GENERAL YORK Model BCH units are single package heat pump s designed for outdoor installation on a roof top or a slab. Supplemental electric heaters are available as field-installed accessories. The units are manufactured under ISO 9002 Quality System Certification.
035-12984-001-A-0204 2 Unitary Products Group General ................................................................................ 1 Inspection ............................................................................ 1 Reference ..............
LIMIT ATIONS These units must be installed in accordance with national and local or municiple safety codes: Refer to T able 1 for Unit Application Data. If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and / or the customer's expense.
size and type. Dirty filters reduce the capacity of the unit and result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in T able 3. CONDENSA TE DRAIN Plumbing must conform to local codes. Use a sealing compound on male pipe threads.
035-12984-001-A-0204 Unitary Products Group 5 FIG . 3 - TYPICAL FIELD WIRING CONTROL WIRING POWER WIRING NOMINAL HEA TER SIZE KW VOL TAGE UNIT MODEL SIZE, NOMINAL TONS 45 MINIMUM SUPPL Y AIR CFM 7 10 .
heater accessory installation instruction for the heater electrical data. The minimum air flow limitations across these heaters are listed in T able 2. OPTIONAL ECONOMIZER RAIN HOOD The following procedure should be used when assembling an economizer rain hood onto a unit.
035-12984-001-A-0204 Unitary Products Group 7 FIG . 5 - ENTHALPY SET POINT ADJUSTMENT MODELS BCH 048 060 SUPPL Y AIR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd.,mm/in.) F AN MOTOR HP (Direct-Drive Units) F AN MOTOR HP (Belt-Drive Units) 305 x254 12 x 10 0.75 NA 305 x 254 12 x 10 NA 1.
035-12984-001-A-0204 8 Unitary Products Group FIGURE 6 - DIMENSIONS & CLEARANCES Front 610mm (24") Back 25mm (12") (Less Economizer) 914mm (36") (With Economizer) Left Side (Filter .
035-12984-001-A-0204 Unitary Products Group 9 DET AIL “B” UNIT WITH FIXED OUTDOOR AIR / BAROMETRIC RELIEF RAINHOOD 111 “ 260 “ 89 “ 210 A B 454 “ 184 “ 416 “ 260 “ 11 7 “ 1340 “ L.H. END VIEW REAR VIEW L.H. END VIEW REAR VIEW 638 “ 41 “ 698 267 “ 1 140 “ 502 “ “ CONDEN- SA TE DRAIN CONN.
035-12984-001-A-0204 10 Unitary Products Group T ABLE 4 - SUPPL Y AIR PERFORMANCE - BCH048 MODEL AIR FLOW m 3 /s / CFM Available External S tatic Pressure -Pa/ IWG* 223 / 0.90 248 / 1.00 273 / 1.10 298 / 1.20 322 / 1.30 347 / 1.40 372 / 1.50 RPM W atts RPM W atts RPM W atts RPM W atts RPM W atts RPM Watt s RPM Watt s 060 1.
035-12984-001-A-0204 Unitary Products Group 11 MODEL BCH POWER SUPPL Y VOL TAGE LIMIT ATIONS COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA TOT AL UNIT AMP ACITY , AMPS MAX. FUSE SIZE, (SEE NOTE 1) AMPS MAX. HACR BREAKER SIZE, AMPS MIN.
screw fully clockwise and then energize and de-energize terminals “R” to “G”. With terminals “R” to “G” energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained. 1 1. Replace the filter section access panel.
During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module. The pegs are 13mm ( in.) long, 1mm ( in.) apart and are mounted on a white base. See Figure 8. LOCKOUT CONTROL Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode: 1.
3. Using an inclined manometer , determine the pressure drop across a dry indoor coil. Since the moisture on an indoor coil may vary greatly , measuring the pressure drop across a wet coil under field conditions would be inaccurate. T o ensure a dry coil, the compressors should be de-energized while the test is being run.
035-12984-001-A-0204 Unitary Products Group 15.
Unitary Products Group 5005 Y ork Drive, Norman, Ok 73069 Subject to change without notice. Printed in U.S.A. Copyright by Y ork International Corporation 2004.
Ein wichtiger Punkt beim Kauf des Geräts York B3CH 048 and 060 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie York B3CH 048 and 060 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für York B3CH 048 and 060 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von York B3CH 048 and 060 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über York B3CH 048 and 060 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon York B3CH 048 and 060 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von York B3CH 048 and 060 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit York B3CH 048 and 060. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei York B3CH 048 and 060 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.