Benutzeranleitung / Produktwartung 38APD025-100 des Produzenten Carrier
Zur Seite of 36
Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without notice and without inc urring obligations. Catalog No . 04-53 380002-01 Printed in U .S .A. Form 38AP-1SI Pg 1 8-09 Replaces: Ne w Installation Instr uctions CONTENTS Page SAFETY CONSIDERA TIONS .
2 DO ME ST IC UN IT S — S tandard 38AP unit packaging con- sists of coil protection only . Skids ar e not pr ovided. If overhead rigging is not available at the jobsite, place the unit on a skid or pad before dragging or rolling. When rolling, use a minimum of 3 rollers.
3 Table 1 — 38AP025-050 U nit Physical Data — English LEGEND *T ypical o perating charge with 25 ft o f interconnecting pipi ng. Operati ng charge is appro ximate f or maximum system capacity . Unit is factory supplied with nitrogen holding ch arge.
4 Table 2 — 38AP060-100 U nit Physical Data — English LEGEND *T ypical o perating charge with 25 ft o f interconnecting pi ping. Operati ng charge is appro ximate f or maximum system capacity . Unit is factory supplied with nitrogen holding charge .
5 Table 3 — 38AP025 -050 Unit Physical Data — SI LEGEND *T ypical oper ating charge with 7.62 m of interconnecting pipi ng. Operating charge is appro ximate f or maximum system capacity . Unit is factory supplied with nitrogen holding ch arge. Refrigera nt charge f or dual circuit uni ts is the total for b ot h circuits .
6 Table 4 — 38AP060 -100 Unit Physical Data — SI LEGEND *T ypical operating charge with 7.62 m of intercon necting piping. Oper ating charge is appro ximate f or maximum system capacity . Unit is factory supplied with nitrogen holding charge . Refrigerant cha rge f or dual circuit units is the total for b oth circuits .
7 Table 5 — Oper ational Corner Weights wit h Refrigerant Charge (Appro ximate) 38APS Unit (lb) 38APD Unit (lb) 38APS Unit (kg) 38APD Unit (kg) 38APS UNIT SIZE TOT A L WEIGHT OPERA TIONAL CORNER WEI.
8 Fig. 3 — Rigging Labels Fig. 4 — Perimeter Support Channe l SIZES 025 TO 060 SIZES 070 T O 100 a38-71 15 a38-71 16 LEGEND ASTM — American Society for T esting a nd Materials 4 x 24 in.
9 UNIT ST AND ARD WEIGHT , lb (kg) CENTER OF GRA VITY , in. (mm) HEIGHT , in. (mm) PO WER ENTR Y , in. (mm) SER VICE V AL VE CONNECTIONS, in. (mm) X Y H P Suction Liquid Standard 38APS025 1077 (489) 17.8 (452) 36.9 (937 ) 61.0 (1549) 24.9 (632) 1 5 / 8 (41) 5 / 8 (16) 38APD025 1095 (497) 17.
10 UNIT ST ANDARD WEIGHT , lb (kg) CENTER OF GRA VITY , in. (mm) HEIGHT , in. (mm) SER VICE V AL VE CONNECTIONS, in. (mm) X Y H Suction Liquid Standard 38APS040 1968 (893) 35.0 (869) 44.0 (1118) 73.0 (1854) 2 1 / 8 (54) 7 / 8 (22) 38APD040 2094 (950) 33.
11 UNIT ST ANDARD WEIGHT , lb (kg) CENTER OF GRA VITY , in. (mm) HEIGHT , in. (mm) SER VICE V AL VE CONNECTIONS, in. (mm) Suction Li quid X Y H Circuit A Circuit B Standard 38APD070 2450 (1111) 50.9 (1293) 40.6 (1031) 73.0 (1854) 2 1 / 8 (54 ) 1 5 / 8 (41) 7 / 8 (22) Low Sound 38APD070 2522 (1144) 50.
12 UNIT ST ANDARD WEIGHT , lb (kg) CENTER OF GRA VITY , in. (mm) HEIGHT , in. (mm) SER VICE V AL VE CONNECTIONS, in. (mm) Suction Li quid X Y H Circuit A Circuit B Standard 38APD080 2610 (1184) 67.6 (1716) 40.2 (1020) 73.0 (1854) 2 1 / 8 (54) 1 5 / 8 (41) 7 / 8 (22) 38APD090 2835 (1286) 72.
13 OUTDOOR FAN LAYOUT ( S in g le and Dual Circuit) S IZE S 025-0 3 0 S IZE S 040-050 S IZE S 060-070 COMPRE SS OR LAYOUT DUAL CIRCUIT S IZE S 025-0 3 0 S IZE S 040-060 S IZE S 070-0 8 0 TOP VIEW S IZ.
14 40RU a38-7098_gs LEGEND *Field supplied. †If dou b le suction riser is re q uired f or piping system, size short riser (3 ft maximum) according to Fig.
15 a38-7099_gs NO TES: 1. All piping must follo w standard refrigerant piping techni q ues. Ref er to Carrier System Design Manual f or details. 2. All wiring must comply with the applica b le local and national codes.
16 Table 6 — Refriger ant Specialt ies Part Numbers LEGEND *Bushing re q uired to fit 5 / 8 in. line. NO TE: 1. Fil ter drie rs hav e b een sized b ased upon 1 to 2 p sig pressure drop clean in accordance with ARI Standard 710. 2. All pip e sizes are OD inches.
17 Step 3 — Make Refrigerant Piping Connections The units have large suction lines to minimize friction loss- es. The units also have the ability to operate at low capacity . Because of these capabilities, use special care with suction pip- ing and suction risers to ensure proper compressor oi l return under all operating conditions.
18 Table 7 — Refrigerant Piping Re quirements 38APS025-050 Single-Circuit Units (60 Hz) 38APD025-100 Dual-Circuit Units (60 Hz) LEGEND NO TES: 1. Shading indicates dou b le suction riser re q uired on units if con- densing unit is located higher than ev aporator .
19 Table 7 — Refrigerant Piping Requirement s (cont) 38APS025-050 Single-Circuit Units (50 Hz) 38APD025-100 Dual-Cir cuit Units (50 Hz) LEGEND NO TES: 1. Shading indicates dou b le suction riser re q uired on units if con- densing unit is located higher than ev aporator .
20 Table 7 — Refrigerant Piping Requirement s (cont) 38APS025-50 Single-Circuit Unit s Double Suction Riser (60 Hz) 38APD025-100 Dual-Circ uit Units Double Suction Riser (60 Hz) LEGEND 1. Refer to the figure locat ed to the right f or suction line piping locations .
21 Table 7 — Refrigerant Piping Requirement s (cont) 38APS025-50 Single-Circuit Unit s Double Suction Riser (50 Hz) 38APD025-100 Dual-Circuit Units Double Suction Riser (50 Hz) LEGEND 1. Refer to the figure locat ed to the right f or suction line piping locations .
22 LIQUID LINE SOLENOID V AL VE — Fi el d - su p p l ie d liquid line solenoid valve(s) must be in stalled at the evaporator if coil surface area is exceeded per T able 8. Install liquid line solenoid valve just ahead of the TXVs (thermostatic expansion valves) which will be mounted at the evaporator .
23 LEGEND *Field-supplied. †Field-supplied when re q uired. See T a b le 8. Fig. 13 — Re quired Location of Solenoid Valves a nd Recommended Filter Drier and Sight Glass Locat ions for 38APD025-1 00 Dual-Circui t Units LLS — Li q uid Line Solenoid TXV — Ther mostatic Expansion V alve *Field-supplied.
24 SECTION SECTION SECTION SECTION a38-7120 SECTION SECTION SECTION SECTION LEGEND NO TE: F or units with single condensat e pan, lo wer coil section is first on, last off.
25 Table 8 — Requirements for Installation of Liquid Line Solenoid Valve 38AP UNIT SIZE CIRCUIT MAXIMUM ALLO W ABLE EV APORA T OR SURF ACE AREA WITHOUT LIQUID LINE SOLENOID V AL VE (sq ft) 4-Row , 1 / 2 in. T ube 6-Row , 1 / 2 in. T ube 8-Row , 1 / 2 in.
26 Step 4 — Make Electrical Connection s PO WE R S UP PL Y — The electrical characteristic s of the available power supply must agree with the unit nameplate rating. Supply voltage must be within the limits shown in T ables 9-12. See T able 13 for incoming power options.
27 Fig. 18 — Field Po wer Wiring LEGEN D NO TES : 1. Factory wiring is in accordance with UL 1995 standards. Field modifi cations or additions must b e in compliance wit h all applica b le codes. 2. All unit s or modules hav e single point primary power connection.
28 a38-7125 * * LV T TERMINAL S TRIP † 6 * LV T TERMINAL S TRIP Fig. 20 — Constant Volume Applic ation Wiring Diagra m 2-Stage Thermos tat Control, Sizes 025 -030 — without Digital Scroll O ption *Not re q uired f or single circuit units. a38-7126 Fig.
29 Fig. 23 — Variable Air Volume Appl icatio n Wiring Diagram, Sizes 025-100 *See Fig. 19 for EA T and SA T location. †Not re q uired for single circuit units. LV T TERMINAL S TRIP * * † a38-7127 *See Fig. 19 fo r EA T and SA T location. †Not re q uired f or single circuit units.
30 Legend and Notes f or Fig. 20-24 LEGEND NO TES: 1. F actory wir ing is in accordance with UL 1995 standards. Field modifications or additions must b e in compliance with all appli- ca b le codes. 2. All units or modules hav e single point primary power connec- tion.
31 Table 9 — 38APS Standa rd Condenser Fan Electrical Da ta Table 10 — 38APS Low Sound Condenser Fa n Electrical Data LEGEND NO TES: 1. Units are suita b le for use on electrical systems where v oltage supplied to the unit terminals is not b elow or a b ov e the liste d minimum and maximum limit s.
32 Table 11 — 38APD Standard Condenser Fan Electrica l Data LEGEND NO TES: 1. Units are suita b le for use on electrical systems where voltage supplied to the unit ter minals is not b elow or a b ov e the listed minimum and maximum limits . Maximum allo wa b le phase im b alance is: voltage 2%; amps 10%.
33 Table 12 — 38APD Low Sound C onde nser Fan Electrical Data LEGEND NO TES: 1. Units are suita b le for use on electrical systems where voltage supplied to the unit ter minals is not b elow or a b ov e the listed minimum and maximum limits . Maximum allo wa b le phase im b alance is: voltage 2%; amps 10%.
34 Table 13 — Unit Incomin g Power Options LEGEND NO TES: 1. T er minal b loc k high SCCR option units must use approv ed fuses to meet high SCCR rating. 2. High SCCR disconnect option un its can use either approv ed fuse or circuit b reaker f or incoming power protection.
35.
Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No .
Ein wichtiger Punkt beim Kauf des Geräts Carrier 38APD025-100 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier 38APD025-100 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier 38APD025-100 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier 38APD025-100 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier 38APD025-100 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier 38APD025-100 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier 38APD025-100 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier 38APD025-100. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier 38APD025-100 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.