TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 15 SEER – R-410A MODELS: YZE024THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr oduct improvement, spec ifications are subject to change without notice. Visit us on the web at www .york.com Additional rati ng information can be foun d at www .
2 Johnson Controls Unitary Products 246750-YTG-L-0408 All dimensions are in inches. They are subject to change without notice. Certified dimensions wil l be provided upon request.
Johnson Controls Unitary Produ cts 3 246750-YTG-L-0408 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table.
4 Johnson Controls Unitary Products 246750-YTG-L-0408 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL W ST AGE RA TED CFM NET MBH SENSIBL E SEER EER YZE0241 1 A V24 17 – 1 535 18.6 13.6 15.00 13.00 2 800 24.
Johnson Controls Unitary Produ cts 5 246750-YTG-L-0408 COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE YZE0241 1 PV8*A12 FC/MC/PC/UC30A 14 1 430 17.
6 Johnson Controls Unitary Products 246750-YTG-L-0408 YZE0361 1 P(C,V)9*C16 FC/MC/PC/UC48C 21 1 640 24.2 16.2 15.50 12.70 2 1200 35.2 25.1 12.00 PV8*C16 FC/MC/PC/UC48C 21 1 780 25.0 18.9 15.00 12.85 2 1200 34.8 26.8 12.00 PV8*C20 FC/MC/PC/UC48C 21 1 800 25.
Johnson Controls Unitary Produ cts 7 246750-YTG-L-0408 HEA TIN G CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER MODEL COIL 1 MODEL HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 OD YZE0241 1 A V24 - 1 650 19.0 - - 3.30 2 775 24.0 15.
8 Johnson Controls Unitary Products 246750-YTG-L-0408 ** Refer to Q uick Selectio n Char t for specific furnace match-up. YZE0601 1 A V60 - 1 1200 37.6 - - 3.26 2 1900 55.0 32 .4 8.05 3.50 2 1200 50.0 29 .8 7.90 3.22 F2FV060 - 1 1200 37.6 - - 3.26 2 1900 54.
Johnson Controls Unitary Produ cts 9 246750-YTG-L-0408 YZE0361 1 P(C,V)9*B12 FC/MC/PC3 5B 17 1 650 2 3.0 - - 3.54 2 1200 33.0 20.8 8.50 3.70 2 650 29.4 19.6 8.35 3.30 PV8*B16 FC/MC/PC35B 17 1 650 23.0 - - 3.54 2 1200 33.0 21.0 8.50 3.70 2 650 29.4 19.
10 Johnson Controls Unitary Products 246750-YTG-L-0408 YZE0481 1 PV8*C20 FC/PC/UC60C 21 1 860 31.2 - - 3.56 2 1610 48.0 27.8 8.35 3.96 2 860 44.5 26.2 8.30 3.66 P(C,V)9*C20 FC /PC/UC60C 21 1 870 31.2 - - 3.56 2 1590 48.0 27.8 8.40 3.96 2 870 44.5 26.2 8.
Johnson Controls Unitary Produ cts 11 246750-YTG-L-0408 ACCESSORIES* TXV Kits - 1 TVM9 series thermal expansion val ves precisely meter refrigerant for optimu m performance. Bonnet Sensor (2SB137 00124) - The bonnet sensor is u sed to sense plenum temperatur e, and is optional with a gas or oi l back-up heat source.
12 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet wee.
Johnson Controls Unitary Produ cts 13 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween .
14 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet wee.
Johnson Controls Unitary Produ cts 15 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween .
16 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet wee.
Johnson Controls Unitary Produ cts 17 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween .
18 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet wee.
Johnson Controls Unitary Produ cts 19 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween .
20 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor section. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Johnson Controls Unitary Produ cts 21 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor section. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
22 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Johnson Controls Unitary Produ cts 23 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
24 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Johnson Controls Unitary Produ cts 25 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
26 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Johnson Controls Unitary Produ cts 27 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Subject to change without notice. Printe d in U.S.A. 246750-YTG-L-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 246750-YTG-K-0108 Johnson Controls Unit ary Products.
Ein wichtiger Punkt beim Kauf des Geräts York YZE024 THRU 060 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York YZE024 THRU 060 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York YZE024 THRU 060 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York YZE024 THRU 060 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York YZE024 THRU 060 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York YZE024 THRU 060 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York YZE024 THRU 060 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York YZE024 THRU 060. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York YZE024 THRU 060 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.