Benutzeranleitung / Produktwartung 38AKS028-044 des Produzenten Carrier
Zur Seite of 24
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 BEFORE INST ALLA TION .....................1 - 3 Rigging ......................................1 Placing Unit .................................3 Mounting Unit .
T able 1A — Physical Data — English UNIT 38AKS 028 034 044 COMPRESSOR Reciprocating Semi-Hermetic No. ...T ype 1...06E9265 1...06E9275 1...06E9299 No. Cyls (ea)...Speed, Rpm (60/50 Hz) 6...1750/1460 Capacity Steps 3 Oil Charge*, Pt 20.0 20.0 19.0 Oil Pressure Switch (psi) Set Points — Cutout 6 6 2 Differential — Cut-in 14 Max.
Placing Unit — There must be 4 ft (1220 mm) for ser- vice on all sides of unit, and a minimum of 8 ft (2440 mm) clear air space above unit. For multiple units, allow 8 ft (2440 mm) separation between units for airflow and service.
Receiver — No receiver is provided with the unit; it is recommended that one not be used. Piping Procedure — Do not remove run-around pipe from suction and liquid line stubs until piping connections are ready to be made. Pass nitrogen or other inert gas through piping while brazing, to prevent formation of copper oxide.
T able 2A — Refrigerant Piping Sizes — 60 Hz SINGLE SUCTION RISERS UNIT 38AKS LENGTH OF INTERCONNECTING PIPING, FT (M) 16-25 (4.9-7.6) 26-50 (7.9-15.
Power Supply — Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in T able 3. IMPOR T ANT : Operating unit on improper supply volt- age, or with excessive phase imbalance, constitutes abuse and may af fect Carrier warranty .
FIELD CONNECTIONS 1. Main Power — Bring wires from the fused disconnect switch through hole in bottom rail of unit to control box 11 12 (Fig. 6 and 7) and connect terminals , , and 13 line side of terminal block TB1 (see Fig.
Fig. 6 — Dimensional Drawing, 38AKS028,034 LEGEND NEC — National Electrical Code VAV — V ariable Air V olume NOTES: 1. There must be minimum (2440 mm) 8 ft.
LEGEND NEC — National Electrical Code NOTES: 1. There must be minimum (2440 mm) 8 ft. clear air space above unit. 2. The approximate operating weight of the unit is: 50 HZ AND 60 HZ UNIT WT (Lb) WT (Kg) 38AKS044 2437 1 106 38AKS044C 2745 1246 Fig. 7 — Dimensional Drawing, 38AKS044 3.
LEGEND AFS — Airflow Switch CB — Circuit Breaker EQUIP — Equipment FU — Fuse GND — Ground LLS1 — Liquid Line Solenoid for Solenoid Drop Control LLS2 — Liquid Line Solenoid for Capacity Control NEC — National Electrical Code, U.
BPR — Bypass Relay C— Contactor , Compressor DB — Circuit Breaker CR — Control Relay CM — Control Module EQUIP — Equipment FC — Fan Contactor Fig. 9A — Component Arrangement — 60 Hz FM — Fan Motor FU — Fuse GND — Ground LLSV — Liquid Line Solenoid V alve NEC — National Electrical Code (U.
LEGEND BPR — Bypass Relay C— Contactor , Compressor CB — Circuit Breaker CR — Control Relay CM — Control Module EQUIP — Equipment FC — Fan Contactor FM — Fan Motor FU — Fuse GND — Ground LLSV — Liquid Line Solenoid V alve NEC — National Electrical Code (U.
ST ART -UP Initial Check Do not attempt to start the condensing unit, even mo- mentarily, until the following steps have been com- pleted. Compressor damage may result. 1. Check all auxiliary components, such as air -handling equip- ment, and other equipment.
Fig. 10 — 38AKS028 Charging Chart, 50/60 Hz 14.
Fig. 1 1 — 38AKS034 Charging Chart, 50/60 Hz 15.
Fig. 12 — 38AKS044 Charging Chart, 50/60 Hz 16.
FOR SER VICING ONL Y — T o speed up the 5-minute anti- short cycle, a temporary jumper may be placed between ter- minals T1 and T6 of the control module. This jumper must be removed after servicing is com- plete. Failure to remove this jumper is considered abu- sive treatment and will void the Carrier warranty.
COMPRESSOR END AND RIGHT -SIDE VIEW TRAN2 CB1 CB2 TB3 FC3 FC2 FC CM CR1 TRAN1 TB2 C1 COMPRESSOR END, CONTROL P ANEL REMOVED OIL PRESSURE SAFETY SWITCH COMPRESSOR END, LEFT -SIDE ACCESS DOOR (JUNCTION BOX COVER REMOVED) LIQUID LINE SERVICE VA LV E COMPRESSOR END, RIGHT -SIDE ACCESS DOOR Fig.
Fan Adjustment — Adjust fan as shown in Fig. 14. Oil Charge — Compressors are factory charged with oil as follows: COMPRESSOR AMOUNT pints (liters) 06E9265 20.0 (9.4) 06E9275 20.0 (9.4) 06E9299 19.0 (9.0) When additional oil or a complete charge is required, use only Carrier-approved compressor oil: Petroleum Specialities Inc.
Oil Pressure Safety Switch (OPS) — The OPS in the control circuit stops the compressor and unit, if proper oil pressure dif ferential is not established at start-up or main- tained during operation. If OPS stops the unit, determine the cause and correct before restarting unit.
TROUBLESHOOTING SYMPTOM AND PROBABLE CAUSE PROBABLE REMEDY COMPRESSOR DOES NOT RUN 1. Control circuit breaker tripped 1. Reset control circuit breaker 2. Power line open 2. Reset circuit breaker 3. Oil pressure switch tripped 3. Reset oil pressure switch at unit 4.
P ACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Installation Overview • Maintenance • Operating Sequence A large selection of product, theory , and skills programs is available.
ST ART -UP CHECKLIST (Remove and store in job file) A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
C. Start-Up CHECK EV APORA TOR F AN SPEED AND RECORD. CHECK CONDENSER F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE S.
Ein wichtiger Punkt beim Kauf des Geräts Carrier 38AKS028-044 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Carrier 38AKS028-044 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Carrier 38AKS028-044 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Carrier 38AKS028-044 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Carrier 38AKS028-044 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Carrier 38AKS028-044 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Carrier 38AKS028-044 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Carrier 38AKS028-044. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Carrier 38AKS028-044 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.