TECHNICAL GUIDE LX SERIES SPLIT-SYSTEM HEAT PUMPS 13 SEER – R-410A – 1 PHASE 1.5 THRU 5 NOMINAL TONS MODELS: YHJD18 THRU 60 Due to continuou s pro duc t impro vement, speci fic a tio ns are subject to chan ge without notice. Visit us on the web at www .
571209-YTG-C-1012 2 Johnson Controls Unitary Products * Adapter fi tting required for 1-1/8" lin e set. All dimensions are in inches an d are subject to change without notice. Overall height is from bottom of base pan to top of fan guar d. Overall length and widt h includ e screw heads.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplat e includes refrigerant f or th e outdoor unit, the smallest matched indoor unit, and 15 fe et of interconnecting line tubin g.
571209-YTG-C-1012 4 Johnson Controls Unitary Products COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SENS. 13 SEER HP WITH AIR HANDLERS YHJD18S41S2 AHE18B 17.5 – 610 18.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 5 — = Not applicable. MA Modular Air Handlers use Coil Only Ratings. YHJD42S41S4 AHE48D 24.5 – 1385 40.5 33.2 14.00 12.00 AHR48D 24.5 – 1320 39.5 29.6 13.00 11 . 0 0 AHV48D 24.5 – 1300 39.5 30.
571209-YTG-C-1012 6 Johnson Controls Unitary Products MA Modular Air Handlers use Coil Only Ratings. PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Rating s. COOLING CAP ACITY - Up flow , Downflow & Horizo ntal Furnaces and Coils (Coil Only Ratings) UNIT MODEL COIL CFM RANGE (Min.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 7 YHJD18S41S2 T*(8,L)X*A12 14.5 UC24B 570 18.0 14.1 14.50 12.00 T*(8,L)X*A12 14.5 UC30B 570 18.0 14.1 14.50 12.00 T*(8,L)X*B12 17.5 FC/MC/PC18B 580 18.0 14.6 14.00 12.00 T*(8,L)X*B12 17.5 FC/MC/PC24B 620 18.
571209-YTG-C-1012 8 Johnson Controls Unitary Products YHJD24S41S4 T*(8,L)V*A12 14.5 FC/MC/PC32A 775 24.0 17.2 14.00 12.00 T*(8,L)V*A12 14.5 FC /MC/PC37A 805 24.0 17 .3 14.50 12.00 T*(8,L)V*B12 17.5 FC /MC/PC35B 760 24.0 17 .2 14.00 12.00 T*(8,L)V*B12 17.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 9 YHJD30S41S4 T*(8,L)V*A12 14.5 FC/MC/PC32A 1045 30.0 22.0 13.50 1 1.00 T*(8,L)V*A12 14.5 FC/MC/PC37A 950 30.0 22.0 14.50 12.00 T*(8,L)V*B12 17.5 FC/MC/PC35B 995 30.0 22.0 14.50 12.00 T*(8,L)V*B12 17.
571209-YTG-C-1012 10 Johnson Controls Unitary Products YHJD36S41S4 T*(8,L)V*C20 21.0 FC/MC/PC48C 1 155 36.0 26.6 14.50 12.00 T*(8,L)V*C20 21.0 UC48C 1 155 36.0 26.8 14.50 12.00 T*(8,L)X*A12 14.5 FC /MC/PC37A 1290 36.0 27 .6 14.50 12.00 T*(8,L)X*B12 17.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 11 YHJD42S41S4 T*(8,L)V*C16 21.0 FC/PC60C 1420 41.5 32.2 14.00 12.00 T*(8,L)V*C 16 21.0 UC60C 1420 41.0 31.4 13.75 11 . 5 0 T*(8,L)V*C 20 21.0 FC/PC60C 1410 42.0 32.4 14.00 12.00 T*(8,L)V*C 20 21.0 UC60C 1410 41.
571209-YTG-C-1012 12 Johnson Controls Unitary Products PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Rating s. YHJD48S41S4 T*9(C,V)*D20 24.5 FC/MC/PC60D 1615 44.5 33 .6 14.00 12.00 T*9(C,V)*D20 24.5 FC/MC62D 1630 45.0 34.0 14.00 12.00 T*9(C,V)*D20 24.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 13 HEA TING CAP ACITY - With Air Handler UNIT MODEL AIR HANDLER COIL 1 MODEL HEA TING 2 47 F 17 F HSPF MBH COP KW MBH COP KW STD 13 SEER HP WITH AIR HANDLERS YHJD18S41S2 AHE18B – 18.0 3.70 1.
571209-YTG-C-1012 14 Johnson Controls Unitary Products COP equals MBH output divided by (tot al KW input x 3.412). HSPF (Heating Seasonal P erformance Fact or) is the tot al heati ng outpu t during a normal a nnual usage perio d for heating d ivided by the tot al electric power input during the same period.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 15 COP equals MBH output divided by (tot al KW input x 3.412). HSPF (Heating Seasonal Per formance Factor) i s the tot al heati ng o utput during a normal annual u sage period for heating divide d by the tot al electric power input during the same period.
571209-YTG-C-1012 16 Johnson Controls Unitary Products HEA TING CAP ACITY - With High Efficiency Motor Furnaces MODEL FURNACE MODEL COIL 1 MODEL HEA TING 2 47 F 17 FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES 3 YHJD18S41S2 T*(8,L)V*A12 FC/MC/PC18A 18.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 17 YHJD18S41S2 Y*(8,L)C*B12 UC24B 18.0 3.70 1.34 10.5 2.96 1.04 8.20 Y*(8,L)C*B12 UC30B 18.0 3.70 1.34 10.4 2.96 1.03 8.20 Y*9C*B12 FC/MC/PC18B 18.0 3.60 1.36 7.7 2.30 0.98 8.00 Y*9C*B12 FC/MC/PC24B 18.
571209-YTG-C-1012 18 Johnson Controls Unitary Products YHJD30S41S4 T * ( 8 , L ) V * A 1 2 F C / M C / P C 3 2 A 2 7 . 43 . 3 02 . 4 31 6 . 02 . 3 22 . 0 27 . 8 5 T*(8,L)V*A12 FC /MC/PC37A 27.2 3.48 2.29 15.7 2.42 1.90 8.05 T*(8,L)V*B12 FC /MC/PC35B 27.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 19 YHJD36S41S4 T*(8,L)X*C20 FC/MC/PC43C 34.0 3.66 2.72 21.4 2.80 2.24 8.20 T*(8,L)X*C 20 FC/MC/PC48C 34.2 3.70 2.71 21.6 2.84 2.23 8.20 T*(8,L)X*C 20 UC48C 34.6 3.80 2.67 21.8 2.84 2.25 8.20 T*9(C,V)*B12 FC/MC/PC43B 34.
571209-YTG-C-1012 20 Johnson Controls Unitary Products YHJD42S41S4 T * 9 X * C 2 0 F C / P C 6 0 C 4 0 . 03 . 9 82 . 9 42 2 . 42 . 6 82 . 4 58 . 2 0 T*9X*C20 UC60C 39.5 3.90 2.97 22.2 2.64 2.46 8.20 T*9X*D20 FC/MC/PC60D 40.0 4.04 2.90 22.4 2.72 2.41 8.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 21 COP equals MBH output divided by (tot al KW input x 3.412). HSPF (Heating Seasonal Per formance Factor) i s the tot al heati ng o utput during a normal annual u sage period for heating divide d by the tot al electric power input during the same period.
571209-YTG-C-1012 22 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (S1 -2SA067*) - May be required on 24, 30, 36, & 42 models when a T XV is installed. May also be required o n 18 & 60 models in low voltage application.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 23 TYPICAL INST ALLA TION TYPICAL FIELD WIRING 60” OVERHEAD CLEARANCE MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE WEA THERPROOF DISCONNEC.
571209-YTG-C-1012 24 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 25 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC18A 0.99 0.98 0.93 T*(8,L)V*A12 FC/MC/PC24A 1.02 1.06 0.93 T*(8,L)V*A12 FC/MC/PC30A 1.02 1.06 0.93 T*(8,L)V*A12 UC18A 0.99 0.99 0.93 T*(8,L)V*A12 UC24A 1.
571209-YTG-C-1012 26 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 27 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.02 0.99 0.94 T*(8,L)V*A12 FC/MC/PC37A 1.06 1.04 0.94 T*(8,L)V*B12 FC/MC/PC35B 1.05 1.02 0.94 T*(8,L)V*B12 FC/MC/PC43B 1.06 1.04 0.94 T*(8,L)V*C16 FC/MC/PC35C 1.
571209-YTG-C-1012 28 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 29 Furnaces Coils T .C. S.C KW T*(8,L)V*A12 FC/MC/PC32A 1.01 1.05 0.99 T*(8,L)V*A12 FC/MC/PC37A 1.02 1.06 0.95 T*(8,L)V*B12 FC/MC/PC35B 1.02 1.06 0.95 T*(8,L)V*B12 FC/MC/PC43B 1.04 1.09 0.96 T*(8,L)V*C16 FC/MC/PC35C 1.
571209-YTG-C-1012 30 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 31 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC37A 1.03 1.03 1.00 T*(8,L)V*B12 FC/MC/PC43B 1.04 1.06 1.01 T*(8,L)V*C16 FC/MC/PC43C 1.04 1.04 0.96 T*(8,L)V*C16 FC/MC/PC48C 1.05 1.05 0.96 T*(8,L)V*C16 UC48C 1.
571209-YTG-C-1012 32 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 33 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
571209-YTG-C-1012 34 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)V*C16 FC/MC62D 0.99 0.99 0.95 T*(8,L)V*C16 FC/PC60C 0.98 0.98 0.96 T*(8,L)V*C16 UC60C 0.98 0.95 0.96 T*(8,L)V*C20 FC/MC62D 1.00 0.99 0.95 T*(8,L)V*C20 FC/PC60C 0.
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 35 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
571209-YTG-C-1012 36 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. Continu ed on next p age. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD18S41S2 EV APORA TOR COIL MODEL NO FC35 AIR TEMP .
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 37 Furnaces Coils MBH COP KW T*(8,L)V*A12 FC/MC/PC18A 1.03 0.99 1.04 T*(8,L)V*A12 FC/MC/PC24A 1.04 1.06 0.98 T*(8,L)V*A12 FC/MC/PC30A 1.04 1.06 0.98 T*(8,L)V*A12 UC18A 1.04 1.02 1.02 T*(8,L)V*A12 UC24A 1.
571209-YTG-C-1012 38 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD24S41S4 EV APORA TOR COIL MODEL NO AHP30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 39 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD30S41S4 EV APORA TOR COIL MODEL NO AHP30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
571209-YTG-C-1012 40 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. Continu ed on next p age. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD36S41S4 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP .
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 41 Furnaces Coils MBH COP KW T*(8,L)V*A12 FC/MC/PC37A 0.93 0.98 0.95 T*(8,L)V*B12 FC/MC/PC43B 0.93 0.98 0.95 T*(8,L)V*C16 FC/MC/PC43C 0.92 1.01 0.91 T*(8,L)V*C16 FC/MC/PC48C 0.91 1.02 0.90 T*(8,L)V*C16 UC48C 0.
571209-YTG-C-1012 42 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD42S41S4 EV APORA TOR COIL MODEL NO AHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
571209-YTG-C -1012 Johnson Controls Unitary Pro ducts 43 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD48S41S4 EV APORA TOR COIL MODEL NO AHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
Subject to change without notice. Published in U .S.A. 571209-YTG-C-1012 Copyright © 2012 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 571209-YTG-B-1211 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the p erfo rman ce with other indoor sections.
Ein wichtiger Punkt beim Kauf des Geräts York YHJD18 thru 60 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York YHJD18 thru 60 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York YHJD18 thru 60 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York YHJD18 thru 60 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York YHJD18 thru 60 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York YHJD18 thru 60 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York YHJD18 thru 60 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York YHJD18 thru 60. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York YHJD18 thru 60 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.