ank is installed and configured the current settin gs can be modified at any time by opening the corr esponding Properties dialog.
System Configuration Manual 300510EN, Rev AA December 2010 5-1 13 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.1 1.6 T o Uninst all a Ta n k T o remove a tank from the WinSetup wor kspace do the following : 1. In the Workspace window selec t the tank you want to remove.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 14 Section 5. Installing a Ra ptor Level Gauging System 5.12 ADDING A T ANK TO A RAPTOR SYSTEM New tanks can easily be added to a Raptor system. The procedure will be slightly diffe rent depending on the spec ific system configuration.
System Configuration Manual 300510EN, Rev AA December 2010 5-1 15 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.12.1 Adding a New T ank and a New 2410 T ank Hub T o add a new tank and new field devices to a Raptor system do the following: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 16 Section 5. Installing a Ra ptor Level Gauging System 7. Configure the Slave Databa se with Modbus addresses for the new level gauge and A TD devices, see “In stalling a Rosemoun t 2160 FCU” on page 5-2 5 for more information.
System Configuration Manual 300510EN, Rev AA December 2010 5-1 17 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.12.2 Adding a New Ta n k t o a n Existing 2410 Ta n k H u b In.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-1 18 Section 5. Installing a Ra ptor Level Gauging System 7. Select the T ank Dat abase tab: 8. V erify that the new device s connec ted to the T ankbus appear in the Device T ype column.
System Configuration Manual 300510EN, Rev AA December 2010 5-1 19 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 1 1. V erify that a new t ank position appears in the right-hand pane of the Ta n k Database window .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-120 Section 5. Installing a Ra ptor Level Gauging Sy stem 12. T ype a name in the Ta n k N a m e field.
System Configuration Manual 300510EN, Rev AA December 2010 5-121 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 17. V erify that the T a nkMaster Le vel T ag is correct or enter a ne w one. 18. V erify that the T a nkMaster A T D T ag is correct or enter a new one.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-122 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.13 LEVEL GAUGE CALIBRATION Normally a minor level gauge adjus tment is needed in order to achieve good agreement between m easured and actual product levels.
System Configuration Manual 300510EN, Rev AA December 2010 5-123 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.13.2 Using the Calibrate Function The Calibrate function is a tool which allows you to calculate the Correction Factor for still-pipe measur ements and the Calibration Distance.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-124 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.14 T ANK CAPACITY The tank geometr y can be defined in a strapping table; the T ank Cap acity Ta b l e (TCT). The TCT is used to convert a product level to a vo lume.
System Configuration Manual 300510EN, Rev AA December 2010 5-125 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 5.15 T ANK ENTRY The T ank Entry window is used for s pecifying a number of product parame ters to be used for inventory calculatio ns.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-126 Section 5. Installing a Ra ptor Level Gauging Sy stem 5.16 SETTING UP A HYBRID SYSTE M This is a description of how to inst all a Rosemount Raptor on-line d ensity measurement system to be used for mass calculations.
System Configuration Manual 300510EN, Rev AA December 2010 5-127 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 8. For Local Gravity choose calculation method Manual or Calculated . The Local Gravity is used as input for calculating the Observed Density .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-128 Section 5. Installing a Ra ptor Level Gauging Sy stem 13. V erify that the p arameters V apor Pressure and Liquid Pressure are mapped to the correct pressur e sensors (Source Device).
System Configuration Manual 300510EN, Rev AA December 2010 5-129 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 18. Choose source parameter and measurement unit for V apor Pressure and Liquid Pressure. 19. V erify measurement s by opening the Ta n k V i e w window ( Service>T anks>Open T ank View ).
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-130 Section 5. Installing a Ra ptor Level Gauging Sy stem 22. Enter the P1 Senso r Position , i.e. the cent er position o f the Liquid Pressure se nsor memb rane. 23. Enter the Hybrid Min Level .
System Configuration Manual 300510EN, Rev AA December 2010 5-131 Rosemount Raptor Section 5. Installing a R aptor Level Gauging System 28. Make sure that the Reference Density is measu red au tomatically , i.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 5-132 Section 5. Installing a Ra ptor Level Gauging Sy stem 33. Ensure that V alue Source is set to Automatic for the Liquid Pressure and V apor Pressure measurement varia bles.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 6 Device Handling 6.1 T o Change Device Configuration . . . . . . . . . . . . . . page 6-1 6.2 T o Uninstall a Device . . . . . . . . . . . . . .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 6-2 Section 6. Device Handling A number of tabs are available fo r configuration of communication parameters, t ank geometry , device specific parameter s and advanced configuration options.
System Configuration Manual 300510EN, Rev AA December 2010 6-3 Rosemount Raptor Section 6. Device Handling 6.2 T O UNINST ALL A DEVICE A device can be uninstalled from the WinSetup workspace at any time. However , the associated tank must be un installed first.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 6-4 Section 6. Device Handling 3. Click the Change button. 4. In the right-hand side of the Select Devices window , select the device and click the arrow button. The device will be removed from the Selected Devices pane to the Availa ble Devices pane on the left-hand side.
System Configuration Manual 300510EN, Rev AA December 2010 6-5 Rosemount Raptor Section 6. Device Handling 6. Open the Ta n k s folder: 7. V erify that the device (L T -TK-1 in this case) is no longer associated with the tank. 8. Open the Devices folder: 9.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 6-6 Section 6. Device Handling.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 7 Service Functions 7.1 System St atus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 7-1 7.2 Customizing the T ools Menu in WinSetup .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-2 Section 7. Service Fu nctions 7.2 CUSTOMIZING THE T OOLS MENU IN WINSETUP T o add custom options to the T ools menu do the following: 1. Choose the T ools> Applicatio ns menu option.
System Configuration Manual 300510EN, Rev AA December 2010 7-3 Rosemount Raptor Section 7. Service Functions 4. Press the button next to the Command field. 5. Browse to the program file that will be associated with the new T ools menu option as given in the Menu T ext field.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-4 Section 7. Service Fu nctions 7.3 USER DEFINED T EM PERATURE CONVERSION The Rosemount 2240S Mul ti-input T emperature T ransmitter supports the use of non-standa rd spot temperature sens ors.
System Configuration Manual 300510EN, Rev AA December 2010 7-5 Rosemount Raptor Section 7. Service Functions 7.3.1 User Defined Linearization Ta b l e When using a resistance temperature sensor , the electrical resist ance values can be converted to tempe rature values by using a table of resist ance and temperature value s.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-6 Section 7. Service Fu nctions 7.3.2 User Defined Formula For a res istance temperat ure sens or , the relatio n between .
System Configuration Manual 300510EN, Rev AA December 2010 7-7 Rosemount Raptor Section 7. Service Functions 7.3.3 User Defined Individual Formula When using User Defined Individual Formula, a mathema.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-8 Section 7. Service Fu nctions 7.4 VIEWING INPUT AND HOLDING REGISTERS In a Rosemount Raptor system measuremen t data is cont inuously stored in Input registers of devices such as the Rosemount 2410 T ank Hub, Rosemount 5900S Radar Level Gau ge, and other devices.
System Configuration Manual 300510EN, Rev AA December 2010 7-9 Rosemount Raptor Section 7. Service Functions 7.5 T O EDIT HOLDING REGISTERS Most Holding registers can be edited simply by typi ng a new value in the appropriate Va l u e input field. Some holding registers (marked gr ey in the V alue column) can be edited in a separ ate window .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-10 Section 7. Service Fu nctions 4. Click the Apply button to store the register data, or click the Close button to store and close the window .
System Configuration Manual 300510EN, Rev AA December 2010 7-1 1 Rosemount Raptor Section 7. Service Functions 7.6 VIEW DIAGNOSTIC REGISTERS The V iew Diagnostic Registers window sho ws a predefined set of diagnostic input and holding registers.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-12 Section 7. Service Fu nctions A grey back ground colo r of the table cell in th e V alue column mean s that the register is of either Bitfield or ENUM type. An expanded Bitf ield/ENUM window can be ope ned for that type of registers.
System Configuration Manual 300510EN, Rev AA December 2010 7-13 Rosemount Raptor Section 7. Service Functions 4. The order in which registers are displaye d in the View Diagnost ic Registers window can be configured. Select a register in the right pane and press to move it upwards, or to move it downwards in the list.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-14 Section 7. Service Fu nctions 7.7 LOGGING MEASUREMENT DAT A Raptor device s such as the Ros emount 2410 and Rosemoun t 5900S suppor t logging of diagnostic registers. This fu nction is useful for verifying that the gauge works proper ly .
System Configuration Manual 300510EN, Rev AA December 2010 7-15 Rosemount Raptor Section 7. Service Functions 7.8 SAVING AND LOADING DAT ABASE REGISTERS Input and Holding Reg isters of the Rosemount 5900S a nd the 2410 can be stored on disk. This can be useful fo r backup purposes and troubleshooting .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-16 Section 7. Service Fu nctions 7.8.2 T o Save Device Registers Multiple Devices T o save a backup copy of the current configuration for multip le devices, do the following: 1.
System Configuration Manual 300510EN, Rev AA December 2010 7-17 Rosemount Raptor Section 7. Service Functions 7.8.3 T o Recover a Device Dat abase T ankMaster WinSetup of fers the option to replace the current hold ing register database with a backup database s tored on d isk.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-18 Section 7. Service Fu nctions 7.9 UPGRADING THE DEVICE SOF TWARE T ankMaster WinSetup allows you to upgrade the software of Rosemount Raptor level gauges and othe r devices.
System Configuration Manual 300510EN, Rev AA December 2010 7-19 Rosemount Raptor Section 7. Service Functions 7. Click the St art Programming button to activate device progr amming. See, for example, th e Rosemount 5900 S Reference Manu al (Docum ent No.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-20 Section 7. Service Fu nctions 7.10 T ANK SCAN The Ta n k S c a n window allows you to view tank echoes an d setup the most important p arameters to enable a radar level gau ge such as the Rosemount 5900S to sep arate a surface echo from disturbing echoes and noise.
System Configuration Manual 300510EN, Rev AA December 2010 7-21 Rosemount Raptor Section 7. Service Functions 4. The T ank Scan window cont ains the Graph Area, Legend/Op tions area, File S torage buttons, and vario us action buttons.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-22 Section 7. Service Fu nctions 7.10.1 Graph Area When the Ta n k S c a n window opens, WinSetup reads tank dat a from the gauge. The proces s is indicated by a progress bar in the lower right corn er of the T ank Scan w indow .
System Configuration Manual 300510EN, Rev AA December 2010 7-23 Rosemount Raptor Section 7. Service Functions 7.10.2 Legend/Options The following items can be shown in the graph ar ea (check the appro.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-24 Section 7. Service Fu nctions A TP (Amplitude Threshold Points) A weak disturbing echo can be filtered out by creating a curve of Amplitude Threshold Point s .
System Configuration Manual 300510EN, Rev AA December 2010 7-25 Rosemount Raptor Section 7. Service Functions T ank Bottom The Ta n k B o t t o m is shown in red: Echo Peaks Echo Peaks are shown in bl.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-26 Section 7. Service Fu nctions 7.10.3 File Storage T o save T ank Scan dat a displayed in the Graph Area 1. In the T ank Scan window click the Save button. 2. Enter a name to identify the tank scan data.
System Configuration Manual 300510EN, Rev AA December 2010 7-27 Rosemount Raptor Section 7. Service Functions T o export t ank scan dat a to an external file T ank sc an data can be saved to file for viewing w ith the T ank Echo Viewer (T ools>T ank Echo Viewer): 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-28 Section 7. Service Fu nctions 7. Press Ye s to create t he file. 8. Press OK .
System Configuration Manual 300510EN, Rev AA December 2010 7-29 Rosemount Raptor Section 7. Service Functions T o load data from a saved file into the Graph Area 1. In the T ank Scan window press the Stored Echoe s button. 2. Select the file to be loaded.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-30 Section 7. Service Fu nctions 7.10.4 Action Buttons The following buttons can be found in the Ta n k S c a n window: Save See “File S torage” on p age 7-26. S tored Echoes See “File S torage” on page 7-26.
System Configuration Manual 300510EN, Rev AA December 2010 7-31 Rosemount Raptor Section 7. Service Functions 7.10.5 Editing All the element s having handles can be edited. Each handle may be moved by using the mouse pointer . Clicking the right mouse button on a handle opens a dialog window .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-32 Section 7. Service Fu nctions T o add a False Echo Area or an Amplitude Thresh old Point 1. Click the right mous e button in the graph area where you would like to add a False Echo Area or an Amplitude Th reshold Point : 2.
System Configuration Manual 300510EN, Rev AA December 2010 7-33 Rosemount Raptor Section 7. Service Functions 7.1 1 V IEWING T ANK DAT A WinSetup offers the op tion to view data from a single tank or a group of t anks. V arious parame ters such as L evel, Leve l Rate, and Average T emperature can be displayed.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-34 Section 7. Service Fu nctions 7.1 1.2 Viewing Dat a From a Single Ta n k T o view measurement data for a single tank, do the following: 1. In the WinSetup workspace, select the desired t ank icon.
System Configuration Manual 300510EN, Rev AA December 2010 7-35 Rosemount Raptor Section 7. Service Functions 7.12 VIEWING ALARM STAT US WinSetup lets you view alarm status for all tanks, a cert ain tank group, or a single tank. T o view the current alarm status for all t anks do the following: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-36 Section 7. Service Fu nctions T o v iew the ala rm status of a single ta nk : 1. Open the Ta n k s folder and select the desired t ank: 2. From the Vi ew menu choose Alarms .
System Configuration Manual 300510EN, Rev AA December 2010 7-37 Rosemount Raptor Section 7. Service Functions 7.13 PROTOCOL HANDLING 7.13.1 Logging the Channel Communication WinSetup allows you to log communication on the var ious communication protocol channels.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-38 Section 7. Service Fu nctions 4. Click the OK button to open the Communication Log window . The Channel Commu nication Log window is continuously updated with new data. T o stop WinSetup from feeding new dat a click the right mouse button and choose Freeze .
System Configuration Manual 300510EN, Rev AA December 2010 7-39 Rosemount Raptor Section 7. Service Functions 7.13.2 Saving the Communication Log to File T o save the communication log to file: 1. Select the protocol channel icon. 2. Click the right mouse button and choose Properties, or from the Service menu choose Channels/Properties .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-40 Section 7. Service Fu nctions 5. The Multiple Log files section allows you to op timize file size for storing on floppy disk. Choose the One File option if you pref er the log t o be stored in a single file.
System Configuration Manual 300510EN, Rev AA December 2010 7-41 Rosemount Raptor Section 7. Service Functions 9. Choose the Selected Function Code option if you would like to log a specific function . 10. Choose one of the device address options; Any Address or Select ed Address .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-42 Section 7. Service Fu nctions 7.13.3 Searching for Connected Devices Y ou can se arch for devices on the communication protocol channe ls: 1. In the WinSetup workspace , open the Protocols folder and th e appropriate protocol sub folder .
System Configuration Manual 300510EN, Rev AA December 2010 7-43 Rosemount Raptor Section 7. Service Functions 7.13.4 Channel Stat is t i cs The Protocol S tatistics function is a tool which can be used to check the quality of communication between the T ankMaster workst ation and the connected field devices.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-44 Section 7. Service Fu nctions 7.14 T ANKMASTER ADMINISTRATOR The T ankMaster Administrator program provides the option to select which T ankMaster programs that will start automatically when the PC is turned on.
System Configuration Manual 300510EN, Rev AA December 2010 7-45 Rosemount Raptor Section 7. Service Functions 7.14.1 Log on T o be able to make any changes in the T ankMaster Administrator window you need to use the Log on function. T o log on to the T ankMaster Administrator do the fo llowing: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-46 Section 7. Service Fu nctions 7.14.2 Changing the Admini strator Program password T o change the T ankMaster Administrator password, do th e following: 1. Open the T ankMaster Ad ministrator window .
System Configuration Manual 300510EN, Rev AA December 2010 7-47 Rosemount Raptor Section 7. Service Functions 7.14.3 Autost art The Autostart fun ction lets you specify programs to st art automatically when the T ankMaster computer is st arted. T o con figure the A utostart option: 1.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-48 Section 7. Service Fu nctions 7.14.4 Backup The backup function can be used to save configuration dat a for devices and tanks as well as worksp ace settings for WinSetup and WinOpi.
System Configuration Manual 300510EN, Rev AA December 2010 7-49 Rosemount Raptor Section 7. Service Functions 4. Choose the desired file destinatio n. T an kMaster automatically creates subdirectories for WinOpi, WinSetup, and T ankserver files. 5. Click the OK button to close the Browse for Folder window and return to the Backup window .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-50 Section 7. Service Fu nctions 7.14.5 Restore If the PC operating system has crashed resulting in corrupt T ankMaster files, the T ankMaster settings can be restored by using the backup files.
System Configuration Manual 300510EN, Rev AA December 2010 7-51 Rosemount Raptor Section 7. Service Functions 5. The Restore Bac kup Wizard lets you restore tank and device configuration, BatchServe r data and Historical dat a. Y ou may also restore WinOpi and WinSetup configurations such as group s, color , network set tings etc.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-52 Section 7. Service Fu nctions 8. The following options will also need to be specified: 9. The first option, Cr eate a backup of the current configuration, should not be used if the restor e function is us ed to replace corru pt configuration files.
System Configuration Manual 300510EN, Rev AA December 2010 7-53 Rosemount Raptor Section 7. Service Functions 12. The Copy Log button can be used to store the restore log in the ...RosemountServer Log directory . Click the Ne xt button to continue. 13.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-54 Section 7. Service Fu nctions 7.14.6 File V ersion Information The File Info option allows you to view a list of all the files included in the T ankMaster software p ackage.
System Configuration Manual 300510EN, Rev AA December 2010 7-55 Rosemount Raptor Section 7. Service Functions 7.14.7 Processes T o view the ru nning T an kMaster prog rams, click the Processes button in the T ankMaster Admin istrator window: The Shut down TM button let s you close all T ankMaster programs except the T ankMaster Administrator .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 7-56 Section 7. Service Fu nctions.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Section 8 Menu Guide 8.1 File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8-2 8.2 View . . . . . . . . . . . . . . .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-2 Section 8. Menu Guide 8.1 FILE If a workstation is selected , new options are available in the File menu: 8.2 VIEW New Connection Connect to another tank server . Install New > T ank Install new tanks by starting the t ank installation wizard.
System Configuration Manual 300510EN, Rev AA December 2010 8-3 Rosemount Raptor Section 8. Menu Guide 8.3 SERVICE The service options are found in the Service menu or by clicking the right mouse button on a specific folder , device, or tank. Servers > Rename Change the server name.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-4 Section 8. Menu Guide When selecting a t ank in the T anks folder , new options are a vailable under the Service > T .
System Configuration Manual 300510EN, Rev AA December 2010 8-5 Rosemount Raptor Section 8. Menu Guide 2410 T ank Hub See the Rosemount 2410 T ank Hub Reference Manual ( Document no. 300530EN) for more information. Devices > Expand all Show all devices connected to the selected Rosemount 2410 T ank Hub.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-6 Section 8. Menu Guide 5900S Radar Level Gauge See the Rosemount 5900S Reference Manual (Document no. 300520EN) for more information. Devices > Uninstall Remove the selected device.
System Configuration Manual 300510EN, Rev AA December 2010 8-7 Rosemount Raptor Section 8. Menu Guide Auxiliary T ank Devices (A TDs) (2240S, 2230 etc.) For more information about the various A TD devices, see the reference manual for the specific device.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-8 Section 8. Menu Guide When selecting a specific protoc ol, new options will be available: Protocols > Disable Disable the selected protocol. Properties Open the protocol Properties window and choose a communication channel.
System Configuration Manual 300510EN, Rev AA December 2010 8-9 Rosemount Raptor Section 8. Menu Guide 8.4 T OOLS 8.5 HELP Applications Customize the T ools menu. Administrative T ools > User Manager Manage the user accounts. User Information Display information about the current user .
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor 8-10 Section 8. Menu Guide.
System Configuration Manual 300510EN, Rev AA December 2010 Rosemount Raptor www .rosemount-tg.com Index Numerics 2160 FCU Slave Database 5-29 , 5-32 , . . . . . . . . . . 5-35 , 5-38 , 5-43 , 5-120 2160 Field Communication Uni t . 2-3 2240S temperature sensor conversion method .
Rosemount Raptor Index-2 System Configuration Manual 300510EN, Rev AA December 2010 F FCU . . . . . . . . . . . . . . . . . . 2-3 , 5-25 communication setup . . . . . 5-26 slave database setup . . . . . 5-29 FCU Slave Database . . . . . . . . 5-29 Field Bus ports .
Index-3 Rosemount Raptor System Configuration Manual 300510EN, Rev AA December 2010 Protocols folder . . . . . . . . . . . . . . 5-7 Protocols/Properties . . . . . . . . . . 5-7 R Rapid Level Change 5-63 , 5-89 , 5- 99 Recover database . . . . . . . .
Rosemount Raptor Index-4 System Configuration Manual 300510EN, Rev AA December 2010 Tank Bottom Type . . . . . . . . . . . 5-62 Tank Capacity Table . . . 5-19 , 5-124 Tank Configuration . . . 5-106 , 5 - 111 Tank Connection Length .5 - 5 5 , 5-81 Tank Connection Length (TCL) .
.
System Configuration Manual 300510EN, Rev. AA December 2010 Rosemount Raptor Emerson Process Management © 2010 Rosemount T ank Radar AB. All rights reserved. Rosemount and the Rosemount logotype are trademarks o f Rosemount Inc. HART is a trademark of the HART Communication Foundation.
Ein wichtiger Punkt beim Kauf des Geräts Emerson 300510EN (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Emerson 300510EN noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Emerson 300510EN - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Emerson 300510EN reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Emerson 300510EN erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Emerson 300510EN besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Emerson 300510EN verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Emerson 300510EN. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Emerson 300510EN gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.