Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the d evice before trying to install , operate, service o r maintain it.
Notices FCC Part 15 Notice This equipment has be en tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of th e FCC Rules. These limits are des igned to provide reasonable protection against harmful interferen ce in a resid ential installation.
telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with th e FCC if you believe it is necessary. The telephone company may ma ke changes in its facilitie s, equipment, operations or procedures that could affect the oper at ion of this equipment.
.
930-112-01-D.00 PowerLogic TM EM4000/EM4800 Series 11/2013 Table of Con tents ©2013 Schneider Electric All Rights Reserved i Table of Contents PowerLogic configuration tool ............. .............. .............. ........... .............. ... 1 System Set-up and Description .
PowerLogic TM EM4000/EM4800 Series 930-112-01-D.00 Table of Contents 11/2013 ©2013 Schneider Electric All Rights Reserved ii.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 1 PowerLogic configuration tool This document describes how to conf igure the PowerLogic EM4000/EM4800 Series meters, using the PowerLogic co nfigur ation tool.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 2 ©2013 Schneider Electric All Rights Reserved Figure 1: Programming Switch locatio n Table 1 lists the pr ogramming capabilities associat ed with each parameter in combination w ith the pr ogramming switches.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 3 Display Navigation The display on the fron t of the me ter prov ides status information for each circuit, and general information for metering.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 4 ©2013 Schneider Electric All Rights Reserved Normal Mode In Normal mode, the Display butt on scrolls through the information for each meter. The left and ri ght arrow butto ns select the previous or next meter points respectively.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 5 • Ethernet po rt MAC addres s • Firmware revision • Potential transfo rmer ratio Commun.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 6 ©2013 Schneider Electric All Rights Reserved 7. Assign the PC a static IP address such that the first three segments are the same as the default IP address, an d th e last segment is different from the default IP address.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 7 4. Re-install the inner cover. 5. Using a CAT 5 Ethernet patch cable, connect the meter and the PC to a local Ethernet switch. 6. Re-install the outer cover .
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 8 ©2013 Schneider Electric All Rights Reserved Figure 3: Configuration too l main window Connecting to a Meter The configuration tool automatically d etect s and lists the PowerLogic meters on the same network segment as the PC.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 9 To connect to a meter on the same network: 1. Click Unit in the menu bar, then select List from the drop-down menu. The Discovered Units window appears, displa ying a list of meters available for configuration.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 10 ©2013 Schneider Electric All Rights Reserved 2. Enter the IP address of the meter to be configured, th en click Connect. The configuration tool main win dow appears populated with the current programming info rmation for the selecte d meter.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 11 Table 2: Unit Field Co nfiguration tab pa rameters Field Parameter Description Unit Field Configuration Current IP Address The current IP address fo r the unit .
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 12 ©2013 Schneider Electric All Rights Reserved Report Parameters The Report section in the main confi guration window has six tabs: • Int.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 13 Example : Selecting a Recording Interval of 5 minutes with Sliding Window Demand enabled and 3 Sub- intervals, creates a demand calculation every 5 minutes based on the previous 15 min utes.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 14 ©2013 Schneider Electric All Rights Reserved Table 4: Ty pes tab confi guration parame ters NOTE: If parameters are grayed out, they ar e not available on the variant or firmware revision of the meter bein g configured.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 15 Figure 9: Reporting Sch edule tab in the Repo rt section Table 5: Reportin g Schedule tab co.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 16 ©2013 Schneider Electric All Rights Reserved Figure 10: Calculations & Format t ab in the Report section Table 6: Calculation s &.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 17 Figure 11: BACnet tab in t he Report section Table 7: BACnet tab configuration parameters Parameter Description Device ID Set the BACnet device ID by entering a a numeric ID between 0 and 4194303.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 18 ©2013 Schneider Electric All Rights Reserved Figure 12: Comms tab in the Report section.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 19 Table 8: Comms tab configura tion parameters NOTE: The Modbus and RTU Adapter Comms Option para meters are valid only when a Modem module or an RTU adapter module is present.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 20 ©2013 Schneider Electric All Rights Reserved Table 9: List of supporte d PowerLogic metering confi gurations To view the manufacturing informa tion for a specific meter, sele ct a model number from the Model # pull-down list shown in Figure 13.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 21 Meter Points (Circuits) Tab The Meter Po ints (Circuits) tab contain s the configurat ion info rmation for each of the metering points.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 22 ©2013 Schneider Electric All Rights Reserved To change the curren t rating for all probes assigned to a meter point : 1. Select a meter from the Meter Points ( Circuits) List. The selected meter will appear in the Name field of the middle pane.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 23 Figure 15: Badge Numbering pan e Reset Buttons • Reset Dial Readings button - selecting this button rese ts all registers for all energy types and pulse coun ts to zero.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 24 ©2013 Schneider Electric All Rights Reserved • Adjust Dial Re ading button - selecting this button allows the operator to set all of th.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 25 Figure 16: Pulse Probes tab.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 26 ©2013 Schneider Electric All Rights Reserved Completing the Meter Configuration Once you have defined all of the configur able parameters, the PowerLogic meter is ready to be progra mmed. To complete the me ter configuration: 1.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 27 2. Click Unit in the menu bar, then select Send from the drop-down menu to transmit the configuration settin gs from your PC to the selected PowerLogic meter.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 28 ©2013 Schneider Electric All Rights Reserved.
930-112-01-D.00 PowerLogic TM Series EM4000/EM4800 11/2013 ©2013 Schneider Electric All Rights Reserved 29 User notes.
PowerLogic TM Series EM4000/EM4800 930-112-01-D.00 11/2013 30 ©2013 Schneider Electric All Rights Reserved.
.
PowerLogic TM Series EM4000/EM4800 Multi-Circuit Meters Schneider Electric 35 rue Joseph Monier 92500 Rueil-Malmaison, France www.schneider-electric.com 930-112-01-D.00 11/2013 ©2013 All Rights Reserved PowerLogic is a trademark or regi stered trademar k of Schneid er Electric in France, the USA and other countries.
Ein wichtiger Punkt beim Kauf des Geräts Schneider Electric EM4800 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Schneider Electric EM4800 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Schneider Electric EM4800 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Schneider Electric EM4800 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Schneider Electric EM4800 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Schneider Electric EM4800 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Schneider Electric EM4800 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Schneider Electric EM4800. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Schneider Electric EM4800 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.