Benutzeranleitung / Produktwartung 125-5033 des Produzenten Siemens
Zur Seite of 35
Two-State Constant Volume Fume Hood Controller Owner’s Manual 125-5033 Rev. AA, September 2007.
.
Rev. AA, September 2007 NOTICE The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Tec hnologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document.
.
Siemens Building Techologies, Inc. V Table of Contents How To Use This Manual ............................................................................................. VII Manual Organiza tion ......................................................
VI Siemens Building Technologies, Inc. Applicat ions .................................................................................................................. 11 Fume Hood Controller: 2-Posi tion Constant Volume ..............................
Siemens Building Techologies, Inc. VII How To Use This Manual This section covers manual organization, conventions, and symbols used in the manual, and other information that w ill help you understand and use a Laboratory Room Controller — Electronic Output.
VIII Siemens Building Technologies, Inc. Manual Symbols The following table lists symbols that are us ed to draw your attention to important information. Notation Symbol Meaning CA UTION: Indicates that equipment damage or loss of data may occur if the user does not follow a procedure as specified.
Siemens Building Technologies, Inc. 1 1 Product Overview Introduction The Fume Hood Controller is an equipment controller designed to provide Direct Digital Control (DDC) for 2 position fume hoods. The c ontroller consists of a controller board and a controller enclosure.
Fume Hood Controller Owner's Manual 2 Siemens Building Technologies, Inc. Table 1. Fume Hood Controller – Ele ctronic Output A pplications. Application Description 940 2 Position Fume Hood Controller Ordering Notes Fume Hood Controller – Electronic Output (940) 546-00750 Figure 1.
Product Overview Siemens Building Technologies, Inc. 3 Hardware Inputs Analog • Differential pressure transmitter Digital • Operator Display Panel (ODP) • ATTN.
Fume Hood Controller Owner's Manual 4 Siemens Building Technologies, Inc. 24V COMMON 24V HOT GROUND LAB00140R1 FLN TRUNK +- S (SHIELD) (SHIELD) (+) (+) (-) (-) TEC0470R1 Figure 2. Power Wiring. Figure 3. Communication Wiring. Controller LED Indicators The controller has six Light Emitting Diode (LED) indicators.
Product Overview Siemens Building Technologies, Inc. 5 Pressing the Emergency Purge button a second time reverts the Fume Hood Controller to normal operation for the current conditions.
Fume Hood Controller Owner's Manual 6 Siemens Building Technologies, Inc. The terminal is available in diameters ranging from 4 to 18 inches. The terminal is available in a variety of end configurations to match the duc twork construction. It is also available in TEFLON ® coated 18-gauge steel for highly corrosive environments.
Product Overview Siemens Building Technologies, Inc. 7 High Speed Electronic Actuation The High speed electronic actuator assembly cons ists of two parts, t he electronic actuator and the interface board. The actuator is connect ed to the exhaust flow control device in the fume hood exhaust duct.
Fume Hood Controller Owner's Manual 8 Siemens Building Technologies, Inc. Low Speed Electronic Actuation Alternately, when speed of response is not an issue, slower speed electronic actuation may be used. This can be used when the change-of-s tate between High and Low can take place in 15 seconds or more.
Product Overview Siemens Building Technologies, Inc. 9 Figure 8. Pneumatic Actuator. Analog Output-Pneumatic (AO-P) Module The Analog Output-Pneumatic (AO-P) Module is an electric-to-pneumatic interface between the Fume Hood Controller and the pneumatic actuator.
Fume Hood Controller Owner's Manual 10 Siemens Building Technologies, Inc. NOTE: While the pneumatic actuator is bei ng commanded, you may hear a hissing or clicking sound coming from the AO-P module. This is due to the movement of the air valves and the bleeding of air from t he actuator.
Siemens Building Technologies, Inc. 11 2 Applications Fume Hood Controller: 2-Position Constant Volume Application 940 is designed for use with a cons tant volume or two-position fume hood in a manifold fume hood exhaust system.
Fume Hood Controller Owner's Manual 12 Siemens Building Technologies, Inc. Basic Operation The Fume Hood Controller provides Direct Di gital Control (DDC) technology for controlling fume hood face velocities in a manifolded fume hood exhaust system.
Applications Siemens Building Technologies, Inc. 13 DO3 Output Functionality DO3 is designed to operate in two different m odes. DO3 can follow the alarm status of the controller by turning ON during alarm condi tions and OFF during normal operation; or DO3 can follow the HI.
Fume Hood Controller Owner's Manual 14 Siemens Building Technologies, Inc. Alarm Strategies One approach is to use the ALARMs to indicate a condition that requires immediate attention and the WARNINGs to indicate a condition that may require attention but is not urgent.
Applications Siemens Building Technologies, Inc. 15 The fume hood operator may silence the horn by pressing the Horn Silence button on the ODP without affecting the Emergency Purge sequence. In addition to the ODP indicators, the emergency alarm point will toggle to ON and will remain ON until the sequence is canceled.
Fume Hood Controller Owner's Manual 16 Siemens Building Technologies, Inc. In addition to setting up the purge sequence to effectively handle the exhaust needs, decisions must be made on how to use the info rmation available at the central reporting station.
Point Database Siemens Building Technologies, Inc. 17 3 Point Database Chapter 3 presents a description of the Fume Hood Controller point database including point descriptors, point addresses, and a listing of applications in which each point is found.
Fume Hood Controller Owner’ s Manual 18 Siemens Building Technologies, Inc. Address Descriptor Description 15 EMER STPT A value of the preset FLOW STPT, in percent, that the controller uses as the setpoint when EMER ALM is ON. 16 LOW WARN This point displays an ON or O FF status.
Point Database Siemens Building Technologies, Inc. 19 Address Descriptor Description 56 ODP STPT SW Indicates if the lowe r left butt on on the ODP has been pressed. This is a toggle action digital input; when pressed, t he controller changes betw een HI and LOW flow setpoints.
20 Siemens Building Technologies, Inc. 4 Troubleshooting This chapter describes corrective measures you can take should you encounter a problem when using the Fume Hood Controller. For issues not covered in this section, contact your local Siemens Building Technologies, Inc.
Troubleshooting Siemens Building Technologies, Inc. 21 Safety Features The controller board stores the controller's addr ess, applications, and point values. In the event of a power failure or a reset, these val ues are retrieved from the controller’s permanent memory and are used by the controlle r unless overridden by a field panel.
22 Siemens Building Technologies, Inc. Glossary The glossary contains terms and acronyms that are used in this manual. For definitions of point database descriptors, see Chapter 3 - Point Database, in this manual.
Glossary Siemens Building Technologies, Inc. 23 English units The foot-pound-second system of uni ts for weights and measurements. equipment controller A FLN device which provides additional point c apacity to a field panel or provides DDC to individual room or mechanical equipment c ontrol.
Fume Hood Controller Owner's Manual 24 Siemens Building Technologies, Inc. ON text Text indicating the energized state of a di gital point (for example, ON, OPEN, YES). override switch Button on room temperature sensor which can be pressed by an occupant to change the status of a room from night mode to day mode for a predetermined time.
Glossary Siemens Building Technologies, Inc. 25 Terminal Equipment Controller Siemens Building Technologies, Inc. product family of equipment controllers (one is the Unit Conditioner Controller – El.
26 Siemens Building Technologies, Inc. Index A AI see analog input airflow s ensor ..................................................... 9 analog input ........................................................ 2 analog output ..........................
Index Siemens Building Technologies, Inc. 27 analog ............................................................. 3 digital .............................................................. 3 horn silence button ..........................................
Ein wichtiger Punkt beim Kauf des Geräts Siemens 125-5033 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Siemens 125-5033 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Siemens 125-5033 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Siemens 125-5033 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Siemens 125-5033 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Siemens 125-5033 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Siemens 125-5033 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Siemens 125-5033. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Siemens 125-5033 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.