Thermidistat™ Control Installation, Start-Up, and Operating Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. INDEX Page SAFETY CONSIDERATIONS ...........
INSTALLATION Step 1—Thermidistat Control Location Thermidistat Control should be mounted: • Approximately 5 ft (1.5m) from floor. • Close to or in a frequently used room, preferably on an inside partitioning wall. • On a section of wall without pipes or duct work.
3. A2—for 2-speed air conditioner 4. H2—for 2-speed heat pump 5. dF—for 1-speed dual fuel 6. d2—for 2-speed dual fuel 7. HS—for 1-speed heat pump with Intelligent Heat Staging (3-stage auxiliary heat with 40FK, FK4C, or FV4A Series fan coils.
3. Use up and down buttons to move between F and C on large display. 4. Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.
Option 10—Dual Fuel Equipment All dual fuel installations must be equipped with a high pressure switch to turn off compressor under a high indoor coil pressure condition.
will be supplied, resulting in additional outputs being turned on. If room overheats, specified outputs will not turn off, guaranteeing a sufficiently warm leaving air temperature during defrost.
3. Use up and down buttons to move between OF and ON on large display. Factory default is OF. 4. Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.
TO TEST COOLING AND DEHUMIDIFICATION: Press MODE button until COOL icon turns on. Cooling begins within 10 sec and remains on for 4 minutes. If system is 2-speed, low speed comes on for first 2 minutes, followed by high speed for second 2 minutes. At the end of 4-minute run, cooling stops, and MODE reverts back to OFF.
4. Auto and Fan Humidify The 2 choices of AUTO and FAN can be selected together. This provides both functions simultaneously. 5. Humidify Off The humidify function can be turned off completely. This does not require changing existing set points. To Select Humidification (Between NORMAL, FAN, AUTO, FAN and AUTO, or OFF) (See Table 4.
humidity removal is desired, this should be done, if possible. Fan coils have the capability of removing this off delay, furnaces do not. On FK or FV Fan Coils, set delay tap to 0/0. On standard fan coils, a jumper can be cut to disable off delay. Refer to fan coil Installation Instructions for details.
Vacation Dehumidification Normal Dehumidify, Cool to Dehumidify, and Dehumidify OFF, are all available in vacation mode, and selection of 1 of these can be different from that of occupied. Vacation dehumidification selection and set points are remembered the next time vacation is used.
THERMIDIST A T CONTROL CONFIGURA TION RECORD Date Owner/Operator A) Hardware Configuration Switch A ____ AC/HP Select. (OFF = AC) Switch B ____ 1 or 2-Speed Compressor . (OFF = 1-Speed) Switch C ____ Smar t Recov ery . (OFF = Enable) Switch D ____ Installer T est.
Ein wichtiger Punkt beim Kauf des Geräts Carrier Access Thermidistat (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier Access Thermidistat noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier Access Thermidistat - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier Access Thermidistat reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier Access Thermidistat erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier Access Thermidistat besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier Access Thermidistat verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier Access Thermidistat. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier Access Thermidistat gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.