Benutzeranleitung / Produktwartung 440 des Produzenten Siemens
Zur Seite of 328
MICROMASTER 440 Parameter List Issue 01/06 User Documentation 6SE6400-5BB00-0BP0.
Available Documentation for the MICROMASTER 440 Getting Started Guide Is for quick commissioning with SDP an d BOP. Operating Instructions Gives information about features of the MICROMASTER 440, Installation, Commissioning, Control modes, Syst em Parameter structure, Troublesh ooting, Specifications and available options of the MICROMASTER 440.
MICROMASTER 440 Parameter List User Documentation Valid for Issue 01/06 Converter Type Software Version MICROMASTER 440 V2.1 Issue 01/06 Block Diagram and Terminals Parameter List Function Diagrams Fa.
Notes Issue 01/06 MICROMASTER 440 Parameter List 4 6SE6400-5BB00-0BP0 Warning Please refer to all Definitions an d Warnings containe d in the Operating Instructions. You will find the Operating Instructions on the Docu CD delivered with your inverter.
Issue 01/06 Table of Contents MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 5 Parameters MICROMASTER 440 This Parameter List must only be use d together with the Operating Instructions o f the MICROMASTER 440. Please pay special attention to the Warnin gs, Cautions, Notices and Notes contained in these manual s.
Table of Contents Issue 01/06 MICROMASTER 440 Parameter List 6 6SE6400-5BB00-0BP0 3.21 Ramp-function generator....................................................................... 131 3.22 Flying restart .............................................
Issue 01/06 Block Diagram and Terminals MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 7 1 Block Diagram and T erminals 1.1 Block Diagram PE 1/3 AC 200 - 240 V 3 AC 380 - 480 V 3 AC 500 - 600 V SI PE L/L1, N/L2 L/L1, N/L2,L3 L1, L2, L3 = 3 ~ PE U,V,W M 12 ADC 1 ADC 2 12 60 Hz 50 Hz A/D A/D +10 V 0 V 0 - 20 mA max .
Block Diagram and Terminals Issue 01/06 MICROMASTER 440 Parameter List 8 6SE6400-5BB00-0BP0 1.2 Power T erminals You can gain access to the mains an d motor terminals by removing the front covers.
Issue 01/06 Block Diagram and Terminals MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 9 Shield connection Mains cable PE Hoisting eyes Mains cable Phase U1/L1, V1/L2, W1/L3 T op adjustment rail Bo.
Block Diagram and Terminals Issue 01/06 MICROMASTER 440 Parameter List 10 6SE6400-5BB00-0BP0 Cable opening for mains conection U1/L1, V1/L2, W1/L3 Shield connection Mains cable PE Hoisting eyes C able.
Issue 01/06 Block Diagram and Terminals MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 11 1.3 Control T erminals Terminal De signation Function 1 - Output +10 V 2 - Output 0 V 3 ADC1+ Analog input .
Parameters Issue 01/06 MICROMASTER 440 Parameter List 12 6SE6400-5BB00-0BP0 2 Parameters 2.1 Introduction to MICROMASTER System Parameters The layout of the parameter description is as follows. 1 Par number 2 Parameter name 9 Min: [index] 3 CStat : 5 Datatype 7 Unit: 10 Def: 4 P-Group: 6 active: 8 Quick Com m: 11 Max: 13 Description: 1.
Issue 01/06 Parameters MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 13 3. CStat Commissioning status of the parameter . Three states are possible: Commissioning C Run U Ready to r un T This indicates when the parameter can b e changed. One, two or all three st ates may be specified.
Parameters Issue 01/06 MICROMASTER 440 Parameter List 14 6SE6400-5BB00-0BP0 13. Description The parameter descriptio n consists of the sections an d contents listed below. Some of these sections and contents are optional an d will be omitted on a case- to-case basis if not applicable.
Issue 01/06 Parameters MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 15 2.2 Quick commissioning (P0010 = 1) The following parameters are ne cessary for quick commissioni ng (P0010 = 1).
Parameters Issue 01/06 MICROMASTER 440 Parameter List 16 6SE6400-5BB00-0BP0 Seven-segment display The seven-segment display is structure d as follows: 1 0 3 2 5 4 7 6 9 8 11 10 13 12 15 14 Segment Bit Segme nt B it The significance of the relevant bits in the display is described in t he status and control word parameters.
Issue 01/06 Parameters MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 17 2.3 Command and Drive Dat aset s - Overview Command Datasets (CDS) ParNo Parameter text 1) P0700[3] Selection of command sou.
Parameters Issue 01/06 MICROMASTER 440 Parameter List 18 6SE6400-5BB00-0BP0 Drive Datasets (DDS) ParNo Parameter text P0005[3] Display selection r0035[3] CO: Act.
Issue 01/06 Parameters MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 19 ParNo Parameter text P1013[3] Fixed frequency 13 P1014[3] Fixed frequency 14 P1015[3] Fixed frequency 15 P1031[3] Setpoint m.
Parameters Issue 01/06 MICROMASTER 440 Parameter List 20 6SE6400-5BB00-0BP0 ParNo Parameter text P1580[3] Efficiency optimization P1582[3] Smooth time for flux setpoint P1596[3] Int. time field weak. controller P1610[3] Continuous torque boost (SLVC) P1611[3] Acc.
Issue 01/06 Parameters MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 21 2.4 Binector Input Parameters ParNo Parameter text P0731[3] BI: Function of digital output 1 P0732[3] BI: Function of digita.
Parameters Issue 01/06 MICROMASTER 440 Parameter List 22 6SE6400-5BB00-0BP0 2.5 Connector Input Parameters ParNo Parameter text P0095[10] CI: Display PZD signals P0771[2] CI: DAC P1070[3] CI: Main set.
Issue 01/06 Parameters MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 23 2.7 Connector Output Parameters ParNo Parameter text r0020 CO: Freq. setpoint before RF G r0021 CO: Act. filtered frequency r0024 CO: Act. filtered output freq. r0025 CO: Act.
Parameters Issue 01/06 MICROMASTER 440 Parameter List 24 6SE6400-5BB00-0BP0 ParNo Parameter text r1597 CO: Outp. field weak. controller r1598 CO: Flux setpoint (total) r1718 CO: Output of Isq controller r1719 CO: Integral output of Isq ctrl. r1723 CO: Output of Isd controller r1724 CO: Integral output of Isd ctrl.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 25 3 Parameter Description Note Level 4 Parameters are not visible with BOP or AOP. 3.1 Common p arameters r0000 Drive display Min: - Datatype: U16 Unit : - Def: - P-Group: ALWAYS Max: - Displays the user selected output as defined in P0005.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 26 6SE6400-5BB00-0BP0 Dependency: The parameters are sub-divided into groups (P-Group) according t o their functionality. This increases the transparency and allows a parame ter to be quickly searched for.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 27 P0010 Commissioning parameter Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: ALWAYS Act i ve : first confirm QuickComm.: No Max: 30 Filters parameters so that only those related to a particular functional group are selected.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 28 6SE6400-5BB00-0BP0 Index: P0013[0] : 1st user parameter P0013[1] : 2nd user parameter P0013[2] : 3rd user parameter P0013[3] : 4th u.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 29 3.2 Diagnosis p arameters r0018 Firmware version Min: - Datatype: Float Unit : - Def: - P-Group: INVERTER Max: - Displays version number of installed firmware.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 30 6SE6400-5BB00-0BP0 r0024 CO: Act. filtered outp ut freq. Min: - Datatype: Float Unit : Hz Def: - P-Group: CONTRO L Max: - Displays actual output frequency. Slip compensation, resonance damping and frequenc y limitation are included.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 31 r0031 CO: Act. filtered torque Min: - Datatype: Float Unit : Nm Def: - P-Group: CONTRO L Max: - Displays electrical torque.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 32 6SE6400-5BB00-0BP0 r0036 CO:Inverter ov erload utilization Min: - Datatype: Float Unit : % Def: - P-Group: INVERTER Max: - Displays inverter overload utilization calculated via I2t model.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 33 P0040 Reset energy consumption meter Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: INVERTER Act i ve : first confirm QuickComm.: No Max: 1 Resets value of parameter r0039 (energy consum ption meter) to zero.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 34 6SE6400-5BB00-0BP0 r0052 CO/BO: Act. status word 1 Min: - Datatype: U16 Unit : - Def: - P-Group: COMMANDS Max: - Displays first active status word of inverter (bit format) and can be used to diagnose inverter status.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 35 t r 0054 Bit 0 0 ON / OF F 1 ON t r 0054 Bit 1 1 Rev ers e 0 t f ac t t r 0052 Bit 0 2 Dr iv e r unning t r 0052 .
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 36 6SE6400-5BB00-0BP0 f t t f OF F ON t ac t f se t 0 1 r 0053 Bit 0 9 Ramping fi nis hed r 0053 Bi t 09 "R ampi ng fi nis hed&quo.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 37 r0056 CO/BO: Status of motor control Min: - Datatype: U16 Unit : - Def: - P-Group: CONTRO L Max: - Displays status of motor control (MM420: V/f status), which can be used to diagnose inverter status.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 38 6SE6400-5BB00-0BP0 r0064 CO: Dev. frequency controller Min: - Datatype: Float Unit : Hz Def: - P-Group: CONTRO L Max: - Displays actual deviation of speed controller. This value is calculated from the frequency setpoint (r0062) and the actual frequency (r0063).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 39 r0070 CO: Act. DC-link voltage Min: - Datatype: Float Unit : V Def: - P-Group: INVERTER Max: - Displays (unfiltered) DC-link voltage.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 40 6SE6400-5BB00-0BP0 r0075 CO: Current setp oint Isd Min: - Datatype: Float Unit : A Def: - P-Group: CONTRO L Max: - Displays setpoint of flux generating current component.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 41 P0095[10] CI: Display PZD signals Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: CONTRO L Act i ve : first confirm QuickComm.: No Max: 4000:0 Selects source of display for PZD signals.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 42 6SE6400-5BB00-0BP0 3.3 Inverter p arameters (HW) P0100 Europe / North America Min: 0 CStat: C Datatype: U16 Unit : - Def: 0 P-Group: QUICK Act i ve: first confirm QuickComm.: Yes Max: 2 Determines whether power settings (e.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 43 r0200 Act. power stack code number Min: - Datatype: U32 Unit : - Def: - P-Group: INVERTER Max: - Identifies hardware variant as shown in table below.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 44 6SE6400-5BB00-0BP0 Code- No . MM440 MLF B Input Vol tage & F r equency CT Powe r kW VT Pow e r kW Inter nal Fi l t er Fram e Siz e 94 6SE 6440- 2A D 25- 5C A x 3A C 380- 4 80V +10% - 10% 47- 63H z 5,5 7,5 C l.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 45 r0204 Power stack features Min: - Datatype: U32 Unit : - Def: - P-Group: INVERTER Max: - Displays hardware features of power stack.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 46 6SE6400-5BB00-0BP0 It is recommended to modify P0205 first. Afterwards motor paramet er may be adapted.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 47 r0209 Maximum inverter current Min: - Datatype: Float Unit : A Def: - P-Group: INVERTER Max: - Displays maximum output current of inverter.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 48 6SE6400-5BB00-0BP0 P0290 Inverter overload reaction Min: 0 CStat: CT Datatype: U16 Unit : - Def: 2 P-Group: INVERTER Act i ve : first confirm QuickComm.: No Max: 3 Selects reaction of inverter to an internal over-temperature.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 49 P0292 Inverter temperature w arning Min: 0 CStat: CUT Datatype: U16 Unit : °C Def: 5 P-Group: INVERTER Act i ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 50 6SE6400-5BB00-0BP0 3.4 Motor p a rameters P0300[3] Select motor ty pe Min: 1 CStat: C Datatype: U16 Unit : - Def: 1 P-Group: MOTOR Act i ve : first confirm QuickComm.: Yes Max: 2 Selects motor type.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 51 P0304[3] Rated motor voltage Min: 10 CStat: C Datatype: U16 Unit : V Def: 230 P-Group: MOTOR Act i ve : first confirm QuickComm.: Yes Max: 2000 Nominal motor voltage [V] from rating plate.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 52 6SE6400-5BB00-0BP0 NEMA Mo t o r T 1 T 4 T 7 T 3 T 6 T 9 T 8 T 5 T 2 Vol t s UV W T 1 -T 7 T 2 -T 8 T 3 -T 9 low T 4 -T 5 -T 6 T 1 T.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 53 P0308[3] Rated motor cosPhi Min: 0.000 CStat: C Datatype: Float Unit : - Def: 0.000 P-Group: MOTOR Act i ve : first confirm QuickComm.: Yes Max: 1.000 Nominal motor power factor (cosPhi) from rating plate - see diagra m P0304.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 54 6SE6400-5BB00-0BP0 r0313[3] Motor pole pairs Min: - Datatype: U16 Unit : - Def: - P-Group: MOTOR Max: - Displays number of motor pole pairs that the inverter is currentl y using for internal calculations.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 55 r0332[3] Rated power factor Min: - Datatype: Float Unit : - Def: - P-Group: MOTOR Max: - Displays power factor for motor Index: r0332[0] : 1st. Drive data set (DDS) r0332[1] : 2nd.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 56 6SE6400-5BB00-0BP0 P0340[3] Calculation of motor par ameters Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: MOTOR Act i ve : first confirm QuickComm.: No Max: 4 Calculates various motor parameters (see table below).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 57 P0341[ 3] Motor inert ia [k g*m^2] P0344[ 3] Motor w eight P1521[ 3] CO: Lower tor que l imi t P1531[ 3] Regener .
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 58 6SE6400-5BB00-0BP0 P0341[3] Motor inertia [kg*m^2] Min: 0.00010 CStat: CUT Datatype: Float Unit : - Def: 0.00180 P-Group: MOTOR Act i ve : Immedia tely QuickComm. : No Max: 1000.00000 Sets no-load inertia of motor.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 59 P0347[3] Demagnetization time Min: 0.000 CStat: CUT Datatype: Float Unit : s Def: 1.000 P-Group: MOTOR Act i ve : Immedia tely QuickComm. : No Max: 20.000 Defines the de-magnetization time for the connected induction motor.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 60 6SE6400-5BB00-0BP0 P0352[3] Cable resistance Min: 0.0 CStat: CUT Datatype: Float Unit : Ohm Def: 0.0 P-Group: MOTOR Act i ve : Immedia tely QuickComm. : No Max: 120.0 Describes cable resistance between inverter and motor for one phase.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 61 P0360[3] Main inductance Min: 0.0 CStat: CUT Datatype: Float Unit : - Def: 10.0 P-Group: MOTOR Act i ve : Immedia tely QuickComm. : No Max: 3000.0 Sets main inductance [mH] of the motor equivalent circuit (phase value), see diagram below.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 62 6SE6400-5BB00-0BP0 Co n versio n : T - eq u ivalen t curcu it -- > L L 1 k m R R σ σ + = k L L R m m σ Γ = k R R 2 R R R σ Γ = k L L L R R S σ σ σ σ + = Co n versio n : L L 0.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 63 P0364[3] Magnetizing curv e flux 3 Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 115.0 P-Group: MOTOR Act i ve : Immedia tely QuickComm. : No Max: 300.0 Specifies third flux value of saturation characteristic in [%] relative to rated motor voltage (P0304).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 64 6SE6400-5BB00-0BP0 P0369[3] Magnetizing curv e imag 4 Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 170.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 65 r0374[3] Rotor resistance [%] Min: - Datatype: Float Unit : % Def: - P-Group: MOTOR Max: - Displays the rotor resistance of the motor equivalent circuit diagram (phase value) as a [%] at the ambient temperature (in the cold state).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 66 6SE6400-5BB00-0BP0 r0384[3] Rotor time constant Min: - Datatype: Float Unit : ms Def: - P-Group: MOTOR Max: - Displays calculated rotor time constant [ms]. Index: r0384[0] : 1st. Drive data set (DDS) r0384[1] : 2nd.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 67 3.5 S peed encoder P0400[3] Select encoder ty pe Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: ENCODER Acti ve : Immediately QuickCo mm.: No Max: 2 Selects encoder type (number of encoder channels).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 68 6SE6400-5BB00-0BP0 r0403 CO/BO: Encoder status word Min: - Datatype: U16 Unit : - Def: - P-Group: COMMANDS Max: - Displays status word of encoder (in bit format). Bitfields: Bit00 Encoder module active 0 NO 1 YES Bit01 Encoder error 0 NO 1 YES Bit02 Signal o.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 69 Note: The value of P0492 should be approx. 2x rated slip, if the motor po wer is less (<=) 90 kW The value of P0492 should be approx.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 70 6SE6400-5BB00-0BP0 r 0631 AD C 5 V Si gnal loss detec tion T 1 = 4 s 2 1 No sens or PT C KT Y 0 P 0604 F ault F 0015 & P0601 = 2 T her mal motor mode l r 0633 r 0632 r 0035 1 ≥ Motor temp .
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 71 End temperatur e Ins ulati on cl ass Y A E B F 90 °C 105 °C 120 °C 130 °C 155 °C H 180 °C Ex tract o f IE C 85 The motor overheating disturbance threshold is automatically set by the inverter at 10% higher than th e temperature declared in parameter P0604.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 72 6SE6400-5BB00-0BP0 P0625[3] Ambient motor temperatu re Min: -40.0 CStat: CUT Datatype: Float Unit : °C Def: 20.0 P-Group: MOTOR Act i ve : Immedia tely QuickComm. : No Max: 80.0 Ambient temperature of motor.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 73 P0627[3] Overtemperature stator w inding Min: 20.0 CStat: CUT Datatype: Float Unit : °C Def: 80.0 P-Group: MOTOR Act i ve : Immedia tely QuickComm. : No Max: 200.0 Overtemperature of the stator winding.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 74 6SE6400-5BB00-0BP0 r0633[3] CO: Rotor winding temperature Min: - Datatype: Float Unit : °C Def: - P-Group: MOTOR Max: - Displays rotor winding temperature of motor mass model. Index: r0633[0] : 1st.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 75 3.8 Command source P0700[3] Selection of command source Min: 0 CStat: CT Datatype: U16 Unit : - Def: 2 P-Group: COMMANDS Act i ve : first confirm QuickComm.: Yes Max: 6 Selects digital command source.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 76 6SE6400-5BB00-0BP0 P0840 722.0 19.0 722.0 2032.0 2036.0 2090.0 P0842 0.0 0.0 0.0 0.0 0.0 0.0 P0844 1.0 19.1 1.0 2032.1 2036.1 2090.1 P0845 19.1 19.1 19.1 19.1 19.1 19.1 P0848 1.0 1.0 1.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 77 3.9 Digit a l input s P0701[3] Function of digital input 1 Min: 0 CStat: CT Datatype: U16 Unit : - Def: 1 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 99 Selects function of digital input 1.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 78 6SE6400-5BB00-0BP0 P0702[3] Function of digital input 2 Min: 0 CStat: CT Datatype: U16 Unit : - Def: 12 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 99 Selects function of digital input 2.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 79 P0704[3] Function of digital input 4 Min: 0 CStat: CT Datatype: U16 Unit : - Def: 15 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 99 Selects function of digital input 4.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 80 6SE6400-5BB00-0BP0 P0706[3] Function of digital input 6 Min: 0 CStat: CT Datatype: U16 Unit : - Def: 15 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 99 Selects function of digital input 6.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 81 P0708[3] Function of digital input 8 Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: COMMANDS Act i ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 82 6SE6400-5BB00-0BP0 Index: P0719[0] : 1st. Command data set (CDS) P0719[1] : 2nd. Command data set (CDS ) P0719[2] : 3rd.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 83 P0724 Debounce time for digital inputs Min: 0 CStat: CT Datatype: U16 Unit : - Def: 3 P-Group: COMMANDS Act i ve : Immedia tely QuickComm. : No Max: 3 Defines debounce time (filtering time) used for digital inputs.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 84 6SE6400-5BB00-0BP0 3.10 Digit a l outputs r0730 Number of digital outputs Min: - Datatype: U16 Unit : - Def: - P-Group: COMMANDS Max: - Displays number of digital outputs (relays).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 85 P0732[3] BI: Function of digital output 2 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 52:7 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines source of digital output 2.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 86 6SE6400-5BB00-0BP0 r0747 CO/BO: State of digital outputs Min: - Datatype: U16 Unit : - Def: - P-Group: COMMANDS Max: - Displays status of digital outputs (also includes inversion of digital outputs via P0748).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 87 r0752[2] Act. input of ADC [V] or [mA] Min: - Datatype: Float Unit : - Def: - P-Group: TERMINAL Max: - Displays smoothed analog input value in volts before the characteristic block.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 88 6SE6400-5BB00-0BP0 r0755[2] CO: Act. ADC after scal. [4000h] Min: - Datatype: I16 Unit : - Def: - P-Group: TERMINAL Max: - Displays analog input, scaled using ASPmin and ASPmax. Analog setpoint (ASP) from the analog scaling block can vary from min.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 89 AD C 1 A DC2 O F F = [V ], 0 - 10 V O N = [A ], 0 - 20 mA 12 34 5 6 789 O F F = [V ], 0 - 10 V O N = [A ], 0 - 20.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 90 6SE6400-5BB00-0BP0 ASPma x 100 % 10 V V x 100 % % P0760 P0758 P 0757 P0759 P 0756 = 4, P0761 = 0 ASPmin - 10 V 4000 h Index: P0757[0.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 91 P0759[2] Value x2 of ADC scaling [V / mA] Min: -20 CStat: CUT Datatype: Float Unit : - Def: 10 P-Group: TERMINAL Ac ti ve : first confirm QuickComm.: No Max: 20 Sets value of X2 as described in P0757 (ADC scaling).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 92 6SE6400-5BB00-0BP0 ASPmax 100 % 10 V 20 mA V mA x 100 % % P 0760 P 0758 P0757 P0759 ASPm in P0761 4000 h P0761 > 0 an d P 0758 < 0 < P 07 60 The below example produces a -10 to +10 V analog input (-5 0 to +50 Hz) with center zero and a "ho lding point" 0.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 93 3.12 Analog outputs r0770 Number of DACs Min: - Datatype: U16 Unit : - Def: - P-Group: TERMINAL Max: - Displays number of analog outputs available.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 94 6SE6400-5BB00-0BP0 P0776[2] Type of DAC Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: TERMINAL Ac ti ve : first confirm QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 95 Note: The DAC-linear characteristic is described by 4 coordinates, based on a two-point equation: 0777 P 07 79 P .
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 96 6SE6400-5BB00-0BP0 P0781[2] Width of DAC deadband Min: 0 CStat: CUT Datatype: Float Unit : - Def: 0 P-Group: TERMINAL Ac ti ve : first confirm QuickComm.: No Max: 20 Sets width of dead-band in [mA] for analog output.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 97 3.13 Parameter / command / drive dat a set P0800[3] BI: Do wnload parameter set 0 Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 98 6SE6400-5BB00-0BP0 P0809[3] Copy command data se t (CDS) Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 2 Calls "copy Command Data Set (CDS)" function.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 99 The actual active command data set (CDS) is displayed in parameter r005 0. r 0055 Bit 15 r 0054 Bit 1 5 1. CDS 0 0 2. CDS 0 1 3. CDS 1 0 3. CDS 1 1 r 0050 0 1 2 2 se le ct e d CDS ac tiv e CDS Common Settings: 722.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 100 6SE6400-5BB00-0BP0 P0819[3] Copy driv e data set (DDS) Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 2 Calls "Copy Drive Data Set (DDS)" function.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 101 The actual active drive data set (DDS) is displayed in parameter r0051[1]. r 0055 Bit 0 5 r 0055 Bit 04 1. DDS 0 0 2. DDS 0 1 3. DDS 1 0 3. DDS 1 1 r 0051 [0] 0 1 2 2 r 0051 [ 1] 0 1 2 2 se le c t e d DDS ac tiv e DDS Common Settings: 722.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 102 6SE6400-5BB00-0BP0 P0821 BI: DDS bit 1 Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4095:0 Selects command source from which Bit 1 for selecting a drive data set is to be read in (see parameter P0820).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 103 P0842[3] BI: ON rev erse/OFF1 Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Allows ON/OFF1 reverse command source to be selected using BICO.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 104 6SE6400-5BB00-0BP0 P0845[3] BI: 2. OFF2 Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 19:1 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines second source of OFF2.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 105 P0849[3] BI: 2. OFF3 Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 1:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines second source of OFF3.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 106 6SE6400-5BB00-0BP0 P0927 Parameter changeable via Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 15 P-Group: COMM Acti ve : first confirm QuickComm.: No Max: 15 Specifies the interfaces which can be used to change parameters.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 107 r0948[12] CO: Fault time Min: - Datatype: U16 Unit : - Def: - P-Group: ALARMS Max: - Time stamp to indicate when the fault has occurred.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 108 6SE6400-5BB00-0BP0 P0952 Total number of faults Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: ALARMS Act i ve : first confirm Quick Comm.: No Max: 8 Displays number of faults stored in r0947 (last fault code).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 109 r0968 Status w ord 1 Min: - Datatype: U16 Unit : - Def: - P-Group: COMM Max: - Displays active status word of inverter (in binary) and can be used to diagnose which commands are active.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 110 6SE6400-5BB00-0BP0 3.16 Setpoint source P1000[3] Selection of frequency s etpoint Min: 0 CStat: CT Datatype: U16 Unit : - Def: 2 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 111 Index: P1000[0] : 1st. Command data set (CDS) P1000[1] : 2nd. Command data set (CDS ) P1000[2] : 3rd. Command data set (CDS) Example: Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the motor potentiometer.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 112 6SE6400-5BB00-0BP0 P1000 = xy y = 0 y = 1 y = 2 y = 3 y = 4 y = 5 y = 6 y = 7 0.0 1050.0 755.0 1024.0 2015.1 2018.1 2050. 1 755.1 P1070 1.0 1.0 1.0 1.0 1. 0 1.0 1.0 1. 0 P1071 0.0 0.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 113 3.17 Fixed frequencies P1001[3] Fixed frequency 1 Min: -650.00 CStat: CUT Datatype: Float Unit : Hz Def: 0.00 P-Group: SETPOINT Ac ti ve : Immediately Quick Comm.: No Max: 650.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 114 6SE6400-5BB00-0BP0 Direct selection of FF P1001 via DIN 1: P 1 0 1 6 P 0701 = 15 or P0701 = 99, P1020 = 722 .0, P1016 = 1 DIN1 r 1024 r 0722 .0 P1020 1 2, 3 P1001 0 0 P 0702 = 15 or P0702 = 99, P1021 = 722 .
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 115 P1006[3] Fixed frequency 6 Min: -650.00 CStat: CUT Datatype: Float Unit : Hz Def: 25.00 P-Group: SETPOINT Ac ti ve : Immediately Quick Comm.: No Max: 650.00 Defines fixed frequency setpoint 6.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 116 6SE6400-5BB00-0BP0 P1012[3] Fixed frequency 12 Min: -650.00 CStat: CUT Datatype: Float Unit : Hz Def: 55.00 P-Group: SETPOINT Ac ti ve : Immediately Quick Comm.: No Max: 650.00 Defines fixed frequency setpoint 12.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 117 P1017[3] Fixed frequency mode - Bit 1 Min: 1 CStat: CT Datatype: U16 Unit : - Def: 1 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: No Max: 3 Fixed frequencies can be selected in three different modes.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 118 6SE6400-5BB00-0BP0 P1021[3] BI: Fixed freq. selection Bit 1 Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines origin of fixed frequency selection.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 119 P1027[3] Fixed frequency mode - Bit 5 Min: 1 CStat: CT Datatype: U16 Unit : - Def: 1 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 120 6SE6400-5BB00-0BP0 3.18 Motorized potentiometer (MOP) P1031[3] Setpoint memory of the MOP Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: SETPOINT Ac ti ve : Immediately Quick Comm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 121 P1040[3] Setpoint of the MOP Min: -650.00 CStat: CUT Datatype: Float Unit : Hz Def: 5.00 P-Group: SETPOINT Ac ti ve : Immediately Quick Comm.: No Max: 650.00 Determines setpoint for motor potentiometer control (P1000 = 1).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 122 6SE6400-5BB00-0BP0 3.19 JOG P1055[3] BI: Enable JOG right Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines source of JOG right.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 123 P1058[3] JOG frequen cy right Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 5.00 P-Group: SETPOINT Ac ti ve : Immediately Quick Comm.: No Max: 650.00 Jogging increases the motor frequency by small amounts.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 124 6SE6400-5BB00-0BP0 P1060[3] JOG ramp-up time Min: 0.00 CStat: CUT Datatype: Float Unit : s Def: 10.00 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: No Max: 650.00 Sets jog ramp-up time.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 125 3.20 Setpoint channel P1070[3] CI: Main setpoint Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 755:0 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: No Max: 4000:0 Defines source of main setpoint.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 126 6SE6400-5BB00-0BP0 P1076[3] CI: Additional setpoin t scaling Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 1:0 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: No Max: 4000:0 Defines source of scaling for additional setpoint (to be added to main setpoint).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 127 P1080[3] Min. frequency Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 0.00 P-Group: SETPOINT Ac ti ve : Immediately Quick Comm.: Yes Max: 650.00 Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 128 6SE6400-5BB00-0BP0 P1082[3] Max. frequency Min: 0.00 CStat: CT Datatype: Float Unit : Hz Def: 50.00 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: Yes Max: 650.00 Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequ ency setpoint.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 129 r1084 Resultant max. frequenc y Min: - Datatype: Float Unit : Hz Def: - P-Group: CONTRO L Max: - Displays resultant maximum frequency. P1300 < 20 P1800 ≤ 6 k H z → 650.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 130 6SE6400-5BB00-0BP0 P1094[3] Skip frequency 4 Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 0.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 131 P1113[3] BI: Reverse Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 722:1 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines source of reverse command.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 132 6SE6400-5BB00-0BP0 P1121[3] Ramp-down time Min: 0.00 CStat: CUT Datatype: Float Unit : s Def: 10.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 133 P1130[3] Ramp-up initial rounding time Min: 0.00 CStat: CUT Datatype: Float Unit : s Def: 0.00 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: No Max: 40.00 Defines initial rounding time in seconds as shown on the diagram below.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 134 6SE6400-5BB00-0BP0 P1133[3] Ramp-do w n final rounding time Min: 0.00 CStat: CUT Datatype: Float Unit : s Def: 0.00 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: No Max: 40.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 135 P1135[3] OFF3 ramp-do w n time Min: 0.00 CStat: CUT Datatype: Float Unit : s Def: 5.00 P-Group: SETPOINT Ac ti ve : first confirm QuickComm.: Yes Max: 650.00 Defines ramp-down time from maximum frequenc y to standstill for OFF3 command.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 136 6SE6400-5BB00-0BP0 3.22 Flying rest art P1200 Flying start Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: FUNC Act i ve : first confirm QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 137 P1202[3] Motor-curre nt: Flying start Min: 10 CStat: CUT Datatype: U16 Unit : % Def: 100 P-Group: FUNC Act i ve : first confirm QuickComm.: No Max: 200 Defines search current used for flying start.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 138 6SE6400-5BB00-0BP0 r1204 Status word: Flyi ng start V/f Min: - Datatype: U16 Unit : - Def: - P-Group: FUNC Max: - Bit parameter for checking and monitoring states during search, if V/f control mode is selected (see P1300).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 139 3.23 Automatic restart P1210 Automatic restart Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 1 P-Group: FUNC Act i ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 140 6SE6400-5BB00-0BP0 0 −−−−− 1 −− 2 + −−− 3 ++++ 4 ++ −− − 5 + − ++ 6 ++++ + F ault ac knowl . F ault ac knowl . F ault ac knowl . F ault ac knowl . F ault ac knowl .
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 141 3.24 Motor holding brake P1215 Holding brake enable Min: 0 CStat: T Datatype: U16 Unit : - Def: 0 P-Group: FUNC Act i ve : first confirm QuickComm.: No Max: 1 Enables/disables holding brake function.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 142 6SE6400-5BB00-0BP0 Caution: 1. To activate the motor holding brake, in addition to parameter P1215 = 1, the status signal r0052 bit 12 "motor holding brake active" must be output via a digital output.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 143 3.25 DC braking P1230[3] BI: Enable DC braking Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Enables DC braking via a signal applied from an external source.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 144 6SE6400-5BB00-0BP0 P1232[3] DC braking current Min: 0 CStat: CUT Datatype: U16 Unit : % Def: 100 P-Group: FUNC Act i ve : Immedia tely QuickComm. : No Max: 250 Defines level of DC current in [%] relative to rated motor current (P 0305).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 145 Index: P1233[0] : 1st. Drive data set (DDS) P1233[1] : 2nd. Drive data set (DDS) P1233[2] : 3rd. Drive data set (DDS) Value: P1233 = 0.00 : Not active following OFF1 / OFF3.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 146 6SE6400-5BB00-0BP0 3.26 Compound braking P1236[3] Compound braking curr ent Min: 0 CStat: CUT Datatype: U16 Unit : % Def: 0 P-Group: FUNC Act i ve : Immedia tely QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 147 3.27 Dynamic braking P1237 Dynamic braking Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: FUNC Act i ve : Immedia tely QuickComm. : No Max: 5 Dynamic braking absorbs the braking energy.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 148 6SE6400-5BB00-0BP0 t V DC t V D C , C hopper V DC, a ct Chopper ac tiv e t t C hopper , ON C hopper t f 1 = C hopper Hz 2000 1 = t .
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 149 Caution: If P1245 increased too much, it may interfere with the drive normal operation. Note: Vdc max controller automatically increases ramp-down times to keep the DC-link voltage (r0026) withi n limits (r1242).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 150 6SE6400-5BB00-0BP0 P1245[3] Switch on lev el kin. buffering Min: 65 CStat: CUT Datatype: U16 Unit : % Def: 76 P-Group: FUNC Act i ve : Immedia tely QuickComm. : No Max: 115 Enter switch-on level for kinetic buffering (KIB) in [%] relative to supply voltage (P0210).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 151 P1253[3] Vdc-controll er output limitation Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 10.00 P-Group: FUNC Act i ve : Immedia tely QuickComm. : No Max: 600.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 152 6SE6400-5BB00-0BP0 P1256 = 1: Maintain dclink voltage until mains is returned or drive is tripped undervoltage or pulses disabled when frequency falls below the limit in P1257.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 153 3.29 Control mode P1300[3] Control mode Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: CONTRO L Act i ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 154 6SE6400-5BB00-0BP0 P1300 = 19 : V/f control with independent voltage setpoint The following table presents an overview of control parameters (V/f) that can be modif y in relationship to P1300 dependencies: ParNo.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 155 Vector Control (VC): - P1460: P gain - P1462: I term The following table presents an overview of control paramet.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 156 6SE6400-5BB00-0BP0 3.29.1 V/f control technique P1310[3] Continuous boost Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 50.0 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 250.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 157 Dependency: Continous boost P1310 has no effect during vector operation becaus e the inverter calculates continously the optimum operating conditions. Note: - Increasing the boost levels increases motor heating (especially at standstill).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 158 6SE6400-5BB00-0BP0 P1312[3] Starting boost Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 0.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 159 P1316[3] Boost end frequen cy Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 20.0 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 100.0 Defines point at which programmed boost reaches 50 % of its value.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 160 6SE6400-5BB00-0BP0 P1321[3] Programmable V/f volt. coord. 1 Min: 0.0 CStat: CUT Datatype: Float Unit : V Def: 0.0 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 3000.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 161 P1333[3] Start frequency for FCC Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 10.0 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 100.0 Defines the FCC starting frequency as a percent age of the rated motor freq uency (P0310).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 162 6SE6400-5BB00-0BP0 3.29.1.1 Slip compensation P1335[3] Slip compensation Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 0.0 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 600.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 163 P1336[3] Slip limit Min: 0 CStat: CUT Datatype: U16 Unit : % Def: 250 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 600 Compensation slip limit in [%] relative to r0330 (rated motor slip), which is added to frequenc y setpoint.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 164 6SE6400-5BB00-0BP0 3.29.1.3 Imax controller P1340[3] Imax freq. controller prop. gain Min: 0.000 CStat: CUT Datatype: Float Unit : - Def: 0.000 P-Group: CONTRO L Act i ve : Immedia tely QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 165 r1343 CO: Imax controller freq. output Min: - Datatype: Float Unit : Hz Def: - P-Group: CONTRO L Max: - Displays effective frequency limitation. Dependency: If I_max controller not in operation, parameter norm ally shows max.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 166 6SE6400-5BB00-0BP0 3.29.1.4 Soft starting P1350[3] Voltage soft start Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: CONTRO L Act i ve : first confirm QuickComm.: No Max: 1 Selecting the soft starting function.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 167 3.29.2 Field-orientated vector control P1400[3] Configuration of speed c ontrol Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 1 P-Group: CONTRO L Act i ve : Immedia tely QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 168 6SE6400-5BB00-0BP0 3.29.2.1 Speed controller with/w ithout encoder P1442[3] Filter time for act. speed Min: 0 CStat: CUT Datatype: U16 Unit : ms Def: 4 P-Group: CONTRO L Act i ve : Immedia tely QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 169 P1470[3] Gain speed controller (SLVC) Min: 0.0 CStat: CUT Datatype: Float Unit : - Def: 3.0 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 2000.0 Enters gain of speed controller for sensorless vector control (SLVC).
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 170 6SE6400-5BB00-0BP0 r1482 CO: Integral output of n -ctrl. Min: - Datatype: Float Unit : Nm Def: - P-Group: CONTRO L Max: - Displays integral part of speed controller output.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 171 P1489[3] Droop scaling Min: 0.00 CStat: CUT Datatype: Float Unit : - Def: 0.05 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 0.50 Defines amount of droop in per unit at full load in [%].
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 172 6SE6400-5BB00-0BP0 3.29.2.3 Speed controller pre-control P1496[3] Scaling accel. precontrol Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 0.0 P-Group: CONTRO L Act i ve : Immedia tely QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 173 3.29.2.4 Torque control P1500[3] Selection of torque setpo int Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: CONTRO L Act i ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 174 6SE6400-5BB00-0BP0 Caution: Be aware, by changing of parameter P1500 all BICO pa rameters (see table below) are modified. Note: Changing this parameter sets (to default) all settings on item selected (see table).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 175 P1501[3] BI: Change to torque c ontrol Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: CONTRO L Act i ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 176 6SE6400-5BB00-0BP0 P1503[3] CI: Torque setpoin t Min: 0:0 CStat: T Datatype: U32 Unit : - Def: 0:0 P-Group: CONTRO L Act i ve : first confirm QuickComm.: No Max: 4000:0 Selects source of torque setpoint for torque control.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 177 3.29.2.6 Torque / power limiting P1521[3] CO: Lo w er torque limit Min: -99999.00 CStat: CUT Datatype: Float Unit : Nm Def: -5.13 P-Group: CONTRO L Act i ve : Immedia tely QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 178 6SE6400-5BB00-0BP0 r1527 CO: Lower torque limitation Min: - Datatype: Float Unit : Nm Def: - P-Group: CONTRO L Max: - Displays actual lower torque limitation. Details: See parameter r1526.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 179 r1538 CO: Upper torque limit (total) Min: - Datatype: Float Unit : Nm Def: - P-Group: CONTRO L Max: - Displays total upper torque limitation. P1530 M otor ing pow er lim Cur r ent c ontr oll er Speed c ontr ol ler or T or que controll er CO : L o we r tr q .
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 180 6SE6400-5BB00-0BP0 P1574[3] Dynamic voltage headroom Min: 0 CStat: CUT Datatype: U16 Unit : V Def: 10 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 150 Sets dynamic voltage headroom for vector control.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 181 P1582[3] Smooth time for flux setp oint Min: 4 CStat: CUT Datatype: U16 Unit : ms Def: 15 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 500 Sets time constant of PT1 filter to smooth flux setpoint.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 182 6SE6400-5BB00-0BP0 P1611[3] Acc. torque boost (SLVC) Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 0.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 183 r1725 CO: Integral limit of Isd ctrl. Min: - Datatype: Float Unit : V Def: - P-Group: CONTRO L Max: - Displays limit of integral output voltage setpoint of Isd current controller.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 184 6SE6400-5BB00-0BP0 SLVC open loop means that the speed controller does not get an y frequency feedback from the obse rver model.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 185 P1755[3] Start-freq. motor model (SLVC) Min: 0.1 CStat: CUT Datatype: Float Unit : Hz Def: 5.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 186 6SE6400-5BB00-0BP0 P1764[3] Kp of n-adaption (SLVC) Min: 0.0 CStat: CUT Datatype: Float Unit : - Def: 0.2 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 2.5 Enters gain of speed adaptation controller for sensorless vector control.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 187 P1781[3] Tn of Rs-ada ption Min: 10 CStat: CUT Datatype: U16 Unit : ms Def: 100 P-Group: CONTRO L Act i ve : Immedia tely QuickComm. : No Max: 2000 Enters Rs-adaptation controller integral time.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 188 6SE6400-5BB00-0BP0 3.30 Inverter p arameters (Modulator) P1800 Pulse frequency Min: 2 CStat: CUT Datatype: U16 Unit : kHz Def: 4 P-Group: INVERTER Act i ve : Immediately QuickCo mm.: No Max: 16 Sets pulse frequency of power switches in inverter.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 189 P1825 On-state voltage of IGBT Min: 0.0 CStat: CUT Datatype: Float Unit : V Def: 1.4 P-Group: INVERTER Act i ve : Immediately QuickCo mm.: No Max: 20.0 Corrects on-state voltage of the IGBTs.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 190 6SE6400-5BB00-0BP0 Notice: When choosing the setting for measurement, observe the following: 1.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 191 r1917[3] Identified stator inductance 2 Min: - Datatype: Float Unit : - Def: - P-Group: MOTOR Max: - Displays identified stator inductance.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 192 6SE6400-5BB00-0BP0 3.32 S peed optimization P1960 Speed control optimisation Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: MOTOR Act i ve : first confirm QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 193 Caution: Parameter P2000 represents the reference frequency of the above mentioned interfaces. A maximum frequency setpoint of 2*P2000 can be applied via the corresponding interface.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 194 6SE6400-5BB00-0BP0 P2002[3] Reference current Min: 0.10 CStat: CT Datatype: Float Unit : A Def: 0.10 P-Group: COMM Acti ve : first confirm QuickComm.: No Max: 10000.00 Full-scale output current used over serial link (corresponds to 4000H).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 195 3.34 Communication parameters (USS, CB) P2009[2] USS denormalization Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: COMM Acti ve : first confirm QuickComm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 196 6SE6400-5BB00-0BP0 P2012[2] USS PZD length Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 2 P-Group: COMM Acti ve : first confirm QuickComm.: No Max: 8 Defines the number of 16-bit words in PZD part of USS telegram.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 197 P2013[2] USS PKW length Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 127 P-Group: COMM Acti ve : first confirm QuickComm.: No Max: 127 Defines the number of 16-bit words in PKW part of USS telegram.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 198 6SE6400-5BB00-0BP0 P2014[2] USS telegram off time Min: 0 CStat: CT Datatype: U16 Unit : ms Def: 0 P-Group: COMM Acti ve : Immediately Quick Comm.: No Max: 65535 Defines the telegram failure time for the serial interfaces with USS protocol.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 199 P2016[8] CI: PZD to BOP link (USS) Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 52:0 P-Group: COMM Acti ve : Immediately Quick Comm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 200 6SE6400-5BB00-0BP0 r2018[8] CO: PZD from COM link (USS) Min: - Datatype: U16 Unit : - Def: - P-Group: COMM Max: - Displays process data received via USS on COM link.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 201 P2019[8] CI: PZD to COM link (USS) Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 52:0 P-Group: COMM Acti ve : Immediately Quick Comm.: No Max: 4000:0 Selects signals (process data PZD) to be transmitted to serial interface via USS on COM link P2012 .
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 202 6SE6400-5BB00-0BP0 r2026[2] USS character frame error Min: - Datatype: U16 Unit : - Def: - P-Group: COMM Max: - Displays number of USS character frame errors.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 203 r2033 BO: CtrlWrd2 from BOP l ink (USS) Min: - Datatype: U16 Unit : - Def: - P-Group: COMM Max: - Displays control word 2 from BOP link (i.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 204 6SE6400-5BB00-0BP0 P2040 CB telegram off time Min: 0 CStat: CT Datatype: U16 Unit : ms Def: 20 P-Group: COMM Acti ve : Immediately Quick Comm.: No Max: 65535 Defines time after which a fault will be generated (F0070) if no telegram is received via the link.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 205 P2051[8] CI: PZD to CB Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 52:0 P-Group: COMM Acti ve : Immediately Quick Comm.: No Max: 4000:0 Selects signals (process data PZD) to be transmitted via CB on COM link .
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 206 6SE6400-5BB00-0BP0 r2090 BO: Control word 1 from CB Min: - Datatype: U16 Unit : - Def: - P-Group: COMM Max: - Displays control word 1 received from communication board (CB).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 207 3.35 Fault s, Alarms, Monitoring P2100[3] Alarm number selection Min: 0 CStat: CT Datatype: U16 Unit : - Def: 0 P-Group: ALARMS Act i ve : first confirm Quick Comm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 208 6SE6400-5BB00-0BP0 P2104[3] BI: 2. Faults ackno w ledgement Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Selects second source of fault acknowledgement.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 209 r2114[2] Run time counter Min: - Datatype: U16 Unit : - Def: - P-Group: ALARMS Max: - Displays run time counter. It is the total time the drive has been powered up.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 210 6SE6400-5BB00-0BP0 Example: P2115[0] = 13625 P2115[1] = 2579 P2115[2] = 516 The conversion into binary quantities (U16) results in the following bit pattern: Seconds + minutes: - High byte (MSB) = 00110101 corresponding to the number 53, i.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 211 P2155[3] Threshold frequen cy f_1 Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 30.00 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 650.00 Sets a threshold for comparing actual frequency or frequency to threshold values f_1.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 212 6SE6400-5BB00-0BP0 P2159[3] Threshold frequen cy f_3 Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 30.00 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 650.00 Threshold_3 for comparing frequenc y to thresholds.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 213 P2162[3] Hysteresis fr eq. for overfreq. Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 20.00 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 650.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 214 6SE6400-5BB00-0BP0 P2166[3] Delay time ramp up completed Min: 0 CStat: CUT Datatype: U16 Unit : ms Def: 10 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 10000 Delay time for signal that indicates completion of ramp-up.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 215 r2169 CO: Act. filtered frequen cy 3 Min: - Datatype: Float Unit : Hz Def: - P-Group: ALARMS Max: - Filtered frequency for monitoring behind first-order lowpass filter.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 216 6SE6400-5BB00-0BP0 P2172[3] Threshold DC-link v oltage Min: 0 CStat: CUT Datatype: U16 Unit : V Def: 800 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 2000 Defines DC link voltage to be compared to actual voltage as illustrated in the diagram below.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 217 P2174[3] Torque threshold M_thre sh Min: 0.00 CStat: CUT Datatype: Float Unit : Nm Def: 5.13 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 99999.00 Defines torque threshold for comparing actual torque.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 218 6SE6400-5BB00-0BP0 P2179 Current limit for no load ident. Min: 0.0 CStat: CUT Datatype: Float Unit : % Def: 3.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 219 P2182[3] Belt threshold frequency 1 Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 5.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 220 6SE6400-5BB00-0BP0 P2184[3] Belt threshold frequency 3 Min: 0.00 CStat: CUT Datatype: Float Unit : Hz Def: 50.00 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 650.00 Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 221 P2190[3] Lo wer torque threshold 3 Min: 0.0 CStat: CUT Datatype: Float Unit : Nm Def: 0.0 P-Group: ALARMS Act i ve : Immediately QuickCo mm.: No Max: 99999.0 Lower limit threshold value 3 for comparing actual torque.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 222 6SE6400-5BB00-0BP0 3.37 T echnology controller (PID controller) P2200[3] BI: Enable PID controller Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 223 P2201[3] Fixed PID setpoint 1 Min: -200.00 CStat: CUT Datatype: Float Unit : % Def: 0.00 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 200.00 Defines Fixed PID Setpoint 1 There are three options available for selection of the PID fixed setpoints: 1.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 224 6SE6400-5BB00-0BP0 Direct selection of PID-FF1 P2201 via DIN 1: P 2 2 1 6 P0701 = 15 or P0701 = 99, P2220 = 722 .0, P2216 = 1 DIN1 r 2224 r 0722 .0 P2220 1 2,3 P2201 0 . . . . 0 . . .
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 225 P2206[3] Fixed PID setpoint 6 Min: -200.00 CStat: CUT Datatype: Float Unit : % Def: 50.00 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 200.00 Defines Fixed PID Setpoint 6 Index: P2206[0] : 1st.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 226 6SE6400-5BB00-0BP0 P2212[3] Fixed PID setpoint 12 Min: -200.00 CStat: CUT Datatype: Float Unit : % Def: 110.00 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 200.00 Defines Fixed PID Setpoint 12 Index: P2212[0] : 1st.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 227 P2218[3] Fixed PID setpoint mode - Bit 2 Min: 1 CStat: CT Datatype: U16 Unit : - Def: 1 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 3 BCD or direct selection Bit 2 for PID setpoint.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 228 6SE6400-5BB00-0BP0 P2222[3] BI: Fixed PID setp. select Bit 2 Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 0:0 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines command source of fixed PID setpoint selection Bit 2 Index: P2222[0] : 1st.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 229 P2227[3] Fixed PID setpoint mode - Bit 5 Min: 1 CStat: CT Datatype: U16 Unit : - Def: 1 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 2 Direct selection / direct selection + ON Bit 5 for PID setpoint.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 230 6SE6400-5BB00-0BP0 P2235[3] BI: Enable PID-MOP (UP -cmd) Min: 0:0 CStat: CT Datatype: U32 Unit : - Def: 19:13 P-Group: COMMANDS Act i ve : first confirm QuickComm.: No Max: 4000:0 Defines source of UP command.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 231 r2250 CO: Output setp oint of PID-MOP Min: - Datatype: Float Unit : % Def: - P-Group: TECH Max: - Displays output setpoint of motor potentiometer in [%].
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 232 6SE6400-5BB00-0BP0 These structures are selected using parameters P2200 and P22 51 (refer to the following table).
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 233 P2253[3] CI: PID setpoint Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 Defines setpoint source for PID setpoint input.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 234 6SE6400-5BB00-0BP0 P2257 Ramp-up time for PID setpoint Min: 0.00 CStat: CUT Datatype: Float Unit : s Def: 1.00 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 650.00 Sets the ramp-up time for the PID setpoint.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 235 P2261 PID setpoint filter timeconstant Min: 0.00 CStat: CUT Datatype: Float Unit : s Def: 0.00 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 60.00 Sets a time constant for smoothing the PID setpoint.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 236 6SE6400-5BB00-0BP0 P2267 Max. value for PID feedback Min: -200.00 CStat: CUT Datatype: Float Unit : % Def: 100.00 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 200.00 Sets the upper limit for the value of the feedback signal in [%].
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 237 P2274 PID derivative time Min: 0.000 CStat: CUT Datatype: Float Unit : s Def: 0.000 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 60.000 Sets PID derivative time.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 238 6SE6400-5BB00-0BP0 P2292 PID output lower limit Min: -200.00 CStat: CUT Datatype: Float Unit : % Def: 0.00 P-Group: TECH Ac ti ve : Immediately Quick Comm.: No Max: 200.00 Sets lower limit for the PID controller output in [%].
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 239 P2354 PID tuning timeout length Min: 60 CStat: CUT Datatype: U16 Unit : s Def: 240 P-Group: TECH Ac ti ve : Immediately Quick Comm.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 240 6SE6400-5BB00-0BP0 P2484[3] No. of shaft turns = 1 Unit Min: 0.01 CStat: CUT Datatype: Float Unit : - Def: 1.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 241 3.39 Free function blocks (FFB) P2800 Enable FFBs Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 1 Free function blocks (FFB) are enabled in two steps.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 242 6SE6400-5BB00-0BP0 P2802[14] Activ ate FFBs Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 3 Free function blocks (FFB) are enabled in two steps.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 243 P2810[2] BI: AND 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 P2810[0], P2810[1] define inputs of AND 1 element, output is P2811.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 244 6SE6400-5BB00-0BP0 P2816[2] BI: OR 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 P2816[0], P2816[1] define inputs of OR 1 element, output is P2817.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 245 P2822[2] BI: XOR 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 P2822[0], P2822[1] define inputs of XOR 1 element, output is P2823.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 246 6SE6400-5BB00-0BP0 P2828 BI: NOT 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 P2828 defines input of NOT 1 element, output is P2829.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 247 P2834[4] BI: D-FF 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 P2834[0], P2834[1], P2834[2], P2834[3] define inputs of D-FlipFlop 1, outputs are P2 835, P2836.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 248 6SE6400-5BB00-0BP0 r2838 BO: Q D-FF 2 Min: - Datatype: U16 Unit : - Def: - P-Group: TECH Max: - Displays output of D-FlipFlop 2, inputs are defined in P2837[0], P2837[1], P2837[2], P2837[3] Dependency: P2801[13] is active level for the D-FlipFlop.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 249 r2845 BO: NOT-Q RS-FF 2 Min: - Datatype: U16 Unit : - Def: - P-Group: TECH Max: - Displays Not-output of RS-FlipFlop 2, inputs are defined in P2843[0], P2843[1] Dependency: P2801[15] is active level for the RS-FlipFlop.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 250 6SE6400-5BB00-0BP0 P2849 BI: Timer 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 0:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 Define input signal of timer 1.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 251 P2851 Mode timer 1 Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 13 Selects mode of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 252 6SE6400-5BB00-0BP0 r2858 BO: Nout timer 2 Min: - Datatype: U16 Unit : - Def: - P-Group: TECH Max: - Displays Not-output of timer 2 P2854, P2855, P2856 are the inputs of the timer, out puts are P2857, P2858.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 253 P2866 Mode timer 4 Min: 0 CStat: CUT Datatype: U16 Unit : - Def: 0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 13 Selects mode of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 254 6SE6400-5BB00-0BP0 P2873[2] CI: SUB 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 755:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 Define inputs of Subtracter 1, result is in P2874.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 255 P2879[2] CI: MUL 2 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 755:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 Define inputs of Multiplier 2, result is in P2880.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 256 6SE6400-5BB00-0BP0 P2885[2] CI: CMP 1 Min: 0:0 CStat: CUT Datatype: U32 Unit : - Def: 755:0 P-Group: TECH Ac ti ve : first confirm QuickComm.: No Max: 4000:0 Defines inputs of Comparator 1, output is P2886.
Issue 01/06 Parameter Description MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 257 3.40 Inverter p arameters P3900 End of quick commissioning Min: 0 CStat: C Datatype: U16 Unit : - Def: 0 P-Group: QUICK Act i ve: first confirm QuickComm.: Yes Max: 3 Performs calculations necessary for optimized motor operation.
Parameter Description Issue 01/06 MICROMASTER 440 Parameter List 258 6SE6400-5BB00-0BP0 P3980 Commissioning command selection Min: 0 CStat: T Datatype: U16 Unit : - Def: 0 P-Group: - Act i ve : first confirm QuickComm.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 259 4 Function Diagrams - 10 - Function diagram 8 7 6 5 4 3 2 1 0010_Symbols.vsd MICROMASTER 440 16.01.2006 V2.1 Symbols in funktion diagr ams ParName [Dim] PNumber.C/D [3] (Default) ParName [Dim] PNum.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 260 6SE6400-5BB00-0BP0 - 1100 - Function diagram 8 7 6 5 4 3 2 1 1100_Overview.vsd Overview MICROMASTER 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 261 - 1200 - Function diagram 8 7 6 5 4 3 2 1 1200_B ICO_ Overv .v sd Overview MICROMASTER 440 16.01.2006 V2.1 Connection of External and Internal Setpoints CO/BO: Bin.inp.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 262 6SE6400-5BB00-0BP0 r0722 - 2000 - Function diagram 8 7 6 5 4 3 2 1 2000_DIN.vsd External Interfaces MICROMASTE R 440 16.01.2006 V2.1 Digital Inputs 24 V T0 & 0 1 PNP/NPN DIN 0 ... 1 P0725 (1) KL5 0 V 24 V Debounce time: DIN 0 .
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 263 - 2100 - Function diagram 8 7 6 5 4 3 2 1 2100_DOUT.vsd External Interfaces MICROMASTE R 440 16.01.2006 V2.1 Digital Outputs (52:3) BI: Fct. of DOUT 1 P0731.C -1 0 1 Invert DOUTs 0 .
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 264 6SE6400-5BB00-0BP0 - 2200 - Function diagram 8 7 6 5 4 3 2 1 2200_ADC.vsd External Interfaces MICROMASTE R 440 16.01.2006 V2.1 Analog Input (ADC) D A Switching bipolar unipolar Digit Warning, signal lost (F0080) ADC after scal.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 265 - 2300 - Function diagr am 8 7 6 5 4 3 2 1 VisioDocu ment External Interfa ces MICROMASTER 440 16.01.20 06 V2.1 Analog Outpu t (DAC) Type of DAC 0 ... 1 P0776 [2 ] (0) A D x(t) Value x1 :DAC sca l.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 266 6SE6400-5BB00-0BP0 POWER ON is selected, a changeover to the value di splay has taken place with the toggle key and the unit is in the "Operation" status.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 267 - 2500 - Function diagram 8 7 6 5 4 3 2 1 2500_USSonBOP.vsd External Interfaces MICROMASTE R 440 16.01.2006 V2.1 USS on BOP link, Receiving All parameters: Index = 1 => BOP link PKW PZD 1 [0] r2015 [1] [2] [3] 2 3 4 5 6 7 0 [4] [5] [6] [7] USS baudrate 4 .
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 268 6SE6400-5BB00-0BP0 - 2510 - Function diagram 8 7 6 5 4 3 2 1 2510_USSonBOP.vsd External Interfaces MICROMASTE R 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 269 - 2600 - Function diagram 8 7 6 5 4 3 2 1 2600_USSonCOM.vsd External Interfaces MICROMASTE R 440 16.01.2006 V2.1 USS on COM link, Receiving All parameters: Index = 0 => COM link PKW PZD 1 [0] r2018 [1] [2] [3] 2 3 4 5 6 7 0 [4] [5] [6] [7] USS baudrate 4 .
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 270 6SE6400-5BB00-0BP0 - 2610 - Function diagram 8 7 6 5 4 3 2 1 2610_USSonCOM.vsd External Interfaces MICROMASTE R 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 271 - 2700 - Function diagram 8 7 6 5 4 3 2 1 2700_CBonCOM.vsd External Interfaces MICROMASTE R 440 16.01.2006 V2.1 CB on COM link, Receiving PKW PZD 1 [0] r2050 [1] [2] [3] 2 3 4 5 6 7 [4] [5] [6] [7] CB tel.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 272 6SE6400-5BB00-0BP0 - 2710 - Function diagram 8 7 6 5 4 3 2 1 2710_CBonCOM.vsd External Interfaces MICROMASTE R 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 273 - 3100 - Function diagram 8 7 6 5 4 3 2 1 3100_MOP.vsd Internal Setpoint Source MICROMASTE R 440 16.01.2006 V2.1 Motor Pote ntiometer (MOP) (19:13) BI: Enable MOP(UP) P1035.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 274 6SE6400-5BB00-0BP0 - 3200 - Function diagram 8 7 6 5 4 3 2 1 3200_FF .vs d Internal Setpoint Source MICROMASTER 440 16.01.2 006 V2.1 Fixed Frequency (FF) bit coded Fixed frequency 4 -650.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 275 - 3210 - Function dia gram 8 7 6 5 4 3 2 1 3210_FF.v sd Internal Setpoint Source MICROMA STER 4 40 16.01.2 006 V2. 1 Fixed F requenc y ( FF) bina ry c oded 0 0 0 1 0 1 0 1 0 1 1 0 1 1 1 1 0 0 0 0 Fixed frequency 5 -650.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 276 6SE6400-5BB00-0BP0 - 3300 - Function diagram 8 7 6 5 4 3 2 1 3300_FP ID. vsd Internal Setpoint Source MICROMASTER 440 16.01.2 006 V2.1 Fixed PID setpoint, bit coded Fixed PID setp. 4 -200.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 277 - 3310 - Function dia gram 8 7 6 5 4 3 2 1 3310_FPI D.v sd Internal Setpoint Source MICROMA STER 4 40 16.01.2 006 V2. 1 Fixed PID setpoint, binar y co ded 0 0 0 1 0 1 0 1 0 1 1 0 1 1 1 1 0 0 0 0 Fixed PID setp.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 278 6SE6400-5BB00-0BP0 - 3400 - Function diagram 8 7 6 5 4 3 2 1 3400_PIDMOP.v sd Internal Setpoint Source MICROMASTER 440 16.01.2006 V2.1 PID Motor Pot entiometer (P ID-MOP ) (19:13) BI: PID-MOP (UP) P2235.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 279 - 4100 - Function diagram 8 7 6 5 4 3 2 1 4100_S W21. vs d Technology Func tions MICROMASTER 440 16.01.2006 V2.1 Monitoring SwOff freq. f_off 0.00 ... 10.00 [Hz] P2167.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 280 6SE6400-5BB00-0BP0 - 4110 - Function diagram 8 7 6 5 4 3 2 1 4110_S W22. vs d Technology Func tions MICROMASTER 440 16.01.2006 V2.1 Monitoring f_act >= f_set Tconst. freq. filt 0 ... 1000 [ms] P2153.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 281 - 4150 - Function diagram 8 7 6 5 4 3 2 1 4150_STW1.vsd Technology Functions MICRO MASTER 440 16.01.2006 V2.1 Control word 1 (r0054) 1) (1:0) BI: 1. OFF2 P0844.C (19:1) BI: 2.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 282 6SE6400-5BB00-0BP0 - 4160 - Function diagram 8 7 6 5 4 3 2 1 4160_STW2.vsd Technology Func tions MICROMASTER 440 16.01.2006 V2.1 Control word 2 (r0055) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1) (0:0) BI: FF sel.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 283 - 4170 - Function diagram 8 7 6 5 4 3 2 1 4170_ZSW1.vsd Technology Func tions MICROMASTER 440 16.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 284 6SE6400-5BB00-0BP0 - 4180 - Function diagram 8 7 6 5 4 3 2 1 4180_ZSW2.vsd Technology Func tions MICROMASTER 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 285 - 4600 - Function diagram 8 7 6 5 4 3 2 1 4600.vsd Technology Func tions MICROMASTER 440 16.01.2006 V2.1 Vdc Control (max , min) r0070 CO: Act. Vdc [V] r1242 CO: Vd c-max O N lev [V] Int.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 286 6SE6400-5BB00-0BP0 - 4800 - Function diagram 8 7 6 5 4 3 2 1 4800_FreeBlocks1.v sd Free Blocks MICROMAST ER 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 287 - 4810 - Function diagram 8 7 6 5 4 3 2 1 4810_FreeBlocks2.v sd Free Blocks MICROMAST ER 440 16.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 288 6SE6400-5BB00-0BP0 - 4820 - Function diagram 8 7 6 5 4 3 2 1 4820_FreeBlocks3.vsd Free Blocks MICROMASTER 440 16.01.2006 V2.1 Timers T 0 ON Delay 0 T OFF Delay T T ON/OFF Delay Pulse G ernerator r2852 1 r2853 P2849 Index0 Index0 0 1 2 3 P2851(0) Mode P2850 (0.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 289 - 4830 - Function diagr am 8 7 6 5 4 3 2 1 4830_FreeBlocks 4.vs d Free Bl ocks MICROMASTER 440 16.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 290 6SE6400-5BB00-0BP0 - 5000 - Function diagram 8 7 6 5 4 3 2 1 5000_Overview.vsd Overview MICROMASTER 440 16.01.2006 V2.1 Setpoint channel and Motor control 0 1 r1078 CO: Tot. freq.setp [Hz] r2294 CO: Act.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 291 - 5100 - Function diagram 8 7 6 5 4 3 2 1 5100_PID.vsd Setpoint Channel MICROMASTER 440 16.01.2006 V2.1 PID controller Kp Tn x y + + x y PID trim gain fact 0.00 ... 100.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 292 6SE6400-5BB00-0BP0 No evaluation with PID - 5200 - Function diagram 8 7 6 5 4 3 2 1 5200_AFM.vsd Setpoint channel MICROMASTER 440 16.01.2006 V2.1 Additional Frequency Modifications (AFM) (0:0) BI: Inh.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 293 PID trim from AFM POWER ON (Freeze y) Stop RFG - 5300 - Function diagram 8 7 6 5 4 3 2 1 5300_RFG.vsd Setpoint Channel MICROMASTER 440 16.01.2006 V2.1 Ramp Function Gener ator P1133 P1132 (1:0) BI: RFG start P1141.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 294 6SE6400-5BB00-0BP0 PID trim from AFM Frequency output to modulator n/f(max) + control reser ve active - 6100 - Function diagram 8 7 6 5 4 3 2 1 6100_V_f.vsd V/f Control MICROMASTER 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 295 Setpoint channel **) settable via P1000 *) Access level 4 - 7000 - Function diagram 8 7 6 5 4 3 2 1 7000.vsd Vector Control MICROMAST ER 440 16.01.2006 V2.1 Overv iew of Speed Control without Encoder (SLVC): – Asyc.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 296 6SE6400-5BB00-0BP0 Encoder Setpoint channel – Asyc. Mot. 3~ + + 1 4 2 Max. frequency 0.00 ... 650.00 [Hz] P1082.D (50.00) Max. frequency 0.00 ... 650.00 [Hz] P1082.D (50.00) r1170 CO:Setp.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 297 **) The speed integrator doesn't w ork in the range of the observer mode l *) settable via P1500 - 7200 - Function diagram 8 7 6 5 4 3 2 1 7200.vsd Vector Control MICROMAST ER 440 16.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 298 6SE6400-5BB00-0BP0 Encoder **) The speed integrator doesn't w ork in the range of the observer mode l *) settable via P1500 - 7210 - Function diagram 8 7 6 5 4 3 2 1 7210.vsd Vector Control MICROMAST ER 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 299 Forward speed Speed precontrol Speed controller output Torque limitation Torque limitation **) changeable in run via DDS Observer model Torque limitation Torque limitation speed from observer model Ramp generator - 7500 - Function diagram 8 7 6 5 4 3 2 1 7500_SLVC.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 300 6SE6400-5BB00-0BP0 Forward speed Speed precontrol Speed controller output Torque limitation Torque limitation **) changeable in run via DDS Observer model Torque limitation Torque limitation Speed measurement Ramp generator - 7510 - Function diagram 8 7 6 5 4 3 2 1 7510_VC.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 301 Current control Observer model Forward speed **) selectable with P1500 enable Flux setpoint - 7700 - Function diagram 8 7 6 5 4 3 2 1 7700_TC.vsd Vector Control MICROMASTER 440 16.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 302 6SE6400-5BB00-0BP0 Motor stall protection Current control **) selectable with P1500 act. frequency Flux setpoint - 7710 - Function diagram 8 7 6 5 4 3 2 1 7710_TC.vsd Vector Control MICROMASTER 440 16.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 303 Current control and stall protection Saturation characteristic P0362 ... P0369 *) Speed control Field weakening controller Efficiency optimization Field weakening characteri stic Act.
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 304 6SE6400-5BB00-0BP0 only SLVC: speed to speed controller Field weakening control Speed or torque control iq controller id controller Flux setpoint Rotor flux Speed control - 7900 - Function diagram 8 7 6 5 4 3 2 1 7900_MM.
Issue 01/06 Function Diagrams MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 305 from sheet from sheet from sheet from sheet from sheet from sheet - 8000 - Funct ion diagram 8 7 6 5 4 3 2 1 8000.vsd Vector Control MICROMASTER 440 16.01. 2006 V2 .1 Analog outputs and dis play va lues x y = f(x) y D A 12 13 AOUT1 D A 26 27 AOUT2 0 .
Function Diagrams Issue 01/06 MICROMASTER 440 Parameter List 306 6SE6400-5BB00-0BP0.
Issue 01/06 Faults and Alarms MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 307 5 Fault s and Alarms 5.1 Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display. NOTE To reset the fault code, one of three methods li sted below can be used: 1.
Faults and Alarms Issue 01/06 MICROMASTER 440 Parameter List 308 6SE6400-5BB00-0BP0 F0003 Undervoltage STOP II Quit Refer to F0001 Cause - line voltage failed - shock stressing outside the permissible limits.
Issue 01/06 Faults and Alarms MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 309 F0015 No motor temperature signal STOP II Quit Refer to F0001 Cause - motor temperature sensor either short-circuited or open-circuit.
Faults and Alarms Issue 01/06 MICROMASTER 440 Parameter List 310 6SE6400-5BB00-0BP0 F0023 Output fault STOP II Quit Refer to F0001 Cause - one output phase has not been correctly connected. Diagnosis & Remed y Please check the following: - are the connections at the motor terminal box o.
Issue 01/06 Faults and Alarms MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 311 F0041 Failure, motor data identification STOP II Quit Refer to F0001 Cause Motor data identification run unsuccessful (refer to fault value r0949): - r0949 = 0: Load missing.
Faults and Alarms Issue 01/06 MICROMASTER 440 Parameter List 312 6SE6400-5BB00-0BP0 F0054 Incorrect I/O module STOP II Quit Refer to F0001 Cause - incorrect I/O module i nserted.
Issue 01/06 Faults and Alarms MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 313 F0090 Signal loss, encoder STOP II Quit Refer to F0001 Cause - encoder signal between the encoder and inverter is in.
Faults and Alarms Issue 01/06 MICROMASTER 440 Parameter List 314 6SE6400-5BB00-0BP0 F0452 Load torque fault detected STOP II Quit Refer to F0001 Cause - load conditions at the motor signify a load torque fault (e.
Issue 01/06 Faults and Alarms MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 315 5.2 Alarm Messages Alarm messages are stored in para meter r2110 under their code number (e.
Faults and Alarms Issue 01/06 MICROMASTER 440 Parameter List 316 6SE6400-5BB00-0BP0 A0510 Motor overtemperature A0511 Motor overtemperature Cause - motor is overloaded.
Issue 01/06 Faults and Alarms MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 317 A0590 Alarm, no signals from the speed encoder Cause - no speed encoder signals - inverter has changed-over to encoderless vector control.
Faults and Alarms Issue 01/06 MICROMASTER 440 Parameter List 318 6SE6400-5BB00-0BP0 A0707 CB alarm 8 Cause - CB-(Communications module)-spe cific Diagnosis & Remed y - refer to the CB User Manual .
Issue 01/06 Faults and Alarms MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 319 A0920 ADC parameters not correctly set Cause ADC parameters should not be set to identical values, as this would lead to illogical results. - Index 0: Parameter settings for output identical.
Faults and Alarms Issue 01/06 MICROMASTER 440 Parameter List 320 6SE6400-5BB00-0BP0.
Issue 01/06 Abbreviations MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 321 6 Abbreviations AC Alternating current AD Analog digital converter ADC Analog digital converter ADR Address AFM Addition.
Abbreviation s Issue 01/06 MICROMASTER 440 Parameter List 322 6SE6400-5BB00-0BP0 EMC Electro-magnetic compatibility EMF Electromotive force EMI Electro-magnetic interference ESB Equivalent circuit FAQ.
Issue 01/06 Abbreviation s MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 323 RCCB Residual current circuit breaker RCD Residual current device RFG Ramp function generator RFI Radio-frequency inter.
Abbreviation s Issue 01/06 MICROMASTER 440 Parameter List 324 6SE6400-5BB00-0BP0.
MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 325 Suggestions and/or Corrections Suggestions Corrections To Siemens AG Automation & Drives Group SD SPA PM 4 P.O. Box 3269 D-91050 Erlangen Federal Republic of Germany For Publication/Manual: MICROMASTER 440 Parameter List Email: documentation.
MICROMASTER 440 Parameter List 326 6SE6400-5BB00-0BP0.
MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0 327.
Siemens AG Automation and Drives Group (A&D) Standard Drives (SD) Division Postfach 3269, D-91050 Erlangen Federal Republic of Germany © Siemens AG, 2001, 2002, 200 3, 2004, 2005 Subject to change without prior noti ce Siemens Aktiengesellschaf t Order No.
Ein wichtiger Punkt beim Kauf des Geräts Siemens 440 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Siemens 440 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Siemens 440 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Siemens 440 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Siemens 440 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Siemens 440 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Siemens 440 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Siemens 440. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Siemens 440 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.