Benutzeranleitung / Produktwartung SQM5 des Produzenten Siemens
Zur Seite of 31
SQM5… Technical Instructions Document No. 155-517P25 July 9, 2007 Reversing Actuators ISO 9000 and 14000 REGISTERED FIRM ¤ EA0511R1 Siemens Building Technologies, Inc. Description SQM5... reversing actuators are used for the pos itioning of flow control valves, butterfly valves, dampers, or any application requiring rotary motion.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 2 Siemens Building Technologies, Inc. Features, Continued • Connections for both base and face mounting .
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 3 Table Of Contents Application Page 2 Product Numbers Product numbers .
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 4 Siemens Building Technologies, Inc. Product Numbers Table 1. Product Numbers for Pre-assembled Actuators. Torque 1 Running Time 2 [lb-in] 90°@ 60 Hzsec Line Voltage 4-20 mA 0-135 Ω 0-10 Vdc 110 V 220 V 24 V 90 8 ccw x x SQM50.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 5 Table 2. Product Numbers for Accessories. Electronic Circuit Boards AGA56.1A97 24-250 Vac (A) board for SQM5x.xxxxx A x AGA56.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 6 Siemens Building Technologies, Inc. Product Number Identification Legend For actuator identification only. To select product numbers for ordering, see Table 1.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 7 Installation and Operation Instructions SQM5… actuators are sometimes shipped without the shaft installed. To install the selected shaft: 1.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 8 Siemens Building Technologies, Inc. Rotational Direction Verification Actuator model numbers that end wit.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 9 Sw itch Adjustment, Continued NOTE: If a potentiometer is installed, the adjustable range of the switches depends on the range of the potentiometer.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 10 Siemens Building Technologies, Inc. Wiring Connections NOTE: SQM5… actuators require a single source, single phase power supply. Wiring connections vary depending on which AGA56….
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 11 Wiring, Continued 0 AZ L AZ L AUTO. MAN. AGA56.1A97 EA0554R3 Figure 8. AGA56.1A97 Terminal/Auto-Manual Board. AGA56.41/42/43… Circuit Boards.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 12 Siemens Building Technologies, Inc. Wiring, Continued EA0556R5 MAX MIN OPE MAX MIN AGA56.4... REG MAX MIN MIN MAX Y 123 11 21 12 22 13 23 M I II III IV V 4 5 14 15 24 25 1 2 13 3 21 12 51 N VI 6 16 26 A L Z wire leads LR ZL 13 N Y+ Y- U M Y M Y (+2 V) 0.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 13 AGA56.9… Circuit Boards See Figures 11 and 12. Manual Operation 1. Set the AUTO/MAN switch in the MAN position. 2. Connect ground to the screw locat ed below the shaft release button.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 14 Siemens Building Technologies, Inc. Wiring, Continued EA0557R6 AGA56.9... Y 0...3 25% 50% 75% MAX MIN 0 or 12 mA 10 mA 8 mA 6 mA 14 mA 16 mA 18 mA 25% 50% 75% MAX 4 mA 20 mA MIN ZF = POS POS LIN Y 0.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 15 Modulation Adjustment See Figures 10 and 12. The blue trim potentiometers allow the adjustment of the minimum (zero) and maximum (span) positions.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 16 Siemens Building Technologies, Inc. Cover Installation 1. Lift the two screws on the cover corner s and slide the cover end into the grooves at the gear end of the actuator.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 17 Electronic Linearization Function Butterfly valves have non-linear flow characteristics. Near the fully closed position, a small change in the valve’s position will produc e a very large change in flow.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 18 Siemens Building Technologies, Inc. Features of SQM5x.xxxxx G x, SQM5x.xxxxx H x, SQM5x.xxxxx K x Actuators SQM5x.xxxxx G x actuators contain the AGA56.41A… circuit board with terminals Y- and Y+ for 4 to 20 mA modulating input.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 19 Reversing Rotational Direction, Continued EA1210R1 POSITION INDICA TION POINTER BROWN BLACK BLUE max. min. max. min. EA1209R1 POSITION INDICA TION POINTER BLUE BLACK BROWN max.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 20 Siemens Building Technologies, Inc. Reversing Rotational Direction, Continued 8. Firmly tighten the black potentiomete r cam attachment screw while manually holding the potentiometer position indica tion pointer in alignment.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 21 AGA56.41/42/43 Circuit Board Installation, Continued 5.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 22 Siemens Building Technologies, Inc. AGA56.41/42/43 Circuit Board Installation, Continued 8. Make the following connections to the actuator: See Figure 22. a.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 23 AGA56.9A… Circuit Board Installation, Continued 4. Guide the base circuit board from the switch housing side of the actuator into the bottom of the circuit board mounting bracket.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 24 Siemens Building Technologies, Inc. AGA56.9A… Circuit Board Installation, Continued 8. Gently guide the L-shaped circuit board containing the three blue trim potentiometers into the vertical support slots located on the cam drum side of the actuator.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 25 Potentiometer Removal 9. Remove the white plastic actuator posit ion-indicating dial by gently pulling while rotating in the clockwise direction.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 26 Siemens Building Technologies, Inc. Specifications SQM5.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 27 Specifications SQM5... Reversing Actuator, Continued Circuit Boards AGA56.1A97 AGA56.41A… AGA56.42A… Conduit connection Two removable inserts with two 1/2-inch NPSM threads.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 28 Siemens Building Technologies, Inc. Specifications, continued AGA56.43A… AGA56.9A ASZ... Potentiometers AGA56.43A… Electronic circuit boards Same specifications as AGA56.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Siemens Building Technologies, Inc. Page 29 Dimensions The first dimension given is measured in inches.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Page 30 Siemens Building Technologies, Inc. Dimensions, Continued 1 1/16 (18) 6-7/16 (164) 4 X 1/4 (7) 4 X 1/4 (7) 1/8 (3) C L AGA57.3 EA0519R2 4-1/16 (103.3) 4-7/16 (1 13) 3-1/8 (80) 4-7/8 (123.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Information in this publicati on is based on current specifications . The company reserves the right to make changes in specifi ca tions and models as design improvements are introduced.
Ein wichtiger Punkt beim Kauf des Geräts Siemens SQM5 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Siemens SQM5 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Siemens SQM5 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Siemens SQM5 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Siemens SQM5 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Siemens SQM5 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Siemens SQM5 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Siemens SQM5. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Siemens SQM5 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.