KOOLMASTER PP-32 CONTROLLER Read this guide carefully before using the controller. ENVIRONMENTAL MANAGEMENT SYSTEM SERIAL NUMBER: DATE: R01.
NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject to change without notice due to further developments.
3 KOOLMASTER PP-32 REV.01 T ABLE OF CONTENTS Page 1. PRECAUTIONS ............................................................ 6 2. FEATURES ................................................................. 7 3. LOCATION OF THE CONTROLS ...............
4 PP-32 KOOLMASTER PP-32 REV.01 5.9 AUXILIARY OUTPUTS ....................................................... 4 2 5.10 ANIMAL AGE ................................................................ 4 4 5.11 CLOCK OUTPUTS .................................
5 PP-32 KOOLMASTER PP-32 REV.01 5.15 ADVANCED SETTINGS .................................................... 7 8 5.15.1 Setting the Temperature Curve ........................................ 7 8 5.15.2 Setting the Minimum Ventilation Curve ............
6 KOOLMASTER PP-32 REV.01 We strongly recommend installing supplementary natural ventila- tion as well as a backup thermostat on at least one cooling stage (refer to the wiring diagram enclosed with this user's manual to connect the thermostat).
7 KOOLMASTER PP-32 REV.01 The PP-32 is an electronic device used for environmental control in livestock buildings. It allows the user to maintain a specified target temperature by controlling the operation of ventilation and heating equipment.
8 PP-32 KOOLMASTER PP-32 REV.01 EIGHT INDEPENDENT TEMPERATURE SENSOR INPUTS Up to eight temperature sensors can be connected to the controller in order to obtain a more accurate reading of the average room temperature and a faster reaction time. Sensors may be assigned to each heater output or to auxiliary outputs.
9 KOOLMASTER PP-32 REV.01 3. LOCATION OF THE CONTROLS NAVIGATION BUTTONS ADJUSTMENT BUTTONS LCD DISPLAY SHORTCUT KEYS MAIN MENUS 32 ON/OFF RELAYS ALARM STATUS LED Front Panel LED DISPLAY.
10 PP-32 KOOLMASTER PP-32 REV.01 LCD Display: The LCD display gives the current readings and param- eters to be adjusted when you select a function. When the parameters for a given function cannot all.
11 KOOLMASTER PP-32 REV.01 ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRICIAN AND MUST COMPLY WITH APPLICABLE CODES, LAWS AND REGULATIONS. BE SURE POWER IS OFF BEFORE DOING ANY WIRING TO AVOID ELECTRICAL SHOCKS AND EQUIPMENT DAMAGE.
12 PP-32 KOOLMASTER PP-32 REV.01 Sensors operate at low voltage and are isolated from the supply. Be sure that sensor cables remain isolated from all high voltage sources. In particular, do not route the sensor cables through the same electrical knockout as other cables.
13 PP-32 KOOLMASTER PP-32 REV.01 3. DWR-F-1A COMMUNICATION HOOKUP If DWR-F-1A air inlet controllers are connected to the PP-32, use id numbers within the range 4-15. Id numbers 1,2 and 3 are reserved for another purpose. Refer to section 5.5.1.1 to set the proper ID numbers.
14 PP-32 KOOLMASTER PP-32 REV.01 E L B A T H C T I W S P I D # h c t i w S F F O N O 1 S E E R G E D T I E H N E R H A F S E E R G E D S U I S L E C 2 E D O M M P / M A E D O M S R U O H 4 2 3 S N O L.
15 KOOLMASTER PP-32 REV.01 5. CONTROLLER SETUP 5.1 CURRENT CONDITIONS The current conditions menu gives a quick view of the actual conditions in the barn. Press to step directly to this menu. Room Set Point: this is the target temperature in the barn.
16 PP-32 KOOLMASTER PP-32 REV.01 5.2 CONTROLLER PROGRAMS The controller allows to use up to 4 separate programs to control the room temperature. It then becomes possible to activate a specific program, that uses particular fan settings, in accordance with the animal age for instance.
17 PP-32 KOOLMASTER PP-32 REV.01 Fan / Sensor Program Selection: (a) Temp Settings: Summr Use the adjustment buttons to select the proper season (winter/ summer). The start and stop temperatures of heating and ventilation stages that are associ- ated with this seasons will be used.
18 PP-32 KOOLMASTER PP-32 REV.01 5.3 ADJUSTING THE ROOM SET POINT The room set point is the target room temperature. It can be adjusted between 32°F and 120°F (0°C and 48.9°C). Note that the temperature curve must be turned off to adjust this value.
19 PP-32 KOOLMASTER PP-32 REV.01 5.4 MINIMUM VENTILATION PRINCIPLE OF OPERATION When the room temperature is below the set point, fans can operate according to a timer. The minimum ventilation cycles runs stage 1 fans according to a timer as shown below.
20 PP-32 KOOLMASTER PP-32 REV.01 Use the arrow keys to select the "1. On Time/Curve" function. Press the right-arrow key. The fans' On- Time, in minimum ventilation, is displayed, as well as the status of the minimum ventilation curve. If the curve is OFF , the On-Time value flashes on the display.
21 PP-32 KOOLMASTER PP-32 REV.01 5.5 INLET / VENT DOOR SETTINGS The PP-32 controller can operate the air inlets / vent doors in two different ways: 1. Inlets' positions can be determined by using a potentiometer feedback controller ( DWR-F-1A ). Refer to the installation setup section to enable DWR-F-1A modules.
22 PP-32 KOOLMASTER PP-32 REV.01 Inlet Compensation Inlet 1 5%/°F Inlet 2 5%/°F Inlet 3 5%/°F Note that the reference numbers that are used by the PP-32 DO NOT correspond to the ID numbers that used by the DWR-F-1A modules because #1, 2 and 3 are reserved for other purpose.
23 PP-32 KOOLMASTER PP-32 REV.01 5.5.2 Vent Door Settings If a static pressure sensor is used, the PP-32 can control the static pressure in the room by opening and closing vent doors. When the pressure drops below the low pressure set point, the vent doors close according to a timer.
24 PP-32 KOOLMASTER PP-32 REV.01 GROUPS OF STATIC PRESSURE SET POINTS : Two groups of static pressure set points can be defined. HI and LO static pressure set points #2 start being used either when a certain ventilation stage is reached or when the outside temperature decreases below a user-define value.
25 PP-32 KOOLMASTER PP-32 REV.01 2. Static pressure set points' transition according to the outside T°: Example : When the outside temperature drops below the "outside temperature influence" value, a transition between the two set point groups starts.
26 PP-32 KOOLMASTER PP-32 REV.01 5.5.2.1 Adjusting Static Pressure Set Points When the high pressure set point is reached (Open at) , the controller opens the vent doors according to a timer cycle. When the low pressure set point is reached (Close at) , the controller closes the vent doors according to the another timer.
27 PP-32 KOOLMASTER PP-32 REV.01 Open Time 30sec Close Time 30sec Off Time 60sec Off Time: once the vent doors have opened or closed (depending on the situation), they then stop operating during the Off time delay. The Off Time delay ranges from 0 to 900 seconds.
28 PP-32 KOOLMASTER PP-32 REV.01 5.5.2.3 Adjusting Stage Level for the Closing of Vent Doors When the stage defined by this parameter is reached, the vent doors start to close continuously until they are completely closed, no matter what the static pressure is.
29 PP-32 KOOLMASTER PP-32 REV.01 Static Settings 2 Outside Temperature Influence: 50.0°F Close At: .070WC Open At: .090WC Use the adjustment buttons to select the fan stage above which the second group of static pressure set points starts being used.
30 PP-32 KOOLMASTER PP-32 REV.01 Use the adjustment buttons to set the outside temperature below which the second group of static pressure set points start to be used. Press the down-arrow key once, the LO static pressure set point #2 (Close At) is selected .
31 PP-32 KOOLMASTER PP-32 REV.01 5.6 TUNNEL CURTAIN The PP-32 allows you to control an endwall curtain for tunnel ventilation. The tunnel curtain is controlled either by the static pressure level in the barn or in timer mode, according to the room temperature.
32 PP-32 KOOLMASTER PP-32 REV.01 Tunnel Curtain Controlled by the Static Pressure: When the pressure drops below the low pressure set point, the tunnel curtain closes according to a timer. Likewise, when the static pressure increases above the high pressure set point, the curtain opens according to another timer.
33 PP-32 KOOLMASTER PP-32 REV.01 TRANSITION BETWEEN SIDEWALL AND TUNNEL VENTILATION MODES: The following section describes the vent doors and curtain's behavior when the transition between sidewall ventilation (vent doors) and tunnel ventilation is being done.
34 PP-32 KOOLMASTER PP-32 REV.01 Tunnel Curtain Tunnel Stage # 5 Min. Animal age 1 5.6.1 Adjusting Minimum Age for Tunnel Ventilation The minimum age is used to prevent tunnel ventilation from being used when the animals are too young. It ranges from 1 to 450 days.
35 PP-32 KOOLMASTER PP-32 REV.01 5.6.3 Adjusting Curtain's Operating Times This function is only used if the curtain operates in timer mode. The curtain's operating time is the time during which the curtain opens when a new tunnel fan stage is activated or closes when a tunnel fan stage is deactivated.
36 PP-32 KOOLMASTER PP-32 REV.01 5.6.4 Adjusting Static Pressure Hi and Lo Set Points This function is only used if the curtain operates in static pressure mode. When controlled by the static pressure, the curtain opens or closes according a timer cycle whenever the static pressure level exceeds the Hi or Lo static pressure set points.
37 PP-32 KOOLMASTER PP-32 REV.01 Open Time: when the static pressure exceeds the Hi pressure set point, the curtain opens during this delay. It ranges from 0 to 900 seconds. Close Time: when the static pressure drops below the Lo pressure set point, the curtain closes during this delay.
38 PP-32 KOOLMASTER PP-32 REV.01 5.7 FAN STAGES SETTINGS The PP-32 controls up to 16 on-off fan stages. These stages operate in a sequence to increase the level of ventilation as the room temperature rises. Each stage can also activate relays in timer mode.
39 PP-32 KOOLMASTER PP-32 REV.01 Stg 1 On 80.5 (S) Stg 1 Off 80.0 (S) Stg 2 On 82.0 (S) Stg 2 Off 80.0 (S) 5.7.1 Adjusting Fan Stages' Start/Stop Temperatures The minimum temperature difference between two consecutive start temperatures is 0.5°F (0.
40 PP-32 KOOLMASTER PP-32 REV.01 Relay 31 Off(1) Relay 32 Off(1) On Time 15 sec Off Time 120 sec Ventilation Stage Relay Assignement 3. Stage 1a 4. Stage 2a Set the function to "17. Fan Settings" from the main menu. Note that this menu is available only in the installer mode (see sec.
41 PP-32 KOOLMASTER PP-32 REV.01 5.8 HEATER SETTINGS The PP-32 operates up to eight independent heater stages. A start and stop temperature is defined for each heating stage. The stop temperature must be at least 0.5°F (0.3°C) greater than the start temperature for a given heater and the start temperature cannot be greater than the set point.
42 PP-32 KOOLMASTER PP-32 REV.01 5.9 AUXILIARY OUTPUTS The PP-32 can control up to two auxiliary outputs. They are used as supplementary outputs for heating or cooling and may be used to control several devices such as chimney dampers, stir fans, lamps, heat mats, etc.
43 PP-32 KOOLMASTER PP-32 REV.01 Set Point: 80.0°F Start / Stop Temp Aux. 1 On 80.0°F Aux. 1 Off 80.5°F Refer to the installation setup to activate the auxiliary outputs and to select either if they operate in heating or cooling mode (sec. 5.14.3).
44 PP-32 KOOLMASTER PP-32 REV.01 5.10 ANIMAL AGE The animal age is used as the reference day to determine the position in curves that are used by the controller (temperature curve, minimum ventilation curve). The controller also refers to the animal age to activate the proper clock output programs.
45 PP-32 KOOLMASTER PP-32 REV.01 5.11 CLOCK OUTPUTS The PP-32 has 4 clock outputs to control various devices, using the real- time clock. Refer to the installation setup section to activate the clock outputs (see sec.
46 PP-32 KOOLMASTER PP-32 REV.01 5.11.1 Adjusting Clock Output Start and Stop Times Set the function to "11.Clock Times" from the main menu using the navigation buttons then press the right-arrow key. This menu is only available if clock outputs have been enabled in the installation setup (see sec.
47 PP-32 KOOLMASTER PP-32 REV.01 5.11.2 Adjusting Starting Day of Clock Programs Clock outputs 1 and 2 use up to 8 programs. The user must select the day at which each program starts (this day number is directly related to the animal age). When a new program starts, the previous program is deactivated.
48 PP-32 KOOLMASTER PP-32 REV.01 5.12 HISTORY 5.12.1 Resetting Histories The controller automatically resets all sensor histories when the animal age goes from " Off " to " 1day ". Note that this reset doen't clear the Alarm Log history.
49 PP-32 KOOLMASTER PP-32 REV.01 5.12.3 Individual Temperature Sensors History The controller has an history in which the minimum and maximum temperature readings of each sensor, for the past 10 days, are logged in. Set the function to "3.Temp. Sensors" from the main menu using the navigation buttons then press the right-arrow key.
50 PP-32 KOOLMASTER PP-32 REV.01 Heater 1 Run Time 2002/10/01 30min Use the down-arrow key to scroll the display. Relative humidity's Hi and Lo readings are displayed for the past 10 days. 5.12.6 Water Consumption History The controller has an history in which the water consumption, for the past 60 days, is logged in.
51 PP-32 KOOLMASTER PP-32 REV.01 Press the down-arrow key once. The Use the down-arrow key to scroll the display. The The total heater run time, since the last reset, is displayed. Keep pressing the down-arrow key to scroll the display. The Heater Run Time values recorded for the past 60 days are displayed.
52 PP-32 KOOLMASTER PP-32 REV.01 5.13 ALARM SETTINGS 5.13.1 Alarm Log When an alarm occurs, the light next to the alarm button turns on and the alarm is logged along with the time and date. To view alarms in the alarm log, press the alarm button then use the up and down- arrow keys to step through the recorded alarms.
53 PP-32 KOOLMASTER PP-32 REV.01 5.13.2 Setting Alarm Limits The following diagram explains how temperature alarms are detected: When the average room temperature exceeds the high temperature alarm setting (Set Point + Hi Offset), a high temperature alarm is generated.
54 PP-32 KOOLMASTER PP-32 REV.01 5.13.2.1 Adjusting Hi/ Lo Temperature Alarms The low alarm temperature can be adjusted from 20°F to 0.5°F (11.1 to 0.3°C) below the set point (Lo Offset) . The high alarm temperature can be adjusted from 0.5°F to 20°F (0.
55 PP-32 KOOLMASTER PP-32 REV.01 Temperature Alarm Lo Offset T° 10.0 Hi Offset T° 15.0 Out. Influence 5.0 Temperature Alarm Lo Offset T° 10.0 Hi Offset T° 15.0 Critical 95.0°F 5.13.2.2 Adjusting Critical Temperature The critical temperature is the absolute maximum temperature allowed in the room.
56 PP-32 KOOLMASTER PP-32 REV.01 Static Press Alarm Low Alarm .015WC Hi Alarm .150WC 5.13.2.4 Adjusting Static Pressure Alarms The controller can generate an alarm if the static pressure drops below the low pressure limit or if it exceeds the high pressure limit.
57 PP-32 KOOLMASTER PP-32 REV.01 Press the down-arrow key to select the Hi alarm limit. Use the adjustment buttons to set the Hi alarm limit to the desired value. Note : If you do not want a relay to be turned off in the case of a low static pressure alarm, set the Low Alarm limit to " Off " by pressing the down-arrow key.
58 PP-32 KOOLMASTER PP-32 REV.01 Adjusting the Open-Time for the Hi Static Pressure Alarm The Open-Time of the tunnel curtain or vent doors, in case a Hi static pressure alarm occurs, can be adjusted from 0 to 900 sec. Set the function to "21.Alarm Limits" from the main menu using the navigation buttons.
59 PP-32 KOOLMASTER PP-32 REV.01 5.14 INSTALLATION 5.14.1 Step-by-Step Installation Guide These are the basic steps to start-up your PP-32 controller. 1 . Connect the control according to the wiring diagram enclosed with this manual. 2 . Turn on the power.
60 PP-32 KOOLMASTER PP-32 REV.01 8 . Adjust the temperature set point. This is the target temperature in the room. Refer to section 5.3. 9 . Adjust the start/stop temperature of fan stages (see sec. 5.7) and heater stages (see sec. 5.8). 1 0. Adjust the minimum ventilation cycle settings (see sec.
61 PP-32 KOOLMASTER PP-32 REV.01 Password Enter password: 01 ** ** 5.14.2 Password Settings This function allows to identify 2 different user types. It is used to restrict the access to certain parameters. The password is made up of three blocks of two digits, for example: 13 44 21.
62 PP-32 KOOLMASTER PP-32 REV.01 Installer Password code #1 1 code #2 1 code #3 1 Modifying the Installer's Password The installer's password must first be entered before being allowed to modify it. Proceed as explained above to enter the installer password ( 1-1-1 by default).
63 PP-32 KOOLMASTER PP-32 REV.01 5.14.3 Installation Setup The following section describes how to customize the controller for your particular application. Normally, this setup needs to be done only once. Parameters are presented below in the order they appear on the display.
64 PP-32 KOOLMASTER PP-32 REV.01 8 . Use Static Pressure ? Set to "Yes" to activate the static pressure sensor. 9 . Static Pressure Set 2. Select whether the activation of the second group of static pressure set points is related to a specific stage (Stage) or to the outside tempera- ture (Out T°) .
65 PP-32 KOOLMASTER PP-32 REV.01 1 6. # of Clock Outputs: Set the number of clock outputs to the desired value. Up to 8 clock outputs can be activated. 1 7 . # of Clock Programs for Clock Outputs 1 & 2 : Set the number of programs for clock outputs 1 & 2.
66 PP-32 KOOLMASTER PP-32 REV.01 5.14.4 Sensor Assignment 5.14.4.1 Assigning Sensors to the Room T° and Fan Stages The controller uses the average reading of activated sensors to calculate the room temperature. Fan stages use this temperature to operate.
67 PP-32 KOOLMASTER PP-32 REV.01 5.14.4.2 Assigning Sensors to Heater Stages Heater stages use the average temperature of their assigned sensors to operate. The assignment of heater stages is common to all programs and can only be set in the installer mode (see sec.
68 PP-32 KOOLMASTER PP-32 REV.01 Select "2.Inlet Sensors" then press the right-arrow key. This option is only available in the installer mode (see sec. 5.14.2). Use the navigation buttons to select the desired inlet then press the right- arrow key .
69 PP-32 KOOLMASTER PP-32 REV.01 Use the right and left-arrow keys to select the desired sensor. When the item is flashing, press to activate the sensor or to deactivate it. Proceed in similar fashion to assign sensors to the second auxiliary output, if applicable.
70 PP-32 KOOLMASTER PP-32 REV.01 5.14.5 Setting Time and Date Set the function to "20.Time / Date" from the main menu using the navigation buttons. Press the right-arrow key. The current time and date are displayed. Press the right-arrow key once.
71 PP-32 KOOLMASTER PP-32 REV.01 RELAY ASSIGNMENT EXAMPLE (an empty template is available at the end of this manual) # Y A L E R / T U P T U O 123 456789 0 11 12 13 14 15 16 17 18 19 10 21 22 23 24 25.
72 PP-32 KOOLMASTER PP-32 REV.01 Stage 1a Relays: Relay 1 On(1) Relay 2 Off(1) Relay 3 Off(1) 5.14.6.1 Assigning Fan Stages' Relays Ventilation stages 1 to 4 use a separate relay assignment for each progam in use. Refer to sec. 5.2 to select the proper program.
73 PP-32 KOOLMASTER PP-32 REV.01 To assign relays on timer mode, proceed as described above and use the adjust- ment buttons to select the " Timer " option. 5.14.6.2 Assigning Heater Stages' Relays Set the function to "16.Heater Settings" from the main menu using the navigation buttons then press the right-arrow key.
74 PP-32 KOOLMASTER PP-32 REV.01 Use the navigation buttons to select the " 2. Relay Settings " menu then press the right-arrow key. Use the navigation buttons to select the " 1.Open Relay " or " 2. Close Relay " menu then press the right-arrow key.
75 PP-32 KOOLMASTER PP-32 REV.01 Clock 1 Relays 13 14 15 16 17 18 19 √ Auxiliary 1 Relays 13 14 15 16 17 18 19 √ 5.14.6.5 Assigning Relays to Clock Outputs Set the function to "11.Clock Times" from the main menu using the navigation buttons then press the right-arrow key.
76 PP-32 KOOLMASTER PP-32 REV.01 Lo Static Alarm Relay Assignment 1 2 3 4 5 6 7 √ 5.14.6.7 Assigning Relays for the Lo Static Pressure Alarm This relay is activated if a low static pressure alarm occurs. Refer to sec. 5.13.2 to activate/deactivate the low static pressure alarm.
77 PP-32 KOOLMASTER PP-32 REV.01 5.14.7 Calibrating the Water Counter The PP-32 provides a pulse input to monitor the water consumption. The user must enter the water flow per pulse, it can be adjusted from 1 to 100 gallons per pulse. Set the function to "13.
78 PP-32 KOOLMASTER PP-32 REV.01 5.15 ADVANCED SETTINGS 5.15.1 Setting the Temperature Curve The user can define a temperature curve to adjust the set point auto- matically over a given time period. A curve is defined using up to 10 points. Each point specifies a day number and a set point for that day.
79 PP-32 KOOLMASTER PP-32 REV.01 Note that the temperature curve must be turned off to adjust its points and days. Use the down-arrow key to scroll each point of the curve. The curve status then flashes on the display. Use the adjustment buttons to turn it Off.
80 PP-32 KOOLMASTER PP-32 REV.01 5.15.2 Setting the Minimum Ventilation Curve Fans' On-Time, in minimum ventilation, can automatically be adjusted over a given period of time, by using the minimum ventilation curve. The On-Time changes using 10 steps.
81 PP-32 KOOLMASTER PP-32 REV.01 Note that the minimum ventilation curve must be turned off to adjust its points and days. Use the down-arrow key to scroll each point of the curve. Then the curve status then flashes on the display. Use the adjustment buttons to turn it Off.
82 PP-32 KOOLMASTER PP-32 REV.01 5.15.3 Humidity Control If a humidity sensor is being used, the PP-32 has three mechanisms to compensate for a high humidity level : 1 . The humidity level can be decreased by increasing the fans' on time during minimum ventilation cycles.
83 PP-32 KOOLMASTER PP-32 REV.01 RH Compensation Add Min Vent sec 30 RH set point % 65 Mist shutoff % Off 5.15.3.2 RH Compensation on Minimum Ventilation When the humidity level reaches the RH set point + 10%, the On-Time portion of the minimum ventilation cycle is increased by an amount ranging from 0 to 900 seconds.
84 PP-32 KOOLMASTER PP-32 REV.01 RH Compensation Add Min Vent 30 RH set point % 65 Mist shutoff % 90 5.15.3.3 Adjusting Mist or Kool-Cel Shutoff When the humidity level is too high, Kool-Cel or mist units are shut off to avoid increasing the humidity level any further.
85 PP-32 KOOLMASTER PP-32 REV.01 RH set point % 65 Mist shutoff % Off Heater On time Off Heater Off time 0 full On-Time when the humidity is at or above RH Set Point + 10% as shown below. The cycle time can be adjusted from 0 to 900 seconds. Set the dipswitch #6 to ON to use this function.
86 PP-32 KOOLMASTER PP-32 REV.01 5.15.4 Calibrating Sensors The reading of each sensor can be slightly adjusted by the user in order to obtain the most accurate and uniform readings of all sensors. The calibration of sensors can only be preformed in the installer mode (see sec.
87 PP-32 KOOLMASTER PP-32 REV.01 Use the adjustment buttons to set the humidity level that will be added or removed from all readings of the humidity sensor. 5.15.4.3 Calibrating the Static Pressure Level The reading of the static pressure level can adjusted by an amount of ±0.
88 PP-32 KOOLMASTER PP-32 REV.01 A test mode allows you to simulate temperature changes and verify the controller's performance. In test mode, the temperature sensor inputs are turned off, allowing the user to change the temperature used by the controller to operate the stages.
89 KOOLMASTER PP-32 REV.01 6. TECHNICAL SPECIFICATIONS Type PP-32 Main supply fuse F1 3A, fast-blow Mains supply/frequency 115/230 Vac , 50/60Hz OUT1 to OUT4 0-10Vdc, 10mA max. 14Vdc output 14 Vdc ±10%, regulated, 1A max. 14Vdc output fuse F2 1A max, fast-blow Alarm contact 10mA to 2A, 24 Vac or dc max.
90 KOOLMASTER PP-32 REV.01 7. FACTORY SETTINGS R E T E M A R A P Y R O T C A F G N I T T E S S E U L A V F O E G N A R t n i o P t e S e r u t a r e p m e T F ° 0 .
91 KOOLMASTER PP-32 REV.01 8. USING THE CONFIGURATION MODULE 8.1 Loading a Configuration Loading a Configuration from the Configuration Module into the PP-32 Controller: 1 - Position the configuration module on the J1 connector, at the top left corner of the board, with the components facing DOWN.
92 PP-32 KOOLMASTER PP-32 REV.01 Load Configuration Press +/- to start Save Configuration Press +/- to start 8.2 Saving a Configuration Saving a Configuration from the PP-32 Controller into the Configuration Module: 1 - Place the configuration module on the J1 connector, at the top left corner of the board, with the components facing DOWN.
93 KOOLMASTER PP-32 REV.01 9. INSTALLATION REPORT CONTACT INFORMATION CLIE NT IN FORMA TION INST ALL ER INFORM A TION.
94 PP-32 KOOLMASTER PP-32 REV.01 Room T° (a) Room T ° (b) Room T° (c) Room T ° (d) Heater 1 Heater 2 Heater 3 Heater 4 Heate r 5 Heater 6 Heate r 7 Auxi liar y 1 Auxi liar y 2 Inl et 1 Inl et 2 In.
95 PP-32 KOOLMASTER PP-32 REV.01 : Rese t Mi n/Max Relative humidity sen sor P re- O pen ve nt s dela y Pre-Open tu nnel delay Us e T unn el ? T unne l Mod e Use st atic pressure sen sor? St atic Set .
96 PP-32 KOOLMASTER PP-32 REV.01 RELAY ASSIGNMENT TEMPLATE (see sec. 5.14.6) PROCEDURE 1- Write down the description of each relay. 2- Put an " X " to assign ON/OFF relays or a " T " for relays that operate in timer mode. RELAY ASSIGNEMENT EXAMPLE In minimum vent.
# Y A L E R / T U P T U O 1 23456789 0 11 12 13 14 15 16 17 18 19 10 21 22 23 24 25 26 27 28 29 20 31 32 3 8 e g a t S r e t a e H 7 e g a t S r e t a e H 6 e g a t S r e t a e H 5 e g a t S r e t a e.
98 KOOLMASTER PP-32 REV.01 10. INDEX A Age see Animal age Air inlets see inlets Alarms Alarm connection 1 2 Alarm limits 53–58 Alarm log 5 2 Resetting the alarm log 48, 58, 63 Clock program alarm 45.
99 PP-32 KOOLMASTER PP-32 REV.01 Assigning sensors to air inlets 67 Inlet compenation 22 Inlets' operation 21 Installation Installation report templates 93–96 Installation setup 63–65 Install.
100 PP-32 KOOLMASTER PP-32 REV.01 Clock output settings 45–47 Factory settings 90 Fan stages settings 38 Heater settings 41 Humidity compensation 82–85 Inlet settings 21–22 Minimum ventilation s.
Ein wichtiger Punkt beim Kauf des Geräts Acme Kitchenettes PP-32 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Acme Kitchenettes PP-32 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Acme Kitchenettes PP-32 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Acme Kitchenettes PP-32 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Acme Kitchenettes PP-32 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Acme Kitchenettes PP-32 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Acme Kitchenettes PP-32 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Acme Kitchenettes PP-32. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Acme Kitchenettes PP-32 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.