Benutzeranleitung / Produktwartung WA421 des Produzenten Bard
Zur Seite of 21
INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W A421 W A482 W A602 Manual : 2100-218I Supersedes: 2100-218H File : V olume III T ab 16 Date: 04-19-99 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned.
Contents Figures Figure 1 Unit Dimensions ...................................... 3 Figure 2 Fresh Air Damper Assembly ................... 6 Figure 3 Mounting Instructions ............................... 8 Figure 4 Electric Heat Clearance .............
Manual 2100-218 Page 1 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-218 Page 2 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W A 42 1 – A 10 X N X X X A NOTE: All vent options are without exhaust capability.
Manual 2100-218 Page 3 FIGURE 1 UNIT DIMENSIONS MIS-1262 l e d o M h t d i W ) W ( h t p e D ) D ( t h g i e H ) H ( y l p p u Sn r u t e R EF GIJ K L M N O P Q R S T A BCB 2 4 A W 8 4 A W 5 7 0 . 2 42 3 4 . 2 25 7 8 . 4 88 8 . 98 8 . 9 28 8 . 5 18 8 .
Manual 2100-218 Page 4 ➀ ➁ ➂ TABLE 2 ELECTRICAL SPECIFICATIONS Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes.
Manual 2100-218 Page 5 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
Manual 2100-218 Page 6 FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel. If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position.
Manual 2100-218 Page 7 INST ALLA TION INSTRUCTIONS W ARNING Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death. WALL MOUNTING INFORMATION 1.
Manual 2100-218 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS-416.
Manual 2100-218 Page 9 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum spacing is maintained at all points.
Manual 2100-218 Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET.
Manual 2100-218 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-550.
Manual 2100-218 Page 12 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
Manual 2100-218 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS-1373.
Manual 2100-218 Page 14 THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
Manual 2100-218 Page 15 Low Pressure Switch, Bypass, and Lockout Sequence If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired.
Manual 2100-218 Page 16 PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.
Manual 2100-218 Page 17 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
Manual 2100-218 Page 18 l e d o M d e t a R * M F C d e t a R * P S E d e d n e m m o c e R e g n a R w o l f r i A 1 2 4 A W0 0 4 10 3 .0 5 1 1 - 0 0 6 1 2 8 4 A W0 5 5 10 2 .5 8 2 1 - 0 5 7 1 2 0 6 A W0 0 7 10 3 .5 7 3 1 - 0 5 9 1 TABLE 8 RECOMMENDED AIRFLOW * Rated CFM and ESP on high speed tap.
Manual 2100-218 Page 19 t r a P r e b m u Nn o i t p i r c s e D 5 0 A - 5 0 A W H E 8 0 A - 5 0 A W H E 0 1 A - 5 0 A W H E 5 1 A - 5 0 A W H E s e g a k c a P r e t a e H s e g a k c a P r e t a e H.
Ein wichtiger Punkt beim Kauf des Geräts Bard WA421 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Bard WA421 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Bard WA421 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Bard WA421 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Bard WA421 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Bard WA421 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Bard WA421 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Bard WA421. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Bard WA421 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.