Legal information Legal information Warni ng notice system This manual contains notices y ou have to observe in or der to en sure your personal saf ety, as well as to prevent damage to property.
Preface Overview of the SCALANCE X product fa mily The SCALANCE X-200 product fam ily is part of the SCALANCE X pro duct family. Below, you will find a brief overvie w of this product family. The SCALANCE X family comprises v arious product lines that complement each other and that are carefully tuned to s pecific automation tasks.
Preface SCALANCE X-200 4 Operating Instructions, 12/2011, A5E00349864 -19 The only difference between the SC ALANCE XF204IRT and the SCALA NCE X-204IRT i s the shape. SCALANCE X-200 IRT PRO managed In terms of functionality, the SC ALANCE X200 IRT PRO switches a re the same as the SCALANCE X-200 IRT managed switc hes listed above.
Preface SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 5 One particular advantage of the SCALANCE X-200IRT switches in P ROFINET networks is the integrated ERTEC.
Preface SCALANCE X-200 6 Operating Instructions, 12/2011, A5E00349864 -19 SIMATIC NET SCALANCE X201-3P IRT PRO 6GK5201-3JR00-2BA6 SIMATIC NET SCALANCE X202-2P IRT 6GK5202-2BH00-2BA3 SIMATIC NET SCALAN.
Table of contents Preface ...................................................................................................................................................... 3 1 Safety not ices ............................................... ......
Table of contents SCALANCE X-200 8 Operating Instructions, 12/2011, A5E00349864 -19 3.10.2 SCALANCE X F204-2 TP ports ............................... .................................................................... 55 3.10.3 SCALANCE X F204-2 FO ports .
Table of contents SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 9 3.22.3 SCALANCE X201-3P IRT PRO FO interfaces .................. ........................................................ 105 3.23 SCALANCE X202-2P IRT ...............
Table of contents SCALANCE X-200 10 Operating Instructions, 12/2011, A5E00349864-19 6.1.3 Configurat ion with DHCP .................................. ........................................................................ 154 6.2 Updating the firmwa re with the boot loader .
Table of contents SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 11 8 PROFINET IO f unctiona lit y .................................... ................................................................................ 245 8.1 Configuring wi th PROFINET IO .
Table of contents SCALANCE X-200 12 Operating Instructions, 12/2011, A5E00349864-19.
Safety notices 1 1.1 Important notes on using the device Safety notices on the use of the devices The following safety notices must be adhere d to when setting up and operating the de vice and during all work relating to i t such as i nstallation, connec ting up, replacing devi ces or opening the device.
Safety notices 1.1 Important notes on using the device SCALANCE X-200 14 Operating Instructions, 12/2011, A5E00349864-19 WARNING Replacing components EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2 OR ZONE 2.
Safety notices 1.1 Important notes on using the device SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 15 WARNING Suitable cables for temperat ures in excess of 70 °C If the cable or conduit entry poin t exceeds 70 °C or the branch ing point of conductors exceeds 80 °C, speci al precautions mus t be taken.
Safety notices 1.1 Important notes on using the device SCALANCE X-200 16 Operating Instructions, 12/2011, A5E00349864-19.
Network topologies / media redundancy 2 2.1 Network topologies Switching technology allows extensive n etworks to be set up with numerous nodes an d simplifies networ k expansion. Which topologies can be implemented? Bus, ring, or star topologies can be implemented with the X-200 IE switches.
Network topologies / media redundancy 2.1 Network topologies SCALANCE X-200 18 Operating Instructions, 12/2011, A5E00349864-19 Star topology Figure 2-2 Electrical star topol ogy.
Network topologies / media redundancy 2.1 Network topologies SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 19 Ring topology Figure 2-4 Optical ring topology , example with SCALANCE X.
Network topologies / media redundancy 2.1 Network topologies SCALANCE X-200 20 Operating Instructions, 12/2011, A5E00349864-19 S7-400 Switch SCALANCE X-400 S7-300 PC Switch SCAL ANCE X208 PC PC S7-400.
Network topologies / media redundancy 2.1 Network topologies SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 21 Figure 2-7 Ring topology with optic al ring, example with SCALAN CE X202.
Network topologies / media redundancy 2.2 Options of media redun dancy SCALANCE X-200 22 Operating Instructions, 12/2011, A5E00349864-19 2.2 Options of media redundancy There are various options avail.
Network topologies / media redundancy 2.3 Media redundancy in ring topologie s SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 23 2.3 Media redundancy in ring topologies Structure of a ring topology Nodes in a ring topology can be external switches an d/or the in tegrated switches of communications mo dules.
Network topologies / media redundancy 2.3 Media redundancy in ring topologie s SCALANCE X-200 24 Operating Instructions, 12/2011, A5E00349864-19 An interruption of the ring can be caused by loss of the con nec tion between two devices or by failure of a device in the ring.
Network topologies / media redundancy 2.4 MRP SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 25 2.4 MRP The "MRP" method conforms to the Media Redunda ncy Protocol (MRP ) specified in the standard IEC 62439-2 Ed ition 1.0 2010-02.
Network topologies / media redundancy 2.4 MRP SCALANCE X-200 26 Operating Instructions, 12/2011, A5E00349864-19 Topology The following schematic shows a possible topolog y for devices i n a ring with MRP.
Network topologies / media redundancy 2.5 MRPD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 27 2.5 MRPD The redundancy procedure MRPD (Media Redundancy with Path Dupli cation) The MRPD procedure is specifi ed in IEC 61158 Parts 5 and 6 type 10 "PROFINET".
Network topologies / media redundancy 2.6 HSR SCALANCE X-200 28 Operating Instructions, 12/2011, A5E00349864-19 2.6 HSR The "HSR" method allows a reconfiguration time of 0.
Network topologies / media redundancy 2.7 Redundant coupli ng of network segments SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 29 2.7 Redundant coupling of network segments Coupling option The coupling of two network segm ents shown here as an example i s possible with X- 200IRT, X-300 and X-400 IE switc hes.
Network topologies / media redundancy 2.7 Redundant coupli ng of network segments SCALANCE X-200 30 Operating Instructions, 12/2011, A5E00349864-19.
3 Product properties 3.1 Overview of the product characteristics Table 3- 1 Overview of the product characteristics Device type SCALANCE XF204 X208 XF208 X216 X224, X204-2 X204-2TS XF204-2 X206-1 XF20.
Product properties 3.1 Overview of the pr oduct characteristics SCALANCE X-200 32 Operating Instructions, 12/2011, A5E00349864-19 Table 3- 2 Overview of th e connection options Fast Ethernet 10/100 Mb.
Product properties 3.2 Components of the product SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 33 3.2 Components of the product The following component s ship with the device (except.
Product properties 3.3 Unpacking and checki ng SCALANCE X-200 34 Operating Instructions, 12/2011, A5E00349864-19 3.3 Unpacking and checking Unpacking, checking 1.
Product properties 3.4 SCALANCE XF204 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 35 3.4 SCALANCE XF204 3.4.1 SCALANCE XF204 pro duct characteristics Possible attachments The SCALANCE XF204 has four RJ- 45 jacks fo r connecting end de vi ces or other network segments.
Product properties 3.4 SCALANCE XF204 SCALANCE X-200 36 Operating Instructions, 12/2011, A5E00349864-19 3.4.2 SCALANCE XF204 TP ports Connector pinout On the SCALANCE XF204, the TP por ts are implemented as RJ-45 ja cks with the MDI-X assignment (Medium Dependent Interf ace Autocrossover) of a netw ork component.
Product properties 3.4 SCALANCE XF204 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 37 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.5 SCALANCE X208 SCALANCE X-200 38 Operating Instructions, 12/2011, A5E00349864-19 3.5 SCALANCE X208 3.5.1 SCALANCE X208 product characteristics Possible attachments The SCALANCE X208 has eight RJ-45 j acks for the connection of e nd devi ces or other network segments.
Product properties 3.5 SCALANCE X208 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 39 3.5.2 SCALANCE X208 TP ports Connector pinout On the SCALANCE X208, the TP ports are implemen ted as RJ--45 ja cks wit h MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.5 SCALANCE X208 SCALANCE X-200 40 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.6 SCALANCE XF208 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 41 3.6 SCALANCE XF208 3.6.1 SCALANCE XF208 pro duct characteristics Possible attachments The SCALANCE XF208 has eight RJ- 45 jacks for the connection of end devices or other network segments.
Product properties 3.6 SCALANCE XF208 SCALANCE X-200 42 Operating Instructions, 12/2011, A5E00349864-19 3.6.2 SCALANCE XF208 TP ports Connector pinout On the SCALANCE XF208, the TP por ts are implemented as RJ-45 ja cks with the MDI-X assignment (Medium Dependent Interf ace Autocrossover) of a netw ork component.
Product properties 3.6 SCALANCE XF208 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 43 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.7 SCALANCE X216 SCALANCE X-200 44 Operating Instructions, 12/2011, A5E00349864-19 3.7 SCALANCE X216 3.7.1 SCALANCE X216 product characteristics Possible attachments The SCALANCE X216 has 16 RJ-45 jacks fo r the connection of end device s or other network segments.
Product properties 3.7 SCALANCE X216 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 45 3.7.2 SCALANCE X216 TP ports Connector pinout On the SCALANCE X216, the TP ports are implemen ted as RJ-45 jac ks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.7 SCALANCE X216 SCALANCE X-200 46 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.8 SCALANCE X224 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 47 3.8 SCALANCE X224 3.8.1 SCALANCE X224 product characteristics Possible attachments The SCALANCE X224 has 24 RJ-45 jacks fo r the connection of end device s or other network segments.
Product properties 3.8 SCALANCE X224 SCALANCE X-200 48 Operating Instructions, 12/2011, A5E00349864-19 3.8.2 SCALANCE X224 TP ports Connector pinout On the SCALANCE X224, the TP ports are implemen ted as RJ-45 jac ks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.8 SCALANCE X224 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 49 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.9 SCALANCE X204-2 / SCALANCE X204-2TS SCALANCE X-200 50 Operating Instructions, 12/2011, A5E00349864-19 3.9 SCALANCE X204-2 / SCALANCE X204-2TS 3.
Product properties 3.9 SCALANCE X204-2 / SCALANCE X204-2TS SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 51 3.9.2 SCALANCE X204-2 / SCALANC E X204-2TS TP interfaces Connector pinout .
Product properties 3.9 SCALANCE X204-2 / SCALANCE X204-2TS SCALANCE X-200 52 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.9 SCALANCE X204-2 / SCALANCE X204-2TS SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 53 3.9.3 SCALANCE X204-2 / SCALANC E X204-2TS FO interfaces Transmission speed The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps.
Product properties 3.10 SCALANCE XF204-2 SCALANCE X-200 54 Operating Instructions, 12/2011, A5E00349864-19 3.10 SCALANCE XF204-2 3.10.1 SCALANCE XF204-2 pro duct characteristics Possible attachments The SCALANCE XF204-2 has fou r R J-45 jacks and two BFOC ports fo r the connec tion of end devices or other network segments.
Product properties 3.10 SCALANCE XF204-2 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 55 3.10.2 SCALANCE XF204-2 TP ports Connector pinout On the SCALANCE XF204-2, the TP ports are implemented as RJ-45 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.10 SCALANCE XF204-2 SCALANCE X-200 56 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.10 SCALANCE XF204-2 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 57 3.10.3 SCALANCE XF204-2 FO ports Transmission speed The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.11 SCALANCE X206-1 SCALANCE X-200 58 Operating Instructions, 12/2011, A5E00349864-19 3.11 SCALANCE X206-1 3.11.1 SCALANCE X206-1 prod uct characteristics Possible attachments The SCALANCE X206-1 has six RJ- 45 j acks and a BFOC port for the connection of end devices or other net work segment s.
Product properties 3.11 SCALANCE X206-1 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 59 3.11.2 SCALANCE X206-1 TP ports Connector pinout On the SCALANCE X206-1, the TP por ts are implemented as RJ-45 j acks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.11 SCALANCE X206-1 SCALANCE X-200 60 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.11 SCALANCE X206-1 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 61 3.11.3 SCALANCE X206-1 FO ports Transmission speed The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.12 SCALANCE XF206-1 SCALANCE X-200 62 Operating Instructions, 12/2011, A5E00349864-19 3.12 SCALANCE XF206-1 3.12.1 SCALANCE XF206-1 pro duct characteristics Possible attachments The SCALANCE XF206-1 has six RJ- 45 jacks and a BFOC port for th e connection of end devices or other network segments.
Product properties 3.12 SCALANCE XF206-1 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 63 3.12.2 SCALANCE XF206-1 TP ports Connector pinout On the SCALANCE XF206-1, the TP ports are implemented as RJ-45 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.12 SCALANCE XF206-1 SCALANCE X-200 64 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.12 SCALANCE XF206-1 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 65 3.12.3 SCALANCE XF206-1 FO ports Transmission speed The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.13 SCALANCE X212-2 SCALANCE X-200 66 Operating Instructions, 12/2011, A5E00349864-19 3.13 SCALANCE X212-2 3.13.1 SCALANCE X212-2 prod uct characteristics Possible attachments The SCALANCE X212-2 has 12 RJ-45 jacks and two BFOC inte rfaces for connecting en d devices or other net work segment s.
Product properties 3.13 SCALANCE X212-2 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 67 3.13.2 SCALANCE X212-2 TP ports Connector pinout On the SCALANCE X212-2, the TP por ts are implemented as RJ-45 j acks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.13 SCALANCE X212-2 SCALANCE X-200 68 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.13 SCALANCE X212-2 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 69 3.13.3 SCALANCE X212-2 FO ports Transmission speed The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.14 SCALANCE X204-2LD SCALANCE X-200 70 Operating Instructions, 12/2011, A5E00349864-19 3.14 SCALANCE X204-2LD 3.14.1 SCALANCE X204-2LD product characteristics Possible attachments The SCALANCE X204-2LD has four RJ-45 ja cks and two BFOC ports f or the connection of end devices or other network segments.
Product properties 3.14 SCALANCE X204-2LD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 71 3.14.2 SCALANCE X204-2LD TP ports Connector pinout On the SCALANCE X204-2LD, the TP ports are implemented a s RJ-45 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.14 SCALANCE X204-2LD SCALANCE X-200 72 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.14 SCALANCE X204-2LD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 73 3.14.3 SCALANCE X204-2LD TP ports Transmission rate The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.14 SCALANCE X204-2LD SCALANCE X-200 74 Operating Instructions, 12/2011, A5E00349864-19 Connectors The cables are connected over BFOC sockets.
Product properties 3.15 SCALANCE X206-1LD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 75 3.15 SCALANCE X206-1LD 3.15.1 SCALANCE X206-1LD product characteristics Possible attachments The SCALANCE X206-1LD has six RJ-45 jacks and a BFOC port for t he connection of end devices or other net work segment s.
Product properties 3.15 SCALANCE X206-1LD SCALANCE X-200 76 Operating Instructions, 12/2011, A5E00349864-19 3.15.2 SCALANCE X206-1LD TP ports Connector pinout On the SCALANCE X206-1LD, the TP ports are implemented a s RJ-45 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.15 SCALANCE X206-1LD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 77 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.15 SCALANCE X206-1LD SCALANCE X-200 78 Operating Instructions, 12/2011, A5E00349864-19 3.15.3 SCALANCE X206-1LD FO ports Transmission rate The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.15 SCALANCE X206-1LD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 79 Connectors The cables are connected over BFOC sockets.
Product properties 3.16 SCALANCE X212-2LD SCALANCE X-200 80 Operating Instructions, 12/2011, A5E00349864-19 3.16 SCALANCE X212-2LD 3.16.1 SCALANCE X212-2LD product characteristics Possible attachments The SCALANCE X212-2LD has twel ve RJ-45 jacks and two BFO C ports for the connection of end devices or other network segm ents.
Product properties 3.16 SCALANCE X212-2LD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 81 3.16.2 SCALANCE X212-2LD TP ports Connector pinout On the SCALANCE X212-2LD, the TP ports are implemented a s RJ-45 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.16 SCALANCE X212-2LD SCALANCE X-200 82 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.16 SCALANCE X212-2LD SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 83 3.16.3 SCALANCE X212-2LD FO ports Transmission rate The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.16 SCALANCE X212-2LD SCALANCE X-200 84 Operating Instructions, 12/2011, A5E00349864-19 Connectors The cables are connected over BFOC sockets.
Product properties 3.17 SCALANCE X202-2IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 85 3.17 SCALANCE X202-2IRT 3.17.1 SCALANCE X202-2IRT product characteristics Possible attachments The SCALANCE X202-2IRT has two RJ -45 jacks and two BFOC p orts f or the connection of end devices or other network segments.
Product properties 3.17 SCALANCE X202-2IRT SCALANCE X-200 86 Operating Instructions, 12/2011, A5E00349864-19 3.17.2 SCALANCE X202-2IRT TP ports Connector pinout On the SCALANCE X202-2IRT, the TP ports are implemented as RJ-4 5 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.17 SCALANCE X202-2IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 87 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.17 SCALANCE X202-2IRT SCALANCE X-200 88 Operating Instructions, 12/2011, A5E00349864-19 3.17.3 SCALANCE X202-2IRT FO ports Transmission speed The transmission spe ed of the optical Fast Ethernet ports i s 10 0 Mbps. Transmission mode The transmission mode for 100Base- FX is specified in the IEEE 8 02.
Product properties 3.18 SCALANCE X204IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 89 3.18 SCALANCE X204IRT 3.18.1 SCALANCE X204IRT product character istics Possible attachments The SCALANCE X204IRT has four RJ- 45 jacks for connecting end de vices or ot her network segments.
Product properties 3.18 SCALANCE X204IRT SCALANCE X-200 90 Operating Instructions, 12/2011, A5E00349864-19 3.18.2 SCALANCE X204IRT TP ports Connector pinout On the SCALANCE X204IRT , the TP ports are imp lemented as RJ-45 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.18 SCALANCE X204IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 91 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.19 SCALANCE XF204IRT SCALANCE X-200 92 Operating Instructions, 12/2011, A5E00349864-19 3.19 SCALANCE XF204IRT 3.19.1 SCALANCE XF204IRT product characteristics Possible attachments The SCALANCE XF204IRT has four R J-45 jacks for con necting end d evices or other network segments.
Product properties 3.19 SCALANCE XF204IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 93 3.19.2 SCALANCE XF204IRT TP ports Connector pinout On the SCALANCE XF204IRT, the TP ports are implemented as RJ-45 jacks with the MDI-X assignment (Medium Dependent Interf ace Autocrossover) of a netw ork component.
Product properties 3.19 SCALANCE XF204IRT SCALANCE X-200 94 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.20 SCALANCE X204 IRT PRO SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 95 3.20 SCALANCE X204 IRT PRO 3.20.1 SCALANCE X204 IRT PRO p roduct characteristics Possib.
Product properties 3.20 SCALANCE X204 IRT PRO SCALANCE X-200 96 Operating Instructions, 12/2011, A5E00349864-19 3.20.2 SCALANCE X204 IRT PRO TP ports Connector pinout On the SCALANCE X204 IRT PRO, the TP ports are implemented as R J-45 jacks wit h MDI- X assignment (Medium Dependent In terface–Autocros sover) of a ne twork component.
Product properties 3.20 SCALANCE X204 IRT PRO SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 97 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.21 SCALANCE X202-2P IRT PRO SCALANCE X-200 98 Operating Instructions, 12/2011, A5E00349864-19 3.21 SCALANCE X202-2P IRT PRO 3.21.1 SCALANCE X202-2P IRT PRO product characteristics.
Product properties 3.21 SCALANCE X202-2P IRT PRO SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 99 3.21.2 SCALANCE X202-2P IRT PRO TP ports Connector pinout On the SCALANCE X202-2P IRT PRO , the TP ports are implemented a s RJ-45 ports with MDI-X assignment (Medium Dependent Interface–Autocr ossover) of a network component.
Product properties 3.21 SCALANCE X202-2P IRT PRO SCALANCE X-200 100 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.21 SCALANCE X202-2P IRT PRO SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 101 3.21.3 SCALANCE X202-2P IRT PRO FO ports Transmission rate The transmission rate of the optical Fast Ethernet ports is 100 Mbps.
Product properties 3.22 SCALANCE X201-3P IRT PRO SCALANCE X-200 102 Operating Instructions, 12/2011, A5E00349864-19 3.22 SCALANCE X201-3P IRT PRO 3.22.
Product properties 3.22 SCALANCE X201-3P IRT PRO SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 103 3.22.2 SCALANCE X201-3P IRT PRO TP interfaces Connector pinout On the SCALANCE X201-3P IRT PRO , the TP interface is implemente d as RJ-45 ports with MDI-X assignment (Medium Dependen t Interface Crossover) of a ne twork component.
Product properties 3.22 SCALANCE X201-3P IRT PRO SCALANCE X-200 104 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.22 SCALANCE X201-3P IRT PRO SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 105 3.22.3 SCALANCE X201-3P IRT PRO FO interfaces Transmission rate The transmission rate of the optical Fast Ethernet ports is 100 Mbps.
Product properties 3.23 SCALANCE X202-2P IRT SCALANCE X-200 106 Operating Instructions, 12/2011, A5E00349864-19 3.23 SCALANCE X202-2P IRT 3.23.1 SCALANCE X202-2P IRT product characteristics Possible attachments The SCALANCE X202-2P IRT has two RJ-4 5 jacks and two SC RJ interfaces for connecting en d devices or othe r network se gments.
Product properties 3.23 SCALANCE X202-2P IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 107 3.23.2 SCALANCE X202-2P IRT TP ports Connector pinout On the SCALANCE X202-2P IRT, the TP ports are implemented as RJ -45 jacks with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.23 SCALANCE X202-2P IRT SCALANCE X-200 108 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.23 SCALANCE X202-2P IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 109 3.23.3 SCALANCE X202-2P IRT FO ports Transmission rate The transmission rate of the optical Fast Ethernet ports is 100 Mbps.
Product properties 3.24 SCALANCE X201-3P IRT SCALANCE X-200 110 Operating Instructions, 12/2011, A5E00349864-19 3.24 SCALANCE X201-3P IRT 3.24.1 SCALANCE X201-3P IRT product characteristics Possible attachments The SCALANCE X201-3P IRT has an RJ -45 jack and three S C RJ interfaces for connecting end device s or other network segmen ts.
Product properties 3.24 SCALANCE X201-3P IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 111 3.24.2 SCALANCE X201-3P IRT TP ports Connector pinout On the SCALANCE X201-3P IRT, the TP port is implemented as an RJ-45 jack with MDI-X assignment (Medium Dependent Interf ace–Autocrossover) of a netw ork component.
Product properties 3.24 SCALANCE X201-3P IRT SCALANCE X-200 112 Operating Instructions, 12/2011, A5E00349864-19 Autonegotiation Autonegotiation means the automatic detection of the functional ity of the port at the opposite end.
Product properties 3.24 SCALANCE X201-3P IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 113 3.24.3 SCALANCE X201-3P IRT FO ports Transmission rate The transmission rate of the optical Fast Ethernet ports is 100 Mbps.
Product properties 3.25 SCALANCE X200-4P IRT SCALANCE X-200 114 Operating Instructions, 12/2011, A5E00349864-19 3.25 SCALANCE X200-4P IRT 3.25.1 SCALANCE X200-4P IRT product characteristics Possible attachments The SCALANCE X200-4P IRT has four S C RJ interfaces for connecti ng end de vices or other network segments.
Product properties 3.25 SCALANCE X200-4P IRT SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 115 3.25.2 SCALANCE X200-4P IRT FO ports Transmission rate The transmission rate of the optical Fast Ethernet ports is 100 Mbps.
Product properties 3.26 C-PLUG (configuration plug) SCALANCE X-200 116 Operating Instructions, 12/2011, A5E00349864-19 3.26 C-PLUG (configuration plug) Area of application The C-PLUG is an exchangeable m edium for storage of the configu ration and project engineering data of the basic devic e.
Product properties 3.26 C-PLUG (configuration plug) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 117 Note Combinations other than those shown in the table are not comp at ible with each other.
Product properties 3.26 C-PLUG (configuration plug) SCALANCE X-200 118 Operating Instructions, 12/2011, A5E00349864-19 To insert the C-PLUG, remove the sc rew cove r. The C-PL UG is in s erted in the receptacle. The screw cover must then be closed corre ctly.
Product properties 3.27 Button SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 119 3.27 Button Button function You can change variou s device settings with the butto n.
Product properties 3.28 Displays SCALANCE X-200 120 Operating Instructions, 12/2011, A5E00349864-19 3.28 Displays 3.28.1 Fault indicator (red LED) Fault indicator (red LED) If the red LED is lit, the IE Swi tch X-200 has d etected a probl em.
Product properties 3.28 Displays SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 121 1. Link down event on a monitored port. 2. Failure of one of the two redundant pow er supplies. Note The following devices do not have a redundant power suppl y: SCALANCE X204 IRT PRO SCALANCE X202-2P IRT PRO SCALANCE X201-3P IRT PRO 3.
Product properties 3.28 Displays SCALANCE X-200 122 Operating Instructions, 12/2011, A5E00349864-19 Power display The LEDs signal that the IE Switc h X-200 can adopt the followin g statuses: The statu.
Product properties 3.28 Displays SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 123 3.28.3 Port status indicator (green/yellow LEDs) Port status indicator (green/yellow LEDs) The LEDs signal that the IE Switc h X-200 can adopt the followin g statuses.
Product properties 3.28 Displays SCALANCE X-200 124 Operating Instructions, 12/2011, A5E00349864-19 3.28.4 Redundancy manager ind icator (green LED) Redundancy manager indicator (green LED) The LED si.
Product properties 3.28 Displays SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 125 3.28.5 Standby functions (yellow LED) Standby functions (yellow LED) The LED signals that the IE Sw.
Product properties 3.28 Displays SCALANCE X-200 126 Operating Instructions, 12/2011, A5E00349864-19 3. Standby partner lost. 4. Standby function is disabled. Note When the device switches from act ive to passive mode because of a fault, the red fault LED is also activated.
Product properties 3.28 Displays SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 127 FOC diagnostic display (yellow LED) The diagnostic status of the SC R J interfaces is signa led by an additional LED per port.
Product properties 3.28 Displays SCALANCE X-200 128 Operating Instructions, 12/2011, A5E00349864-19.
4 Installation 4.1 Installation Types of installation IE Switches X-200 can b e inst alled in variou s ways: ● Installation on a 35 mm DIN rail ● Installation on a SIMATIC S7-300 standard rail (no.
Installation 4.1 Installation SCALANCE X-200 130 Operating Instructions, 12/2011, A5E00349864-19 WARNING If a SCALANCE X204 IRT PRO SCALANCE X204-2TS SCALANCE X204IRT is operated at ambient temperat ures between 60°C and 70°C, the housing temperatu re may exceed 70°C.
Installation 4.2 Installation on a DIN rail SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 131 4.2 Installation on a DIN rail Installation Install the IE Switch X-200 on a 35 mm DIN rail complying with DIN EN 60715.
Installation 4.3 Installation on a standard rail SCALANCE X-200 132 Operating Instructions, 12/2011, A5E00349864-19 4.3 Installation on a standard rail Installing an IE Switch X-200 on a SIMATIC S7-300 standard rail 1. Place the upper guide at the top of the IE Switch X-200 hou sing in the S7 standard rail.
Installation 4.4 Wall mounting SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 133 4.4 Wall mounting Wall mounting 1. For wall mounting, use suitable mounting fittings for the wall (for example, for a concrete wa ll, four plugs 6 mm diameter and 30 mm long, 4 screws 3.
Installation 4.4 Wall mounting SCALANCE X-200 134 Operating Instructions, 12/2011, A5E00349864-19.
5 Connection 5.1 Power supply Power supply The power supply is co nnected usi ng a 4-pin pl ug-in terminal bl ock. The power supply i s connected over a high resistance with the e nclosure to allow an ungrounded set up. The power supply is non-floating.
Connectio n 5.1 Power supply SCALANCE X-200 136 Operating Instructions, 12/2011, A5E00349864-19 Note The current through the power push -pull connector must not exce ed a maximum of 16 A. You should therefore include a fuse that trips at a current hig her than 16 A.
Connectio n 5.1 Power supply SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 137 Figure 5-1 Mounting position for operation und er marginal condi tions Table 5- 1 Operation under margi.
Connectio n 5.1 Power supply SCALANCE X-200 138 Operating Instructions, 12/2011, A5E00349864-19 Table 5- 2 Pin assignment Pin number Assignment (exceptions: SCALANCE X204 IRT PRO, X202-2P IRT PRO, X201-3P IRT PRO) X204 IRT PRO X202-2P IRT PRO X201-3P IRT PRO Pin 1 L1 +24 VDC X204-2TS : L1 +12 V .
Connectio n 5.1 Power supply SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 139 WARNING IE Switches X-200 are designed for operation with SELV (Safety Extra Low Vo ltage). This means that only safety extra-low v oltages ( SELV) compl ying with IEC950/EN60950/ VDE0805 can be connect ed to t he power suppl y terminals.
Connectio n 5.2 Signaling contact SCALANCE X-200 140 Operating Instructions, 12/2011, A5E00349864-19 5.2 Signaling contact Signaling contact The signaling conta ct (relay cont act ) is a floating switch with whi ch error/fault states can be signaled by breaking the contact.
Connectio n 5.2 Signaling contact SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 141 The signaling contact remai ns a ctivated until the error/fault i s eliminated or until the current status is applied as the new desir ed status usi ng the button.
Connectio n 5.3 Grounding SCALANCE X-200 142 Operating Instructions, 12/2011, A5E00349864-19 5.3 Grounding Installation on a DIN rail The device is grounded over the DI N rail. S7 standard rail The device is grounded over its rear panel and the neck of the screw.
Connectio n 5.4 Fitting the IE FC RJ-45 Plug 180 SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 143 5.4 Fitting the IE FC RJ-45 Plug 180 Assembly of the IE FC RJ-45 Plug 180 on an IE .
Connectio n 5.4 Fitting the IE FC RJ-45 Plug 180 SCALANCE X-200 144 Operating Instructions, 12/2011, A5E00349864-19 Removing the IE FC RJ-45 Plug 180 1.
Connectio n 5.5 Fitting the IE RJ 45 Pl ug Pro and IE SC RJ Plug Pro SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 145 5.5 Fitting the IE RJ 45 Plug Pro and IE SC RJ Plug Pro IE RJ 4.
Connectio n 5.5 Fitting the IE RJ 45 Plug Pro and IE SC RJ Plug Pro SCALANCE X-200 146 Operating Instructions, 12/2011, A5E00349864-19.
Configuration / diagnostics using remote mechanisms 6 6.1 Assignment of an IP address 6.1.1 Introduction Initial assignment of an IP address Note The initial assignment of an IP address for an IE Switch X-200 is not possible wi th Web Based Management because this co nfiguration tool requires that an IP address is already available.
Configuration / diagnostics using remote mechanism s 6.1 Assignment of an IP address SCALANCE X-200 148 Operating Instructions, 12/2011, A5E00349864-19 Downloading the Primary Setup Tool The Primary Setup Tool is avail able on the Internet at: SIEMENS Automation and Drives Service & Support Entry ID 19440762 http://support.
Configuration / diagnostics using remote mechanism s 6.1 Assignment of an IP address SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 149 6.1.2.3 The DLC protocol Checking The Primary Setup Tool uses the DL C protocol for communi cation with the modules.
Configuration / diagnostics using remote mechanism s 6.1 Assignment of an IP address SCALANCE X-200 150 Operating Instructions, 12/2011, A5E00349864-19 6.1.2.4 Installing the DLC protocol Procedure Follow the steps below to install the DLC protocol o n a compute r: 1.
Configuration / diagnostics using remote mechanism s 6.1 Assignment of an IP address SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 151 6.1.2.6 Configuring a module If you click an entry in the lis t, the Primary Setup Tool displ ays information on the selected device in the right-hand pane.
Configuration / diagnostics using remote mechanism s 6.1 Assignment of an IP address SCALANCE X-200 152 Operating Instructions, 12/2011, A5E00349864-19 Figure 6-2 Dialog for configuring a mo dule Downloading configuration data to the module Transfer the configuration data to the device by following the steps outlined b elow: 1.
Configuration / diagnostics using remote mechanism s 6.1 Assignment of an IP address SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 153 tarting Web Based Management mponent) such as the X-200 IE switches ha ve a Web ic e you want to configure with Web Based Manag ement with four blue cords).
Configuration / diagnostics using remote mechanism s 6.1 Assignment of an IP address SCALANCE X-200 154 Operating Instructions, 12/2011, A5E00349864-19 6.1.3 Configuration with DHCP The Dynamic Host Configuration Pr otocol (DHCP) is a protocol th at allows the dynamic configuration of IP addresses and provides additional informati on.
Configuration / diagnostics using remote mechanism s 6.2 Updating the firmware with the boot loader SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 155 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 156 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 157 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 158 Operating Instructions, 12/2011, A5E00349864-19 Starting Web Based Management and logging on 1.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 159 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 160 Operating Instructions, 12/2011, A5E00349864-19 Buttons ● Refresh If you click on this button, curr ent data of the switch is requ ested and displayed.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 161 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 162 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 163 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 164 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 165 You apply your settings wit h Set Values.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 166 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 167 ● NOT PRESENT There is no C-PLUG insert ed in the IE Switch X-200.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 168 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 169 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 170 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 171 Restart S ystem Click this button to restart the IE Switc h X-200.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 172 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 173 Firmware File Name and, if applicable, directory path of the file from which you want to load the new firmware.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 174 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 175 Event Log File By clicking "Save", you can s ave the event table (event log fil e) on the local computer.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 176 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 177 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 178 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 179 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 180 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 181 You can save the event table usin g HTTP or TFTP in the System m enu.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 182 Operating Instructions, 12/2011, A5E00349864-19 6.3.5.12 The "X200" WBM menu Status This page provides information on operat ing states such as powe r suppl y and fault status.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 183 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 184 Operating Instructions, 12/2011, A5E00349864-19 Ring Redundancy Manager Here you can cho ose whether the "active" status of the redunda ncy manager triggers an error.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 185 6.3.5.14 The "X200 Ring" WBM menu "Ring redundancy" In this dialog, you can configure the ports for fast ring redun dancy.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 186 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 187 ● MRP Manager(Auto)/Client If this mode is set, the device a ttempts to adopt the role of " MRP Manager".
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 188 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 190 Operating Instructions, 12/2011, A5E00349864-19 6.3.5.15 The "X200 Standby" WBM menu Standby manager Note Standby fun ctionality is sup ported only by X-200IRT IE switches .
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 192 Operating Instructions, 12/2011, A5E00349864-19 6.3.5.16 The "Agent" WBM menu Agent Configuration This menu item provides you with optio ns for the IP address.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 193 Settings for IE Switches X-200 Agent Enabled Features E-Mail Enables/disables E-mail functionality.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 194 Operating Instructions, 12/2011, A5E00349864-19 Table 6- 15 Agent Confi guration - CLIAGENTIP> Command Description Comment info Displays informati on on the IP settings.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 195 6.3.5.18 The "Agent SNMP Config" WBM menu Note On X-20 0IRT IE switches with firm ware versions V4.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 196 Operating Instructions, 12/2011, A5E00349864-19 Write Community String Displays the user nam e for writ e access to SNMP variables.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 197 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 198 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 200 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 202 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 203 Command Description Comment edit <index> <group> [NONE | MD5 | SHA] [Authpass] [Privpass] Changes the properties of an SNMPv3 user.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 204 Operating Instructions, 12/2011, A5E00349864-19 Group Name Here, you select the SNMPv3 user group to which the user you are creating will be assigned .
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 206 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 207 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 208 Operating Instructions, 12/2011, A5E00349864-19 SMTP Server IP Port The IP port over which the mail is sent.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 209 6.3.5.26 The "Agent Time Config" WBM menu Agent Time Client Configuration This dialog is used to conf igure the time protocols.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 210 Operating Instructions, 12/2011, A5E00349864-19 ● SIMATIC time If you use the SIMATIC time transmitter, you do not need to make any further settings.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 211 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 212 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 213 6.3.5.28 The "Switch Ports" WBM menu Switch Ports This dialog informs you a bout t he current status of the ports.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 214 Operating Instructions, 12/2011, A5E00349864-19 Negotiation Indicates whether autonegotia tion is enabled o r disabled.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 216 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 217 Distance Displays the distance to the cabl e end, cable break, or short-c ircuit.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 218 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 219 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 220 Operating Instructions, 12/2011, A5E00349864-19 The LLDP protocol is used to exchange informatio n between neigh borin g devices.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 221 The following settings can be m ade for the displayed ports: Symbol Meaning Port sends and receives LLDP frames.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 222 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 223 Note If DCP is turned off, it may not be possible to configure all s witches with the PST tool.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 224 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 225 The link power margin indicates the attenuation on the connecti on betwe en sender and receiver that can be overcome.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 226 Operating Instructions, 12/2011, A5E00349864-19 Yellow: If the link power margin enters th is range, maint enance is nece ssary.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 228 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 229 ● "Source Port" display box Shows the port that received the frame that triggered the last reaction.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 230 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 231 Utilization Displays the port utilization as a percentage (%).
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 232 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 233 1024-1518 Displays the number of packets w ith a length of 102 4-1518 bytes .
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 234 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 236 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 237 Indicates the number of collision s that have occurred.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 238 Operating Instructions, 12/2011, A5E00349864-19 6.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 239 As an alternative, you can also d i splay the private MI B directl y in the Web browser.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 240 Operating Instructions, 12/2011, A5E003498.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using We b Based Management (WB M) and Command Line Interface (CLI) SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 241 Variable Access rights Description snX200FaultState Read and write Displays the error status of th e device.
Configuration / diagnostics using remote mechanism s 6.3 Configuration using Web Ba sed M anagement (WBM) and Command Line Interface (CLI) SCALANCE X-200 242 Operating Instructions, 12/2011, A5E003498.
IRT technology with SCALANCE X-200 7 With STEP 7 as of V5.4, you can configure PROFINET devi ces that support data exchan ge over isochronous real-time Ethernet (IRT). IRT fr ames are trans ferred deterministically over planned communication paths in a fixed orde r to achieve the bes t possible synchroni city and performance.
IRT technology with SCALANCE X-200 SCALANCE X-200 244 Operating Instructions, 12/2011, A5E00349864-19 In PROFINET IO with IRT, a sync master generates a signal with which the sync slave s synchronize themselves. The sy nc master and sync slaves belong to a sync domain that is assigned a name during projec t engineering.
8 PROFINET IO functionality 8.1 Configuring with PROFINET IO Using PROFINET IO One option for diagnostics, parameter assignment, and gen eratio n of alarm messages of the connected IE Switch X-20 0 is to use PROFINET IO.
PROFINET IO functionality 8.1 Configuring with PROFINET IO SCALANCE X-200 246 Operating Instructions, 12/2011, A5E00349864-19 Figure 8-1 PN IO set up of the station Including the IE Switch X-200 To include the individual X-200 IE switches a s PN IO devices, t he IE Switch X-200 must exist in the module catalog under PROFINET IO.
PROFINET IO functionality 8.1 Configuring with PROFINET IO SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 247 Linking in a GSDML file If the devices are not yet includ ed in STEP 7, follow the steps below: 1. In the dialog box, select HW Config -> Options "Install GSD Fil es".
PROFINET IO functionality 8.1 Configuring with PROFINET IO SCALANCE X-200 248 Operating Instructions, 12/2011, A5E00349864-19 9. Save and compile the hardware config uration.
PROFINET IO functionality 8.2 Settings in HW Config SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 249 8.2 Settings in HW Config 8.2.1 Configuring alarms Procedure 1. Open the dialog with the general settings. In th is dialog, you will find settings tha t apply to the entire device.
PROFINET IO functionality 8.2 Settings in HW Config SCALANCE X-200 250 Operating Instructions, 12/2011, A5E00349864-19 8.2.2 Configuring MRP Procedure 1. In STEP 7, open the properties d ialog of the PROFINET interface of the switch (double- click on the slot "PN-IO").
PROFINET IO functionality 8.2 Settings in HW Config SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 251 These settings are described below. Note Prioritized startup If you configure MRP in a ring , you cannot use the "prioritized startup" function in PROFINET applications on the devices invol ved.
PROFINET IO functionality 8.2 Settings in HW Config SCALANCE X-200 252 Operating Instructions, 12/2011, A5E00349864-19 ● You want to use MRP in a ring t opology only with Siemens device s and without monitoring diagnostic inte rrupts: Assign all devices to the "default-mrpdomain".
PROFINET IO functionality 8.2 Settings in HW Config SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 253 The following diagnostic int errupts can be generated: ● Wiring or port erro r.
PROFINET IO functionality 8.2 Settings in HW Config SCALANCE X-200 254 Operating Instructions, 12/2011, A5E00349864-19 8.2.3 Configuring the topology Procedure 1. Call the dialog box with port-s pe cific settings. To open the dialog, select the device whose settings you want to chan ge.
PROFINET IO functionality 8.2 Settings in HW Config SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 255 Partners ● Partner port Here you can configure the topol og y that will be monitored.
PROFINET IO functionality 8.3 HSR configuration in PROFI NET IO SCALANCE X-200 256 Operating Instructions, 12/2011, A5E00349864-19 8.3 HSR configuration in PROFINET IO With PROFINET IO, the use of MRP rather than HSR is recommended . HSR cannot be confi gured with STEP 7.
PROFINET IO functionality 8.4 Structure of the data records SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 257 8.4 Structure of the data records Data records 4, 5 and 0x802A The structure of the data reco rds 4, 5 and 0x802A is described below.
PROFINET IO functionality 8.4 Structure of the data records SCALANCE X-200 258 Operating Instructions, 12/2011, A5E00349864-19 Data record 5: Supplies the current alarm setting for this port Access: R.
PROFINET IO functionality 8.4 Structure of the data records SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 259 Data record 0x802A Structure typdef struct{ Word BlockType; Word BlockLe.
PROFINET IO functionality 8.4 Structure of the data records SCALANCE X-200 260 Operating Instructions, 12/2011, A5E00349864-19 SlotNumber Slot designation. SubslotNumber Subslot designation LengthOwnPortID Length of the OwnPortID field in bytes. OwnPortID ID of the port used.
PROFINET IO functionality 8.4 Structure of the data records SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 261 Value (hexadecim al) Meaning 0x00000000 Reserved 0x00000001 – 0x7FFFFFFF Cabl e delay in nanoseconds. PeerMACAddress MAC address of the neighboring devi ce.
PROFINET IO functionality 8.4 Structure of the data records SCALANCE X-200 262 Operating Instructions, 12/2011, A5E00349864-19 MulticastBoundary The individual bits of the DWord variables specify which of the 32 first RT_CLASS_2 multicast addresses (from 01-0E-CF-00-02-00 to 01-0E-CF -00-02-1 F) is blocked.
Approvals and markings 9 Note The sp ecified appro vals apply onl y when the corresponding mark is printed on the product. You can check which of the follo wing approvals have been grante d for your product by the markings on the type plate.
Approvals and markings SCALANCE X-200 264 Operating Instructions, 12/2011, A5E00349864-19 EU declaration of conformity You will find the EC Declaration of Conformity for this product on the Internet at the following address: http://support.automation.
Approvals and markings SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 265 ● Keep to the installation guidelines The product meets the requirement s if you adhere to the install ation and safety instructions contained in this documentation and in th e followi ng documen tation when installing and operating the prod uct.
Approvals and markings SCALANCE X-200 266 Operating Instructions, 12/2011, A5E00349864-19 ● SCALANCE X202-2IRT ● SCALANCE X212-2 ● SCALANCE X206-1 ● SCALANCE XF204-2 ● SCALANCE XF206-1 have .
Approvals and markings SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 267 Report Number E115352 UL Approval for Industrial Control Equipment Underwriters Laborato ries (UL) complying .
Approvals and markings SCALANCE X-200 268 Operating Instructions, 12/2011, A5E00349864-19 Approved for use in Cl. 1, Div. 2, GP. A, B, C, D, T4 A Cl. 1, Zone 2, GP.
Approvals and markings SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 269 Approvals Device type SCALANCE cULus cULus for Hazardous Locations 1 FM 1 C-TICK CE ATEX95 Zone 2 1 E1 XF204 UL 60950 -1 CSA C22.2 No. 60950 -1 UL 1604 and UL 2279 Pt.
Approvals and markings SCALANCE X-200 270 Operating Instructions, 12/2011, A5E00349864-19 Device type SCALANCE cULus cULus for Hazardous Locations 1 FM 1 C-TICK CE ATEX95 Zone 2 1 E1 X204-2TS UL 60950 -1 CSA C22.2 No. 60950-1 ANSI / ISA 12.12.01 CSA C22.
Approvals and markings SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 271 Device type SCALANCE cULus cULus for Hazardous Locations 1 FM 1 C-TICK CE ATEX95 Zone 2 1 E1 X206-1 LD UL 60950-1 CSA C22.2 No. 60950-1 ANSI / ISA 12.12.01 CSA C22.
Approvals and markings SCALANCE X-200 272 Operating Instructions, 12/2011, A5E00349864-19 Device type SCALANCE cULus cULus for Hazardous Locations 1 FM 1 C-TICK CE ATEX95 Zone 2 1 E1 X201-3P IRT PRO UL 60950-1 CSA C22.2 No. 60950-1 ANSI / ISA 12.12.01 CSA C22.
Approvals and markings SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 273 Mechanical stability Device type SCALANCE IEC 60068-2-6 vibration IEC 60068-2-27 shock XF204 5 – 9 Hz: 3.5 mm 9 – 500 Hz: 1 g 1 octave/min, 20 sweeps 15 g, 6 ms duration 6 shocks per axis X208 5 – 9 Hz: 3.
Approvals and markings SCALANCE X-200 274 Operating Instructions, 12/2011, A5E00349864-19 Device type SCALANCE IEC 60068-2-6 vibration IEC 60068-2-27 shock X204 IRT PRO 5 – 9 Hz: 3.5 mm 9 – 150 Hz: 1 g 10 cycles per axis 15 g, 11 ms duration 6 shocks per axis X202-2P IRT PRO 5 – 9 Hz: 3.
Technical specifications 10 Table 10- 1 Construction Type Dime nsions (W x H x D) in mm Weight in g Installation options - DIN rail - S7-300 standard rail - Wall mounting XF204 75 x 125 x 73 250 + No .
Technical specifications SCALANCE X-200 276 Operating Instructions, 12/2011, A5E00349864-19 Table 10- 2 Ports Type Connectors end devices or network components via twisted pair RJ-45 jacks with MDI X .
Technical specifications SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 277 Table 10- 3 Electrical data Device type SCALANCE Power supply 2 x 12 ... 24 VDC (10 ... 30 VDC) SELV (Safety Extra Low Voltage) Power loss at 12 VDC Current consumption at rated voltage Overcurrent protection at input Non-replaceable fuse (F) X204-2TS + 6.
Technical specifications SCALANCE X-200 278 Operating Instructions, 12/2011, A5E00349864-19 Table 10- 4 Optical data Device type SCALANCE Optical transmit power Receiver sensitivity X204-2 X204-2TS XF204-2 X206-1 XF206-1 X212-2 X202-2IRT -19 / -17 / -14 dBm (min.
Technical specifications SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 279 Table 10- 6 Permitted cable lengths (copper) Device type SCALANCE 0 - 55 m IE TP torsion cable with IE FC R.
Technical specifications SCALANCE X-200 280 Operating Instructions, 12/2011, A5E00349864-19 Table 10- 7 Permitted cabl e lengths (fiber-optic) Device type SCALANCE 1 - 50 m 980/1000 plastic optical fiber (POF) 1 - 100 m 200/230 polymer cladded fiber (PCF) 6 dB max.
Technical specifications SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 281 Table 10- 8 MTBF Device type SCALANCE Degree of protection MTBF XF204 IP20 48 years X208 IP30 83 years XF20.
Technical specifications SCALANCE X-200 282 Operating Instructions, 12/2011, A5E00349864-19 Table 10- 10 Permitted ambient cond itions Device type SCALANCE Operating temperature Storage/transport temperature Relative humidity in operation Operating altitude at max.
Technical specifications SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 283 Note Note the mounting position of t he SCALANCE XF- 200 and X204-2TS If a SCALANCE XF-200 or X204-2TS are mounted on a vertical rail , an ambient temperature of maximum +40 °C is permitted.
Technical specifications SCALANCE X-200 284 Operating Instructions, 12/2011, A5E00349864-19.
Accessories 11 Table 11- 1 Order numbers Order number Available for SCALANCE "Industrial Ethernet TP and Fiber Optic Net works" manual 6GK1970-1BA10-0AA0 All IE FC Stripping Tool 6GK1901-1 G.
Accessories SCALANCE X-200 286 Operating Instructions, 12/2011, A5E00349864-19 Order number Available for SCALANCE IE FC RJ-45 Plug 180 pack of 1 6GK1901-1BB10-2AA0 IE FC RJ-45 Plug 180 pack of 10 6GK.
12 References Sources of information and other documentation 1. SIMATIC NET Industrial Twisted Pair and Fibe r-Optic Networks, Order numbers: 6GK1970-1BA10-0AA0 German 6GK1970-1BA10-0AA1 English 6GK1970-1BA10-0AA2 French 6GK1970-1BA10-0AA4 Italian 2.
Referenc es SCALANCE X-200 288 Operating Instructions, 12/2011, A5E00349864-19.
13 Dimension drawings 5 5 50 50 5 115 115 Figure 13-1 Dimension drawing SCALANCE X208, X20 6-1, X204-2, X2 04-2TS, X202-2IRT , X204IRT, X204-2LD, X206-1LD, X202- 2P IRT, X202-4P IRT, X201-3P IRT, X200.
Dimension drawings SCALANCE X-200 290 Operating Instructions, 12/2011, A5E00349864-19 Figure 13-2 Dimension drawing SCALANCE X216, X21 2-2 and X212-2L D.
Dimension drawings SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 291 Figure 13-3 Dimension drawing SCALANCE X224 .
Dimension drawings SCALANCE X-200 292 Operating Instructions, 12/2011, A5E00349864-19 Figure 13-5 SCALANCE X-200 POF Figure 13-6 Dimension drawings of the SCALANCE X204 IRT PRO, SC AL.
Dimension drawings SCALANCE X-200 Operating Instructions, 12/2011, A5E00349864 -19 293 Figure 13-7 SCALANCE XF- 200 dimension drawings.
Dimension drawings SCALANCE X-200 294 Operating Instructions, 12/2011, A5E00349864-19.
Index A ATEX, 14 ATEX95, 5 Autonegotiati on, 37 , 40 , 43 , 46 , 49 , 52 , 56 , 60 , 64 , 68 , 72 , 77 , 82 , 87 , 91 , 94 , 97 , 100 , 104 , 108 , 112 B BFOC socket ST socket, 58 , 62 , 75 Button, 11.
Index SCALANCE X-200 296 Operating Instructions, 12/2011, A5E00349864-19 MDI /MDIX autocrossover function, 60 , 72 , 77 , 87 , 100 , 108 MDI /MDIX autoc rossover function, 60 , 72 , 77 , 87 , 100 , 10.
Ein wichtiger Punkt beim Kauf des Geräts Siemens SCALANCE X-200 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Siemens SCALANCE X-200 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Siemens SCALANCE X-200 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Siemens SCALANCE X-200 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Siemens SCALANCE X-200 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Siemens SCALANCE X-200 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Siemens SCALANCE X-200 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Siemens SCALANCE X-200. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Siemens SCALANCE X-200 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.