Benutzeranleitung / Produktwartung W70L1 des Produzenten Bard
Zur Seite of 25
Manual 2100-508A Page 1 of 25 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1 Manual : 2100-508A Supersedes: 2100-508 File: V olume III T ab 16 Date: 02-10-09 Bard Manufacturing Company , Inc.
Manual 2100-508A Page 2 of 25 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, 24, 30, 36 .
Manual 2100-508A Page 3 of 25 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-508A Page 4 of 25 W ALL MOUNT GENERAL INFORMA TION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE W 42 A 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in buildi ng.
Manual 2100-508A Page 5 of 25 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing.
Manual 2100-508A Page 6 of 25 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R A .
Manual 2100-508A Page 7 of 25 I A C K 2.13 H J 2.63 9.06 P M L O E .44 W 5.75 F G R S S S S S T D Return A ir Opening MIS-2488 B Drain Inle t Air Air Outlet Front View Side View Cond.
Manual 2100-508A Page 8 of 25 FIGURE 3A W18A1, W18L1, W24A1, W24L1 MOUNTING INSTRUCTIONS 12" 12" 12" 12" 12" 20" 20" 1" 3" 4" Typ.
Manual 2100-508A Page 9 of 25 FIGURE 3B W30A1, W30L1, W36A1, W36L1 MOUNTING INSTRUCTIONS " 12" 12" 12" 12" 12" Typ . 4 " 2 28" 1" 3" 4" Typ .
Manual 2100-508A Page 10 of 25 FIGURE 3C W42A1, W42L1, W48A1, W48L1, W60A1, W60L1, W70A1, W70L1 MOUNTING INSTRUCTIONS D 16" 16" 16" 16" 16" 1 7 8 " 6 1 2 " 6 1 2 " 2 1 8 " 7 8 " 1" 3" 4" Typ.
Manual 2100-508A Page 11 of 25 FIGURE 4 ELECTRIC HEAT CLEARANCE W30A1, W30L1, W36A1, W36L1, W42A1, W42L1, W48A1, W48L1, W60A1, W60L1, W70A1, W70L1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials.
Manual 2100-508A Page 12 of 25 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS DUCT OPENING RETURN AIR SUPPLY AIR WOOD FRAME WALL INSTALLATION OPENING WALL BE FO R E MOUNT ON UNIT OPENING BEFORE INSTALL ATION BOTTOM M OUNTING CONCRET E B L OCK WAL L I NS T A LL AT IO N BRACKET.
Manual 2100-508A Page 13 of 25 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS LOWER ED RAISED FLOO R RAFTERS SUPPLY AIR CEILING SURFACE WAL L SL EEVE RETURN AIR CLOSET W ALL GRILL E FLASHING RETURN AIR F.
Manual 2100-508A Page 14 of 25 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
Manual 2100-508A Page 15 of 25 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant.
Manual 2100-508A Page 16 of 25 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH All W**A/W**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch.
Manual 2100-508A Page 17 of 25 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.
Manual 2100-508A Page 18 of 25 TROUBLESHOOTING FIGURE 8 FAN BLADE SETTING MIS-1724 TABLE 1 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
Manual 2100-508A Page 19 of 25 TABLE 3 COOLING PRESSURE TABLE Air Temperature Entering Outdoor Coil °F Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil.
Manual 2100-508A Page 20 of 25 TABLE 4 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Manual 2100-508A Page 21 of 25 TABLE 5 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Manual 2100-508A Page 22 of 25 TABLE 6 RECOMMENDED AIRFLOW TABLE 7 INDOOR BLOWER PERFORMANCE TABLE 8 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY V alues shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter . Derate ESP by .
Manual 2100-508A Page 23 of 25 TABLE 9 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 .
Manual 2100-508A Page 24 of 25 W18A1-A W24A1-A W24A1-B W24A1-C W30A1-A W30A1-B W30A1-C W36A1-A W36A1-B W36A1-C W42A1-A W42A1-B W42A1-C W48A1-A W48A1-B W48A1-C W60A1-A W60A1-B W60A1-C W70A1-A W70A1-B W.
Manual 2100-508A Page 25 of 25 TABLE 11 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60, W70 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) e s a h P - 1 V 0 3 2.
Ein wichtiger Punkt beim Kauf des Geräts Bard W70L1 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Bard W70L1 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Bard W70L1 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Bard W70L1 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Bard W70L1 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Bard W70L1 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Bard W70L1 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Bard W70L1. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Bard W70L1 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.