Benutzeranleitung / Produktwartung 3100-01 des Produzenten Sierra Monitor Corporation
Zur Seite of 24
MODEL 3100-XX FLAME DETECTOR.
Sierra Monitor Corporation 1991 T arob Court, Milpitas, CA 95035 (408) 262-661 1, T oll Free: 800-727-4377 Fax: 408-262-9042 MODEL 3100-XX Flame Detector APPLICABILITY & EFFECTIVITY This manual pr.
Instruction Manual T able of Contents TABLE OF CONTENTS SECTION PAGE 1 . PRODUCT DESCRIPTION 1 2 . OPERA TION 2 2.1 General 2 2.2 Field-of-V iew 3 2.3 Range 3 2.4 Environment 3 2.5 Configuration 3 2.6 LED operation 4 2.7 Relay operation 5 3 . INST ALLA TION 7 3.
Model 3100 Series Flame Detector (1 1/04) Page: 1 Instruction Manual FIGURE 1-1: Model 3100 Series Flame Detector 1. PRODUCT DESCRIPTION 1.1 Introduction All versions of the Model 3100 Flame Detector Se- ries utilize Ultraviolet, Infrared and V isible spectrum to provide continuous and reliable flame detection.
Instruction Manual Page: 2 Model 3100 Series Flame Detector (1 1/04) 2 . OPERA TION 2. 1 General When the Model 3100 Flame Detector is powered up, the microprocessor checks the configuration switch settings and configures the detector . The mi- croprocessor then runs a full series of self tests.
Model 3100 Series Flame Detector (1 1/04) Page: 3 Instruction Manual 2.2 Field-of-V iew (See Figur e 2-1) Optical Flame Detectors must be able to “see” the fire to declare an alarm. Any obstruction between the detector and the threat area will impair the de- tectors ability to cover the threat area.
Instruction Manual Page: 4 Model 3100 Series Flame Detector (1 1/04) LED 1 LED 2 Mounting Screw (2 locations) Configuration Switches 2.5.2 V erify Control The Enhanced Model 3100-02, -03, -04, - 05 and -06 have the V erified Fire function.
Model 3100 Series Flame Detector (1 1/04) Page: 5 Instruction Manual (“on” or “off”) of a switch (SW1-SW8). The first flash pattern indicates the position of the first switch (SW1), with each consecu- tive flash indicating the position of the next switch in order .
Instruction Manual Page: 6 Model 3100 Series Flame Detector (1 1/04) ing” - remain energized until power is re- moved, ”Fire Following” - de-energize a short time after the fire is no longer detected. The “J2” connector provides connections for both normally open contacts and normally closed contacts on the Fire Relay .
Model 3100 Series Flame Detector (1 1/04) Page: 7 Instruction Manual 3. 0 INST ALLA TION 3.1 General Precautions All wiring and installation must be done in accor- dance with the NFP A 70 and 72 standards and must comply with any codes specific to the application or location.
Instruction Manual Page: 8 Model 3100 Series Flame Detector (1 1/04) 3.3.5 Auxiliary Relay The Auxiliary Relay connector is located be- tween the Power and Fire Relay connectors. The connection points are labeled “Aux In” and “Aux Out”. The Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 9 Instruction Manual 5 . 0 TROUBLESHOOTING The flame detector has several built-in self test mechanisms which verify function and calibration. The following procedure covers most faults and problems which may occur during installation or during the course of normal operation.
Instruction Manual Page: 10 Model 3100 Series Flame Detector (1 1/04) 1. If the relay closes (0 ohms on the meter) and the LEDs come “on” the detector is operating normally .
Model 3100 Series Flame Detector (1 1/04) Page: 11 Instruction Manual 6 .0 SPECIFICA TIONS SIERRA MONITOR CORPORA TION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment.
Instruction Manual Page: 12 Model 3100 Series Flame Detector (1 1/04) Figure A-2: Model 3100 Series Dimensions Figure A-1: Model 3100 Series Exploded V iew APPENDIX A.
Model 3100 Series Flame Detector (1 1/04) Page: 13 Instruction Manual Figure A-3: Model 3100 Series Common W iring Connections.
Instruction Manual Page: 14 Model 3100 Series Flame Detector (1 1/04) Figure A-4: Model 3100 Series (Enhanced) W iring Connections Factory jumpers are used to set NC or NO connections.
Model 3100 Series Flame Detector (1 1/04) Page: 15 Instruction Manual APPENDIX B T ABLES B.1 Dip Switch Settings B.1.1 Sensitivity Sensitivity SW1 SW2 Level 20 Foot O N O N 4 40 Foot OF F O N 3 60 Foot O N OF F 2 80 Foot OF F OF F 1 B.
Instruction Manual Page: 16 Model 3100 Series Flame Detector (1 1/04) B.2 Connectors B.2.1 Fire Relay Connector (J2) Fire Relay Description Pin 1 (Left Most) & Pin 2 Normally Open Side of Relay Pin 3 & Pin 4 (Middle) Common or Center Side of Relay Pin 5 & Pin 6 (Right Most) Normally Closed Side of Relay B.
Model 3100 Series Flame Detector (1 1/04) Page: 17 Instruction Manual B.3 V erify/Aux. Relay Configurations Model # V erify Relay Aux. Relay 3100-02 Open Contacts Closed Contacts 3100-03 Closed Contac ts Open Contacts 3100-04 Open Contacts Open Contacts 3100-05 Closed Contact Closed Contacts B.
Instruction Manual Page: 18 Model 3100 Series Flame Detector (1 1/04) B.7 Detector Response to Fuels T able Fuel Distance Fire Size Response T ime Heptane 80 Feet 1 Square Foot Less than 3 sec. Silane 5 0 Feet 18 inch jet Less than 3 sec. Hydrogen 15 Feet 18 inch jet Less than 5 sec.
Model 3100 Series Flame Detector (1 1/04) Page: 19 Instruction Manual APPENDIX C -- WIRING CONNECTIONS.
Instruction Manual Page: 20 Model 3100 Series Flame Detector (1 1/04) Index A Alarm Mode 2, 4 V erified 2 Auxiliary Relay 1, 2, 5, 6, 7 C Cleaning 8 Conduit 7, 11 Configuration Relay Control 4 Sensitivity 3 Switches 3, 4 V erify Control 4 Configuration Switches 5 Connection 7 Connector Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 21 Instruction Manual T T esting 8 U Ultraviolet 3 V V erified Fire 2, 4, 5, 6 V erify Control 4 Relay 2, 4, 5, 6, 7, 15 V erify Control 6, 15 V ersions.
Ein wichtiger Punkt beim Kauf des Geräts Sierra Monitor Corporation 3100-01 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Sierra Monitor Corporation 3100-01 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Sierra Monitor Corporation 3100-01 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Sierra Monitor Corporation 3100-01 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Sierra Monitor Corporation 3100-01 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Sierra Monitor Corporation 3100-01 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Sierra Monitor Corporation 3100-01 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Sierra Monitor Corporation 3100-01. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Sierra Monitor Corporation 3100-01 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.