T echnical Services Department DSCA P/N: LA990009-1220 First Issue: March 2003 GAC P/N: LA484007-1351 Printed in the U.S.A. DENSO SALES CALIFORNIA, INC.
LIMITED W ARRANTY DENSO SALES CALIFORNIA, INC. ("DENSO") warrants its MOVINCOOL Products only to the extent stated in its of ficial written warranties.
OPERA TION MANUAL OFFICE PRO 18.
ii.
iii T able of Contents FOREWORD ..................................................................................... 1 Definition of T erms .................................................................... 1 GENERAL WARNINGS & CAUTIONS .......
iv.
1 FOREWORD Congratulations on pur chasing the MovinCool portable air conditioner . This manual explains how to install and operate the MovinCool Office Pro 18 portable air conditioning unit. Please r ead this operation manual thoroughly to familiarize yourself with the featur es of the unit and to ensure years of r eliable operation.
2 GENERAL W ARNINGS & CAUTIONS • All electrical work, if necessary , should only be performed by qualified electrical personnel. Repair to electrical components by non-certified technicians may result in personal injur y and/or damage to the unit.
3 INVENTOR Y After unpacking your MovinCool unit, please check to make sur e you have the following items: •O f fice Pr o 18 MovinCool Unit (1) • Operation Manual/W arranty Car d (1) NOTE: If any of these items were not included in the box or appear damaged, please contact your MovinCool reseller for replacement.
4 INST ALLA TION Choosing an Installation Site CAUTION: Following are some pr ecautions to consider befor e choosing your installation site. Please review car efully as improper installation may r esult in personal injury or damage to the unit. • Do not use the unit in areas wher e leakage of flammable gas may occur .
5 INST ALLA TION (cont.) Moving the Unit Unlock the casters and push the MovinCool unit using the side handles to a flat, level surface and set the casters back to the LOCKED position.
6 INST ALLA TION (cont.) Plugging in the Unit • Check the pr ongs and surface of the power cord plug for dust/dirt. If dust and/or dirt are pr esent, wipe of f with a clean, dry cloth. • Check the power cord, plug and pr ongs for damage or excess play .
7 FEA TURES Office Pr o 18 Features: • An electronic contr ol panel, which allows the user to contr ol the unit’ s operation easily . • Dual fan speeds (either HIGH or LOW) in both COOL and Fan Only modes. • Digital display that indicates the temperatur e SET POINT (either Fahrenheit or Celsius) in which the COOL Mode will operate in.
8 OPERA TION Control Panel Before operating the unit, it is important to familiarize yourself with the basic controls located on the contr ol panel. ➀ COOL ON/OFF Activates/deactivates the COOL mode/ Button turns the unit off. ➁ F AN ON/OFF Activates/deactivates the HIGH or LOW Buttons fan mode.
9 OPERA TION (cont.) Control Panel (Cont.) ➆ T emperature Scale Illuminates to indicate the curr ent LED temperatures being displayed ar e either in °C or °F; also displays the clock when programming. ➇ AM/PM LED Illuminates to indicate AM or PM time of day .
10 OPERA TION (cont.) Operating in COOL Mode ➀ The unit can be operated in COOL mode by pr essing the COOL ON/OFF button (LED illuminates). NOTE: In COOL mode the unit can only be turned off by pressing the COOL ON/OFF button again, not by pressing the fan buttons.
11 OPERA TION (cont.) How to Set a Program ➀ Setting a ST ART TIME Press the Pr ogram SET button. The Program SET button and ST ART TIME LEDs will illuminate. Pr ess the HRS and MIN buttons to set the ST ART TIME. ➁ Setting an END TIME Press the Pr ogram SET button until the END TIME LED illuminates.
12 OPERA TION (cont.) How to Set a Program (Cont.) NOTE: • The unit will return to the previous mode if a program is turned off while it is running. • The Program RUN LED flashes while a program is running. It is illuminated continuously when the program mode is activated.
13 OPERA TION (cont.) Operating Modes The Office Pr o 18 operates in two modes, Fan Only and COOL. When in Fan Only mode, the unit circulates the sur rounding air .
14 OPERA TION (cont.) Emptying the Drain T ank During COOL mode, condensate will accumulate in the drain tank. When the drain tank becomes full, the FULL T ANK LED will flash and the unit will shut off automatically . NOTE: If you want to empty the drain tank, while the unit is in operation, press the COOL ON/OFF button to turn the unit off.
15 DISCHARGE HOSE DRAIN PUMP DRAIN PUMP RESERVOIR OPERA TION (cont.) Drain Pump Kit (Optional) A drain pump kit (CPK-3) is available to allow continuous operation and to eliminate the need for a drain tank. • When the water collects to level (A) in the pump reservoir , the drain pump begins to operate and dischar ges the water .
16 DAIL Y INSPECTION & MAINTENANCE Emptying the Drain T ank To empty the drain tank, refer to instructions on page 14. Cleaning the Air Filters Clean the air filters once a week. If the unit is used in a dusty environ- ment, mor e frequent cleaning may be requir ed.
17 DAIL Y INSPECTION & MAINTENANCE (cont.) Filter Cleaning Method ➀ Remove dust from the element with a vacuum cleaner , or rinse in cold or lukewarm water . If the element is extremely dir ty , wash with a neutral deter gent. ➁ After the element has been cleaned, rinse with clean running water , allow to dry , then r einstall.
TROUBLESHOOTING Self-Diagnostic Codes Self-Diagnostic Codes will be displayed on the Contr ol Board under the following conditions: Code Condition dF When the evaporator thermistor disengages the compr essor . FL When the drain tank switch shuts off the unit ( FULL T ANK LED flashes).
TECHNICAL SPECIFICA TIONS ITEM/FEA TURES Of fice Pro 18 Rating Conditions dry bulb 95º F (35º C) wet bulb 83º F (28.2º C) humidity (60%) Specifications power frequency 60Hz line voltage single phase 115 V power consumption 1.7 KW current consumption 15.
20.
LIMITED W ARRANTY DENSO SALES CALIFORNIA, INC. ("DENSO") warrants its MOVINCOOL Products only to the extent stated in its of ficial written warranties.
T echnical Services Department DSCA P/N: LA990009-1220 First Issue: March 2003 GAC P/N: LA484007-1351 Printed in the U.S.A. DENSO SALES CALIFORNIA, INC.
Ein wichtiger Punkt beim Kauf des Geräts Denso OFFICE PRO 18 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Denso OFFICE PRO 18 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Denso OFFICE PRO 18 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Denso OFFICE PRO 18 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Denso OFFICE PRO 18 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Denso OFFICE PRO 18 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Denso OFFICE PRO 18 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Denso OFFICE PRO 18. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Denso OFFICE PRO 18 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.