Benutzeranleitung / Produktwartung TPS3 12 des Produzenten Siemens
Zur Seite of 16
User Manual - USA TPS3 12 & TPS3 15 Surge Prot ective De vice.
• Only qualified licensed electricians should install or ser vice SPDs • Hazardous voltages e xist within SPDs • SPDs should never be installed or serviced when energized • Use appropriat e s.
T able of Contents F AILURE T O FOLLO W THESE INSTRUCTIONS COULD RESUL T IN DEA TH OR SERIOUS INJURY .............................. 2 Do Not Hi-Po t T est SPDs ...........................................................................................
Introduction Thank you for choosing Siemens TPS3 Surge Pro tective Device (SPD). This is a high quality , high energy surge suppres sor designed to prot ect sensitive equipment fr om damaging transient overvoltages. Proper installation is important to maximize per formance.
2008 NEC Ar t 285 & UL 1449-3 SPD T ypes: T ypes 1, 2, 3, & 4 Based on Location within electrical distribution system (also coincides with ANSI/IEEE C62.
TPS SERIES DESCRIPTION TPS3 12 Externally mount ed SPD, single module in enclosure, standard modes of pr ot ection TPS3 L12 Externally mount ed SPD, single module in enclosure, 10 modes of pr otection.
Parallel Connection This is a Parallel connected SPD – not series connected. As outlined previousl y , an SPD ‘drains of f ’ excessiv e voltage fr om an electrical system. Because of parallel connection, installation of the SPD reasonably near the eq uipment to be pro tect ed is satisfactory.
T able 2: Weight & Dimensions TPS3 12 H/W/D (in./mm.) Weight Standar d Enclosure 12" x12" x 7.5" (305x305x191) 22 lbs (10 kg) Standar d Enclosure, 400 – 500kA with Opt. Disc. Switch 16" x 14" x 6" (496x356x152) 32 lbs (14.
T erminals T erminals will accept 14 - 2 A WG conductor and are provided for line (phase), neutral (if used), and equipment safety ground connections. 8 A WG is the minimum recommended wire size because UL testing and evaluation was performed using 8 A WG.
Optional Flush Mount Installation Considerations The TPS3 12 and TPS3 15 are appro ximately 6” deep. The unit will not mount flush unless there is at least 6” of depth clearance. The TPS3 12 and TPS3 15 are not designed to mount flush on a typical 2 x 4 stud wall.
PRE-PL AN INST ALL A TION TO ACC OMPLISH THE FOLLO WING: • Meet all National and Local codes (NEC® Ar ticle 285 addresses SPDs) • Mount SPD as close to panel or equipment as possible to keep leads short • Ensure leads are as shor t and straight as possible, including neutral and ground.
Figure 4: Electrical Dra wings Figur e 1 SPLIT 2 Hots, 1 Neu, 1 Grnd Hot (BLK) Hot (BLK) Neutral (WHT ) V V } } Ground (GRN ) Figur e 2 WYE 3 Hots, 1 Neu, 1 Grnd } Phase A (BLK) Phase B (BLK) Neutral .
Phase A, B & C: Green LED indicators—one per phase. Green is good. Extinguished green LED indicates loss of prot ection. Every suppres sion element in this SPD is monitor ed. N-G suppres sion element monitoring is logic-connected t o Phase A. Ser vice LED (red): LED illuminates in the event of problems.
Dr y Contact Option T wo sets of Form C dr y contacts are included with the Dr y Cont act option. Dry Contacts change state during inoper ative conditions, including loss of power . Any status change can be monitored elsewhere via Dr y Contacts. A T erminal Block includes two sets of Normally Open (N.
Display Replacement The display is field replaceable. Deenergize SPD, confirm with appropriat e measurement equipment and dischar ge internal capacitance to ground. Mark locations and carefully disconnect diagnostic cables, contacts, connecting conduct ors, etc.
Siemens Industr y , Inc. Building T echnologies Division 5400 T riangle Parkway Norcr oss, GA 30092 888-333-3545 info.us@siemens.com 6.17.11.jb #8172.
Ein wichtiger Punkt beim Kauf des Geräts Siemens TPS3 12 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Siemens TPS3 12 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Siemens TPS3 12 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Siemens TPS3 12 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Siemens TPS3 12 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Siemens TPS3 12 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Siemens TPS3 12 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Siemens TPS3 12. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Siemens TPS3 12 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.