Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS .................1 INST ALLA TION ............................1 - 9 Step 1 — Complete Pre-Installation Checks ..1 • UNCRA TE UNIT • INSPECT SHIPMENT • CONSIDER SYSTEM REQUIREMENTS Step 2 — Rig and Mount the Unit .
T able 1A — Physical Data (English) UNIT 38AQS008 60 Hz 50 Hz OPERA TING WEIGHT (lb) Aluminum Coils (Standard) 540 594 Copper Coils (Optional) 608 662 RIGGING WEIGHT (lb) Aluminum Coils (Standard) 590 644 Copper Coils (Optional) 658 712 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Quantity .
T able 2 — Refrigerant Piping Sizes LINEAR LENGTH OF PIPING — ft (m) UNIT 38AQS 0-25 (0-7.6) 25-50 (7.6-15.2) 50-75 (15.2-22.9) 75-100 (22.9-30.5) Line Size (in. OD) L S L S LSLS 008 1 ⁄ 2 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 LEGEND L— Liquid Line O D— Outside Diameter S— Suction Line NOTES: 1.
UNIT 38AQS008 UNIT W/ALUMINUM COIL UNIT W/COPPER COIL WEIGHT CHART (WITH ALUMINUM COIL) WEIGHT CHART (WITH COPPER COIL) Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg 60 Hz 1 ⬘ -8 ⬙ [508.
All field wiring must comply with NEC (U.S.A.) and lo- cal requirements. Install field wiring as follows: 1. Install conduit through side panel openings. 2. Install power lines to connections as shown in Fig. 8. W rap connections with electrical tape.
LEGEND NEC — National Electrical Code TXV — Thermostatic Expansion V alve *Accessory item. †Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Re- fer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes.
T able 4 — Electrical Data UNIT 38AQS NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y MINIMUM DISCONNECT Min Max RLA LRA FLA MCA MAX FUSE OR HACR BRKR AMPS FLA LRA 008 208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177 460-3-60 414 508 15.
T able 5A — Accessory Electric Heater Data (60 Hz) UNIT 40RMQ HEA TER P ART NO. V -PH-Hz NOMINAL kW HEA TER AMPS MCA* MOCP* 008 CAELHEA T001A00 240-3-60 5 12.0 25.6 30 CAELHEA T002A00 480-3-60 6.0 12.3 15 CAELHEA T003A00 575-3-60 5.0 1 1.9 15 CAELHEA T004A00 240-3-60 10 24.
2 CORNER POST RACEWA Y THERMOST A T FIELD CONNECTION POWER WIRING CONNECTIONS Fig. 6 — Fusible Plug Locations LEGEND NO TE: The 8 o’clock position is shown abo ve . Fig. 7 — TXV Sensing Bulb Location TXV — Ther mostatic Expansion V al ve LEGEND Fig.
ST ART -UP Preliminary Checks 1. Check that all internal wiring connections are tight and that all barriers, covers, and panels are in place. 2. Field electrical power source must agree with unit name- plate rating. 3. Ensure all service valves are open.
Should room temperature continue to fall, circuit R-W is made through second-stage thermostat bulb. If optional elec- tric heat package is used, a relay is energized, bringing on supplemental electric heat. When thermostat is satisfied, con- tacts open, deenergizing contactor and relay; motors and heat- ers deenergize.
5. Remove crankcase heater from compressor base. 6. Remove compressor holddown bolts and lift compres- sor of f basepan. 7. Remove compressor from unit. 8. Clean system. Add new liquid line filter drier (biflow type). 9. Install new compressor and position in unit.
Fig. 16 — Cooling Mode Operation Fig. 17 — Heating Mode Operation 13.
TROUBLESHOOTING CHART , COOLING CYCLE LEGEND TXV — Thermostatic Expansion V alve 14.
TROUBLESHOOTING CHART , HEA TING CYCLE LEGEND N.C. — Normally Closed 15.
.
.
Manufacturer reserves the right to discon tinue, or change at any time, specifications or designs without notice and wit hout inc urring obligation s. PC 111 Catalog No.
ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST AR T -UP? (Y/N) CHECK POWER SUPPL Y .
Manufacturer reserves the right to discon tinue, or change at any time, specifications or designs without notice and wit hout inc urring obligation s. PC 111 C atalog No.
Ein wichtiger Punkt beim Kauf des Geräts Carrier 38AQS008 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier 38AQS008 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier 38AQS008 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier 38AQS008 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier 38AQS008 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier 38AQS008 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier 38AQS008 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier 38AQS008. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier 38AQS008 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.