GENERAL REFERENCE St andard Register TOLL FREE T elephone: 877-318-9675 TOLL FREE Fax: 877-379-7920 INSPECTION SPLIT -SYSTEM HEA T PUMPS OUTDOOR UNITS INST ALLATION MANUAL 035-15410-002-B-0404 MODELS .
2 Unitary Products Group 090 = 7-1/2 T on 120 = 10 T on T ABLE OF CONTENTS INST ALLATION OPERATION ° ST ART -UP MAINTENANCE LIST OF FIGURES LIST OF T ABLES.
LIMIT ATIONS LOCATION 1. The outdoor units must be installed outside the building. The outdoor fans are the propeller type and are not suitable for use with duct work. 2. The outdoor and indoor units should be installed as close together as possible and with a minimum number of bends in the refrigerant piping.
CLEARANCES WARNING: Do not permit overhanging structures or shrubs to obstruct air discharge. COMPRESSORS CAUTION: Do Not loosen compressor mounting bolts. COMPRESSOR CRANKCASE HEA TER CAUTION: Do not attempt to start the compressor without at least eight hours of crankcase heat or compressor damage will occur .
Both the manual and auto changeover thermostats have non- adjustable, voltage-type anticip ators for both cooling and heat - ing. WIRE SIZING REFRIGERANT PIPING GENERAL GUIDELINES Unitary Products Group 5 035-15410-002-B-0404 FIG . 3 - TYPICAL FIELD WIRING 200/230-3-60 0.
6 Unitary Products Group FIG . 4 - UNIT DIMENSIONS AND CLEARANCES - 7-1/2 & 10 TON All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. Overhead (T op) 1 Front (Piping and Access Panels) Left Side Right Side Rear Bottom 2 1 Units must be installed outdoors.
LINE SIZING ° Oil return will be critical during: The cooling cycle when the outdoor unit is above the indoor unit (detail 1 of Figure 5). The heating cycle when the indoor unit is above the outdoor unit (detail 4 of Figure 5). EXAMPLES: #1 - 7-1/2 T on System 125 feet of 1-3/8" OD, type “L” copper tubing (125 feet x 1.
(29 feet x 8.0 psi/100 feet) ............................................. 2.3 p si 7 feet of 1-3/8" OD, type “L” copper tubing (horizontal) (7 feet x 2.8 psi/100 feet) ............................................... 0.2 p si Fitting* .......
NOTE: Use only copper tubing that has been especially cleaned and dehydrated for refrigerant use. If the tub - ing has been open for an extended period of time, it should be cleaned before being used. NOTE: 1. The matched air handlers are shipped with a small R-22 charge and they should be checked for leaks before instal - lation.
BALANCE POINT SETTING The outdoor design temperature, The building heat loss at the outdoor design temperature, and The heating capacity of the system at the outdoor design temperature.
Unitary Products Group 11 035-15410-002-B-0404 FIG . 7 - REFRIGERANT FLOW DIAGRAM.
12 Unitary Products Group FIG . 8 - CHARGING CUR VE EFB090 FIG . 9 - CHARGING CUR VE EFB120.
GENERAL CAUTION: Reversing valves and check valves are precise mechanical devices and will not tolerate any me - chanical abuse such as hammering. If a refrigerant system isn't properly cleaned after a compressor burn-out, scale may build up at these devices and prevent them from operating properly .
IN ALL THREE RESET METHODS DESCRIBED ABOVE, A FIVE MINUTE TIME DELA Y WILL T AKE PLACE AFTER THE RESET BEFORE THE UNIT WILL REST AR T . 8. Supplemental electric heat (if installed) will be controlled by second stage TH2 of the thermostat. The supplement al electric heat circuit is controlled through low voltage termi - nals W , 60 and 66.
CRANKCASE HEA TER CAUTION: DO NOT A TTEMPT TO ST ART THE COMPRES - SOR WITHOUT A T LEAST 8 HOURS OF CRANKCASE HEA T OR COMPRESSOR DAM - AGE WILL OCCUR. PRE-ST ART CHECK 1. Have sufficient clearances been provided? 2. Has all foreign matter been removed from the interior of the unit (tools, construction or shipping materials, etc.
Untiary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright © 2004 by Y ork International Corporation.
Ein wichtiger Punkt beim Kauf des Geräts York E3FB090 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York E3FB090 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York E3FB090 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York E3FB090 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York E3FB090 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York E3FB090 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York E3FB090 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York E3FB090. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York E3FB090 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.