Benutzeranleitung / Produktwartung 4K VA 20K VA UPS des Produzenten EMC
Zur Seite of 23
4K VA – 20K VA UPS ■ User’s and Installation Manual ■ I EMC St atement s CISPR 22 NOTICE: Pursuant to CISPR 22 rules, this product has been tested and thereby complies with the conditions of a.
II CONTENTS 1. Introduction ...........................................................................................1 2. System desc ription............................................................................... 1 2.1 General de scription..
IV The instructions contained with in this saf e ty manual are d eemed important and should be closely followed at all times during installa tion and follow-up maintenance of the UPS and batteries.
2 Fig.1. Block diagram Efficiency Optimizer function The Efficiency Optimizer function is a new feature for the UPS adding cost effectiveness, minimizing power loss and r educing power consumption. Altern ating between bypass and on-line modes is achieved autom atically and in accordance with the condi tions of the utility power.
4 3. Safety information Information presented h ere is vital to all p ersonnel and please also read the UPS safet y manual. Storage and Transporta tion Please handle with extreme caution since a hi gh amount of energy is contained with the batteries. Always keep th e unit in position as marked on the packaging and nev er drop the unit.
6 5.2 Rear panel vie ws 4K/5KV A (120VDC ) Rear panel 7 6KV A Rear panel (W itho ut ISO).
8 6KV A Rear panel (W ith ISO) 9 8K~10KV A Rear panel (W itho ut ISO).
10 8K~10 KV A Rear panel (W ith ISO) 11 12KV A Rear p anel (ISO and With ISO).
12 15/20 KV A Rear panel (ISO and With ISO) 13 5.3 Connection to mains and loads (4 000 - 20 000 VA) Only qualified specialists or technicians who conform to applicable safety standards may carry out the inst allation of this equipment. The install ation must further comply with all local legislation and regu lations .
14 figures 2 and 3 for proper installation. Refer to local wiring rules. z Should computer or alarm connect ions be used, use connections according to ch apter 6 of the manual provided with that option. The connections can be referred to on the rear panel.
16 5.4 Default settings at the factory On the LCD display you will find severa l of the UPS param e ters to select. Default settings are as follows: Settings Selection Factory default Output Voltage S.
18 USB port (option) Connecting the UPS to your computer is a ccomplished through the USB port on the back of your computer. USB compliant hardware and operating s ystem will be necessary including installation of a UPS driver. The se rial port cannot be used when using the USB port.
20 7.3 Control panel functions Operation of the UPS is indicate d on the mon itor panel with five LED indicators and an LCD screen. This display is als o capable of aler ting the user with audible alarms. ON : This green LED is l it when UPS has been turned on.
22 UPS configurations 1. Various settings that have been chosen are shown in the UPS setting display. 2. To enter configuration mode, press the “FUNC” button for one second. The first configuration parameter will be shown on the LC D display. 3. Press the “FUNC” button to scroll through the p arameters.
24 **) Note: In order for the UPS and power ma nagement software to operate normally, Manual Bypass should always be set to OFF as the load will no t be protected by the unit when Manual Bypass is ON. This is aimed for operating an ex ternal mainten a nce bypass switch.
26 7.5 Trouble shooting Displayed on LCD Audible Alarm Alarm Descriptio n What Y ou Should Do Output Overload Two Beeps per second The UPS is overloaded (in Line Mode). Your equipment needs more power than the UPS can provide. The UPS operates in bypass.
28 9. Technical Specifications For model with 3 Phase in 1 Phase out Tower model (with LCD display) 8K31 10K31 12K31 15K31 20K31 Capacity (VA) 8000VA 10000VA 12000VA 15000VA 20000VA Capacity C apacity.
30 Net Weight kg (lb) W/O IS OTR 5 0 ( 1 1 0 ) 86.0 (189.2) 80(176) Shipping W eight kg (lb) W /O ISOTR 5 3 ( 1 1 6 . 7 ) 106.0 (233.2) 101.5(2 23.3) Dimensions W x D x H mm (inc h) W/ ISOTR 257 x 590 x 700 (10.1"x23.2"x 27.6") 342 x 690 x 715 (13.
32 Communication R S-232 Serial Port and USB Type Sealed, main tenance-free lead acid batteries DC Voltage (V) Battery (Tow er ) TBD TBD 240V / 12V7.2AH x 20 240V / 12V9AH x 20 Typical Recharge Time t.
34 10. VGD RM 6KVA(3U+3U) Mechanical A. VGD 6K RACK-MOUNT(3U+3U) DESIGN : (1) BASIC COMPONENT : INCLUDING 3U-UPS & 3U-BA TT . CABINET FRONT VIEW R E A R V I E W 35 (2) UPS REAR P ANEL COMPONENTS: H. TERMINAL BLOCK I. BREAKER J. EXTERNAL BA TTER Y CONNECTOR K.
36 (4) FEA TURE of REMOTE CONTROL FUNCTION: a. Remove the original right si de panel and take apart th e control panel unit. Then assemble the blank right side panel. b. Connect the C ontrol panel unit and Remote contr ol port from rear side. 37 c. Running the remote-c ontr ol function.
38 B. 5 in 1 FUNCTION BRACKETS on RACK-MOUNT 3U DESIGN: (1) 19” Rack installation: Mount the 3U rack-mount in a 19-inch EIA 310 C standard rack. 19” rack width 39 (2) 23” Rack installation: Change the position of the two mounting br ackets to mount the 3U rack-mount in a 23-inch EIA 310 C standard r ack.
40 (4) W all installation: Move the mounting brackets from the front to the side and attach the bracke ts by screws. Then mount th e UPS to the wall as the below pictures shown. (5) Installation with rear Bracket: W e can use bracket to support the rear side of UPS or battery cabinet.
Ein wichtiger Punkt beim Kauf des Geräts EMC 4K VA 20K VA UPS (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie EMC 4K VA 20K VA UPS noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für EMC 4K VA 20K VA UPS - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von EMC 4K VA 20K VA UPS reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über EMC 4K VA 20K VA UPS erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon EMC 4K VA 20K VA UPS besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von EMC 4K VA 20K VA UPS verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit EMC 4K VA 20K VA UPS. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei EMC 4K VA 20K VA UPS gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.