(Supersedes PQ404-5) PQ404-6 CHS 161-048642-001 OCTOBER, 1983 4 and Installation, Operation RENEWAL PARTS IDENTIFICATION Horizontal Electric Steam Boiler Model Number CHS 0 – 150 PSI © 2010 Chromalox, Inc. Power CC Size of Output Nominal 90˚C Amps Standard Lbs.
2 High Pressure Control Pressure Gauge Manual Reset Pressure Conrol Electric Control Box Blow Down Drain Valve (L) Return Inlet (J) Heating Elements Step Sequencer (Optional) Wall 30” C B A Wall D I H E Blow Down Drain Valve (L) Check Valve Water Inlet (K) Water Level Control G 60” Safety Valve (G) Steam Outlet (F) INST ALLA TION (cont’d.
3 INST ALLA TION (cont’d.) SPECIAL INSTRUCTIONS FOR CUSTOMERS SUPPL YING THEIR OWN CONDENSA TE OR PUMP SYSTEMS. 1. Check the voltage of the motor before making the wiring connec- tion. Some Chromalox boilers are supplied with dual voltage sys- tems.
4 WIRING (cont’d.) Figure 8 – T ypical Wiring Diagram Power Circuit T erminal Block T o Other Heater Groups To Other Heater Groups T ypical 3 Phase Heater Group To Power Curcuit Relay Step Sequenc.
NOTES 1. Motor , Solenoid V alve and Dotted Control W iring are included if Motor and Pump package is supplied. Solenoid V alve only is sup- plied with 991 17 W ater feed. 2. 1/3 HP Motor is controlled directly without use of Motor Starter . After proper wiring and piping of boiler system is complete, testing of controls can start.
6 RECOMMENDED ST ART -UP PROCEDURES 1. Close globe valve on outlet side of boiler . (Customer Supplied) 2. T urn on boiler and allow pressure to build up to operating pressure. 3. Only open globe valve by quarter turns at first, introducing small- er amounts of steam into process.
7 OPERA TION (cont’d.) Figure 16 – T ypical Wiring for Automatic Blowdown System Now turn the wheel on the large timer until the “of f” tab passes the “time now” arrow . The “boiler normal” light should go out and the valve should begin to open.
8 AUXILIAR Y LOW W A TER CUT -OFF (See page 4 for Wiring Diagram) Operation Operation of this control is accomplished by sensing a minute AC current flowing between submerged contact probe in the boiler shell.
9 5. Connect the ohmmeter between controller terminals W and R and raise the set point of the controller above the actual pressure being measured. The ohmmeter should read the full value of the poten- tiometer measured in step 4 (135 ohms for an L91B).
10 The Sequence Reverser accomplishes its tasks and shows the rela- tive use of each of ten beat stages during the first four days of the cycle. This is how the work load would be distributed on a boiler with- out Sequence Reverser .
11 MAINTENANCE RENEW AL P ARTS IDENTIFICA TION INSTRUCTIONS FOR ELEMENT REPLACEMENT CAUTION: Before installing your new elements, be sure the McDonnell-Miller low-water cut-off is operating perfectly and the float chamber and lower equalizer column are completely clear of sludge or other foreign matter .
2150 N. RULON WHITE BLVD., OGDEN, UT 84404 Phone: 1-800-368-2493 www.chromalox.com RENEW AL P ARTS IDENTIFICA TION (cont’d.) Low Water Cutoff and Water Feed Controls Description Part Number Complete Assembly . . . . . . . . . . . . . . . . . . . . .
Ein wichtiger Punkt beim Kauf des Geräts Chromalox PQ404-6 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Chromalox PQ404-6 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Chromalox PQ404-6 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Chromalox PQ404-6 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Chromalox PQ404-6 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Chromalox PQ404-6 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Chromalox PQ404-6 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Chromalox PQ404-6. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Chromalox PQ404-6 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.