TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 13 SEER – R-410A MODELS: YHJD 18 THRU 60 (1.5 THRU 5 NOMINAL TONS - 1PHASE) Due to continuous prod uct improvemen t, specifications are subject to chan ge without notice. Vi si t us on the web at ww w .york.
397855-YTG-G-0509 2 Johnson Controls Unitary Products All dimensions are in inche s. They are su bject to change with- out notice. Certified dimensions will be provi ded upon request.
Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes re friger ant for the condenser, the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system u sing the above table.
397855-YTG-G-0509 4 Johnson Controls Unitary Products COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 13 SEER HP WITH MA YHJD 18S41S1 MA08B 17 FC/MC/PC18B 600 17.
Johnson Controls Unitary Pro ducts 5 — = Not applicable. 13 SEER HP WITH AHP / SHP / AHX / F*FP YHJD 18S41S1 AHP18 17 – 600 17.0 12.7 13.00 1 1.00 F4FP024 17 – 600 17.0 12.6 13.00 1 1.00 YHJD 24S41S1 AHP30 17 – 800 23.0 17.2 13.00 1 1.00 AHX30 17 – 820 24.
397855-YTG-G-0509 6 Johnson Controls Unitary Products COOLING CAP ACITY - Up flow , Downflow & Horizontal Furnace s and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. YHJD 18S41S1 450 - 750 14,17 FC/MC/PC18 600 17.
Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - With High Efficiency Motor Furna ces UNIT MODEL FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL S EN S. 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 YHJD 18S41S1 Y *(8,L)C*A12 FC/MC/PC18A 14 620 17.
397855-YTG-G-0509 8 Johnson Controls Unitary Products YHJD 30S41S1 ( Y *9C/T*9V)*C16 FC/MC/PC43C 21 1030 29.6 22.2 14.00 12.60 ( Y *9C/T*9V)*C20 FC/MC/PC43C 21 995 29.6 22.4 14 .40 12 .80 Y *(8,L)C*C16 HC42 21 990 29.6 22 .4 14.50 13 .00 Y *(8,L)C*C20 HC42 21 1000 29.
Johnson Controls Unitary Pro ducts 9 YHJD 42S41S1 T*(8,L)X*C16 FC/MC/PC48C 21 1360 41.5 31.4 13.80 1 1.75 T*9X*C16 FC/MC/PC48C 21 1425 41.5 31.8 13.60 1 1.50 T*(8,L)X*C20 FC/MC/PC48C 21 1475 42.0 32.6 14.00 1 1.75 T*9X*C20 FC/MC/PC48C 21 1420 41.5 32.
397855-YTG-G-0509 10 Johnson Controls Unitary Products YHJD 48S41S1 T*(8,L)X*C16 FC/PC60C 21 1605 46.5 34.6 13.50 1 1.50 T*9X*C16 FC/PC60C 21 1575 46.5 34.6 13.30 1 1.40 T*(8,L)X*C20 FC/MC/PC60D 21 1595 46 .5 34.6 13.55 1 1.50 T*9X*C20 FC/PC60C 21 1625 46.
Johnson Controls Unitary Pro ducts 11 HEA TING PERFORMANC E - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA TING 2 47 F1 7 F HSPF MBH COP KW MBH COP KW STD 13 SEER HP WITH MA YHJD 18S41S1 MA08B FC/MC18B 17.0 3.32 1.50 12.7 3.00 1.
397855-YTG-G-0509 12 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
Johnson Controls Unitary Pro ducts 13 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period.
397855-YTG-G-0509 14 Johnson Controls Unitary Products HEA TING CAP ACITY - With High Efficiency Motor Furnaces MODEL FURNACE MODEL COIL 1 MODEL ARI HEA TING 2 47 F1 7 FH S P F MBH COP KW MBH COP KW STD 13 SEER HP WITH V ARIABLE SPEED FURNACES 3 YHJD 18S41S1 Y *(8,L)C*A12 FC/MC/PC18A 16.
Johnson Controls Unitary Pro ducts 15 YHJD 30S41S1 ( Y *9C/T*9V)*B12 FC/MC /PC43B 28.0 3.50 2.34 16.3 2.48 1.93 7.90 Y *(8,L)C*C16 FC/MC/PC43C 27.6 3.62 2.23 16.0 2.56 1.83 8.00 Y *(8,L)C*C20 FC/MC/PC43C 27.6 3.62 2.23 16.0 2.56 1.83 8.00 ( Y *9C/T*9V)*C16 FC/MC/PC43C 27.
397855-YTG-G-0509 16 Johnson Controls Unitary Products YHJD 42S41S1 T*(8,L)X*C16 FC/MC/PC48C 41. 0 3.82 3.15 27.6 2. 66 3.04 8.20 T*9X*C16 FC/MC/PC48C 41. 5 3.80 3.20 27.8 2.64 3 .09 8.10 T*(8,L)X*C20 FC/MC/PC48C 41. 5 3.88 3.13 27.6 2. 68 3.02 8.20 T*9X*C20 FC/MC/PC48C 41.
Johnson Controls Unitary Pro ducts 17 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period.
397855-YTG-G-0509 18 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) - May be required on 42, 48, 60 models. Models 18, 24 , 30, 36 have been factory installed. Blower Time Delay - Available to increase efficiency when installed.
Johnson Controls Unitary Pro ducts 19 TYPICAL INST ALLA TION TYPICAL FIELD WIRING THERMOST AT SEAL OPENING(S) WITH PERMAGUM OR EQUIV ALENT TO INDOOR COIL TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 2 WIRING NEC CLASS 1 WIRING ALL OUTDOOR WIRING MUST BE WEA THERPROOF .
397855-YTG-G-0509 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible.
397855-YTG-G-0509 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible.
397855-YTG-G-0509 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
Johnson Controls Unitary Pro ducts 25 Furnaces Coils T .C. S.C. KW T*(8,L)X*C16 FC/MC/PC48C 1.00 1.05 0.95 T*9X*C16 FC/MC/PC48C 1.01 1.07 0.97 T*(8,L)X*C20 FC/MC/PC48C 1.02 1.09 0.96 T*9X*C20 FC/MC/PC48C 1.01 1.07 0.96 T*9X*D20 FC/MC/PC48D 1.01 1.07 0.
397855-YTG-G-0509 26 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
Johnson Controls Unitary Pro ducts 27 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible.
397855-YTG-G-0509 28 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD 18S41S1 EV APORA TOR COIL MODEL NO AHP18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
Johnson Controls Unitary Pro ducts 29 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD 24S41S1 EV APORA TOR COIL MODEL NO AHP24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
397855-YTG-G-0509 30 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD 30S41S1 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
Johnson Controls Unitary Pro ducts 31 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD 36S41S1 EV APORA TOR COIL MODEL NO AHP36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
397855-YTG-G-0509 32 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. Continu ed on next p age. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD 42S41S1 EV APORA TOR COIL MODEL NO FC/MC/PC/UC48 AIR TEMP .
Johnson Controls Unitary Pro ducts 33 Furnaces Coils MBH KW COP T*(8,L)X*C16 FC/MC/PC48C 0.98 1.05 0.94 T*9X*C16 FC/MC/PC48C 0.99 1.04 0.95 T*(8,L)X*C20 FC/MC/PC48C 0.98 1.06 0.93 T*9X*C20 FC/MC/PC48C 0.98 1.05 0.94 T*9X*D20 FC/MC/PC48D 0.98 1.05 0.93 T*(8,L)X*C16 UC48C 0.
397855-YTG-G-0509 34 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO YHJD 48S41S1 EV APORA TOR COIL MODEL NO AHP/SHP48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
Johnson Controls Unitary Pro ducts 35 ( Y *9C/T*9V)*D20 UC60D 1.00 1.01 0.98 Furnaces Coils MBH KW COP.
Subject to change without notice. Publishe d in U.S.A. 397855-YTG-G-0509 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 397855-YTG-F-0409 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections.
Ein wichtiger Punkt beim Kauf des Geräts York YHJD18 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York YHJD18 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York YHJD18 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York YHJD18 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York YHJD18 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York YHJD18 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York YHJD18 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York YHJD18. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York YHJD18 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.