Benutzeranleitung / Produktwartung 5476 des Produzenten Samson
Zur Seite of 114
Automation System 5400 Heating and District Heating Controller TROVIS 5476 Mounting and Operating Instructions EB 5476 EN ® Electronics from SAMSON Fi rmw a re v e rsi o n 2 .
Disclaimer of liability We are constantly developing our products and therefore, reserve the right to change the prod - uct or the information contained in this document at any time without notice. We do not assume any liability for the accuracy or completeness of these mounting and operating instructions.
Contents 1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.1 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.1.1 Operating keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.1.2 Operating switches .
5.10 Pump management . . . . . . . . . . . . . . . . . . . . . . . . . . 48 5.11 Potentiometer input . . . . . . . . . . . . . . . . . . . . . . . . . . 48 6 Functions of the DHW circuit . . . . . . . . . . . . . . . . . . . . . . 49 6.1 DHW heating in the storage tank system .
9.1 Controller with RS-232-C port . . . . . . . . . . . . . . . . . . . . . 67 9.2 Controller with serial RS-485 interface . . . . . . . . . . . . . . . . . 68 9.3 Description of communication parameters to be adjusted . . . . . . . . 69 9.4 Meter bus interface .
1 Operation The controller is ready for use with the temperatures and operating schedules preset by the manufacturer. On start-up, the current time and date need to be set at the controller (–> section 1.5). 1.1 Operating elements The operating controls are located in the front panel of the controller and protected by a Plexi - glas door.
1.1.2 Operating switches Heating circuit mode selector switch Automatic mode with switchover between rated operation and reduced operation or standby mode Day mode (rated operation) Night mode (reduce.
1.2 Operating modes Day mode (rated operation) Regardless of the programmed times-of-use, the set points relevant for rated operation are used by the controller. Night mode (reduced operation) Regardless of the programmed times-of-use, the set points relevant for reduced operation are used by the controller.
1.3 Display During operation, the display indicates the current time as well as information about the opera - tion of the controller. The times-of-use are represented by black squares below the row of num - bers at the top of the display. Icons indicate the operating status of the controller.
1.4 Displaying data Measured values, set points, times-of-use, public holidays and vacation periods as well as tem - peratures of the connected sensors and their set points can be retrieved and displayed in the op - erating level. Proceed as follows: Select value.
1.5 Setting the controller time The current time and date need to be set immediately after start-up and after a power failure lasting longer than 24 hours. The time is set in the parameter level. Proceed as follows: Switch to the parameter level. Display: Time, blinks Activate editing mode for the controller time.
1.6 Setting the times-of-use Two times-of-use can be set for each day of the week. If only one time-of-use is required, the start and stop times of the second time-of-use must be programmed to identical times. The times schedules are set for the required control circuits one after the other in the parameter level.
Select datapoint for times-of-use. Display: Activate editing mode for times-of-use. Display: 1–7 Select period/day for which the times-of-use are to be valid: 1–7 = Monday to Sunday 1–5 = Monday to Friday 6–7 = Saturday to Sunday 1 = Monday, 2 = Tuesday, …, 7 = Sunday Activate editing mode for period/day.
1.6.1 Entering public holidays On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holi - days may be entered. The public holidays are set in the parameter level. Set the function block FB6 = ON to make the programmed public holidays also apply to the DHW heating.
1.6.2 Entering vacation periods During vacation periods, the controller constantly remains in the reduced operating mode. The system is monitored for frost. A maximum of 10 vacation periods can be entered. The vacation periods are set in the parameter level.
Deleting vacation periods: Select the vacation period you wish to delete in the datapoint for vacation periods. Confirm selection. Select – – – – .
2 Start-up 2.1 Setting the system code number 10 different hydraulic schematics are available. Each system configuration is represented by a system code number (Anl). The different schematics are dealt with in section 4. Available con - troller functions are described in sections 5, 6 and 7.
Proceed as follows: Switch to the parameter level. Display shows: Time, blinks Switch to the configuration level. Display shows: Current system code number, blink. Select level displaying function blocks 0 to 23 or Select level displaying function blocks 24 to 47.
2.3 Changing parameters Depending on the set system code number and the activated functions, not all parameters listed in the parameter list in the Appendix (–> section 12.2) might be available. Proceed as follows: Switch to the parameter level. Display shows: Time, blinks Select parameter.
2.5 Calibrating sensors The connected sensors are calibrated in the configuration level. The following applies: 4 FB16 = ON, select “P1000“: Pt 1000 and Pt 100 sensors 4 FB16 = ON, select “ntc“: NTC and Pt 100 sensors 4 FB16 = OFF: PTC and Pt 100 sensors (default setting) The resistance values of the sensors can be found on page 98.
Return flow sensor (RüF2) Solar circuit collector sensor (CF) Flow sensor (VF2) Storage tank sensor (SF1–SF2) Flow sensor in DHW circuit (VF3) Activate editing mode for sensor. Correct measured temperature. Read the actual temperature directly from the thermometer at the point of measure - ment and enter this value as the reference temperature.
3 Manual operation Heating circuit and DHW circuit (Anl 9: underfloor heating circuit) can be set to manual mode at their operating mode selector switches. Heating circuit mode selector switch The heating circuit can only be set to manual mode when the DHW/underfloor heating circuit mode selector switch is not positioned at .
4 Systems 10 hydraulic schematics are available. System code number (Anl) 12345678 9 * 11 Heating Outdoor temperature dependent flow temperature control with variable return flow temperature limitatio.
System Anl 1 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 Systems 24 EB 5476 EN.
System Anl 2 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF1 FB15 = OFF Without SF2 Systems EB 5476 EN 25.
System Anl 2, setting different from default setting · With switch valve Setting different from default setting: FB9 = ON, select “US“ FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF.
System Anl 2, setting different from default setting · With solar system Setting different from default setting: FB15 = ON, select “CF“ FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With S.
System Anl 3 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF1 FB15 = ON, select “---“ With SF2 FB27 = OFF Without VF3 Systems 28 EB 5476 EN.
System Anl 3, setting different from default setting · With solar system Setting different from default setting: FB15 = ON, select “CF“ FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With S.
System Anl 4 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB21 = OFF Without RüF2 30 EB 5476 EN Systems.
System Anl 4, setting different from default setting · With solar system Setting different from default setting: FB15 = ON FB13 = OFF Without RF FB15 = ON With SF2 FB20 = ON With RüF1 FB21 = OFF Wit.
System Anl 5 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF1 FB15 = ON, select “---“ With SF2 FB21 = OFF Without RüF2 Systems 32 EB 5476 EN.
System Anl 5, setting different from default setting · With solar system Setting different from default setting: FB15 = ON, select “CF“ FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With S.
System Anl 6 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 34 EB 5476 EN Systems.
System Anl 7 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF1 FB15 = OFF Without SF2 EB 5476 EN 35 Systems.
System Anl 8 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF1 FB15 = ON With SF2 FB27 = OFF Without VF3 36 EB 5476 EN Systems.
System Anl 9 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF1 FB15 = OFF Without SF2 EB 5476 EN 37 Systems.
System Anl 9, setting different from default setting · With solar system Setting different from default setting: FB15 = ON, select “CF“ FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With S.
System Anl 11 Default settings FB13 = OFF Without RF FB20 = ON With RüF1 FB14 = ON With SF1 FB15 = ON With SF2 FB21 = OFF Without RüF2 FB27 = OFF Without VF3 EB 5476 EN 39 Systems.
5 Functions of the heating circuit Which controller functions are available depends on the selected system code number (Anl). 5.1 Weather-compensated control When weather-compensated control is used, the flow temperature is controlled according to the outdoor temperature.
Function WE Configuration Outdoor temperature – Current input OFF FB18 = ON 0: 0 to 20 mA = –20 to 50 °C 4: 4 to 20 mA = –20 to 50 °C 5.1.1 Gradient characteristic Basically, the following rule applies: a decrease in the outdoor temperature causes the flow tem - perature to increase.
5.1.2 4-point characteristic The 4-point characteristic allows you to define your own heating characteristic. It is defined by 4 points for the Outdoor temperature , the Flow temperature and the Return flow temperature . The Set-back difference at points 2 and 3 indicates how much the flow temperature is reduced outside the times-of-use.
Parameters WE WE* Range of values Min. flow temperature 20 °C 20 °C 20 to 130 °C * Default setting applies to system Anl 9, floor heating 5.2 Fixed set point control During the times-of-use, the flow temperature can be controlled according to a fixed set point.
5.4 Deactivation depending on outdoor temperature 5.4.1 OT deactivation value in rated operation If the outdoor temperature during rated operation exceeds the limit OT deactivation value in rated operation , the affected heating circuit is put out of service immediately.
Function WE Configuration Summer mode OFF 01.06 30.09 18 °C FB3 = ON Start summer mode / 01.01 to 31.12 Stop summer mode / 01.01 to 31.12 Outdoor temperature limit / 0 to 30 °C 5.5 Delayed outdoor temperature adaptation The calculated outdoor temperature is used to determine the flow temperature set point.
have been activated. Refer to page 78 onwards for the wiring diagrams of the room panels. Functions WE Configuration Room sensor RF OFF FB13 = ON Potentiometer input 1 to 2 k Ω OFF FB24 = OFF 5.7 Optimization This function requires the use of a room sensor.
5.8 Flash adaptation The function is only active in automatic mode ( ). Direct reactions to deviations in room temperature can be achieved using the function block set - ting: FB2 = ON.
5.10 Pump management The Pump management function can be used for the heating circuit (circulation pump UP1). The binary outputs BA8 and BA9 should always be used to control the operation of this pump.
6 Functions of the DHW circuit 6.1 DHW heating in the storage tank system Start storage tank charging The controller begins charging the storage tank when the water temperature measured at sen- sor SF.
DHW heating from the primary circuit (Anl 4): The control valve opens depending on the DHW temperature from its closed position. Stop storage tank charging The controller stops charging the storage tank when the water temperature in the storage tank measured at sensor SF1 reaches the value T = DHW heating ON + Hysteresis .
6.2 DHW heating in the storage tank charging system Start storage tank charging The controller begins charging the storage tank when the water temperature measured at sen- sor SF1 falls below the set .
Stop storage tank charging The controller stops charging the storage tank when the water temperature in the storage tank measured at sensor SF1 reaches the value T = DHW heating ON + Hysteresis .
6.3 DHW heating with solar system (Anl 2, 3, 4, 5 und 9) The systems Anl 2, 3, 4, 5 and 9 include a solar system for DHW heating. In these systems, the difference between the temperatures measured at storage sensor SF2 and the sensor at the so - lar collector CF is determined.
6.5 Circulation pump operation during storage tank charging With the setting FB26 = ON, the circulation pump continues operation according to the pro - grammed time schedule even during storage tank charging. With the setting FB26 = OFF, the circulation pump is switched off as soon as the storage tank charging pump is activated.
Once a parallel pump operation cycle has been activated and the time for Stop parallel opera - tion has elapsed, system deviations greater than 5 °C cause the controller to suspend parallel operation for 10 minutes and to apply priority operation.
Set-back difference by set-back of the current flow temperature. The amount of time in which the priority for the DHW circuit is given is set in the Priority in case of deviation parameter. Function WE Configuration Priority for DHW circuit OFF 10 min FB8 = ON, Ab Priority in case of deviation / 2 to 10 mi n 6.
7 System-wide functions 7.1 Automatic summer time/winter time changeover The clock is automatically adjusted on the last Sunday in March at 2.00h and on the last Sunday in October at 3.00h. Function WE Configuration Summer time/winter time changeover ON FB5 = ON 7.
The measured temperature reading (return flow temperature) and the set point reading (flow temperature of the heating, charging temperature) blink to indicate that a return flow limitation is active in the control circuit concerned.
7.5 Condensate accumulation control Activate the Limitation of the system deviation for OPEN signal function to start up condensate accumulation plants, in particular to avoid problematic excess temperatures. The controller re - sponse to set point deviations which cause the primary valve to open is attenuated.
7.7 On/off control The flow temperature can be controlled by an on/off signal. The controlled valve is opened when the flow temperature falls below the set point by T = 0.5 x Hysteresis . When the flow tem - perature exceeds the set point by T = 0.5 x Hysteresis , the control valve is closed.
Note! The function cannot be selected in systems Anl 4, 5 and 9 with solar system and in system Anl 11 with VF3. 7.10 Flow rate/capacity limitation Flow rate/capacity limitation can be implemented based on a pulse or standardized signal of 0/4 to 20 mA provided by the heat meter.
Functions WE Configuration Current input for flow rate measurement OFF FB22 = OFF Flow rate or capacity limitation OFF 500 pulse/h 1.0 500 pulse/h 1.0 FB23 = ON Max. limit / 3 to 500 pulse/h Limiting factor / 0.1 to 10 Max. limit for DH W/3t o5 0 0 pulse/h Limiting factor / 0.
switches were set to “Night mode” or Heating circuit(s) deactivated” or “DHW heating un - changed”. Function WE Configuration Locking manual levels OFF FB34 = ON 7.12 Setting a customized key number Switch to the parameter level. Display shows: Time, blinks Switch to the configuration level.
8 Operational faults Malfunctions or faults are indicated by the icon blinking on the display. 8.1 Sensor failure The following list explains how the controller responds to the failure of the different sensors. Safety functions such as frost protection and excess temperature protection no longer work when a sensor fails.
8.3 Temperature monitoring Should a deviation arise in a control circuit that is greater than 10 °C for longer than 30 min - utes, the bit D12 is automatically set in the error status register. If this function is not required, configure FB36 = ON, select “steig“ and leave the input BE8 unswitched.
Example of a transfer to the control system: The error status register is transferred as a word <w> in a holding register (HR) whose value is calculated as follows: <w> = D_0 + D_1 + … +.
9.1 Controller with RS-232-C port The system bus connection is located at the back of the controller housing (RJ-12 jack). In this case, the controller can be connected either directly to the serial interface of a PC (point-to-point connection) or to a (dial-up) modem.
Functions WE Configuration Modem operation OFF 8 bit 30 min 5 min 5 min PULS – FB44 = ON 8 bit/16 bit Cyclical initialization In* / 0 to 255 min Dialing pause to GLT PA* / 0 to 255 min Modem timeout t 0 * / 0 to 99 min Dial procedure / PULS/ton Phone no.
If you wish to use more than 32 devices in line or need to bridge greater distances, make sure repeaters (e.g. TROVIS 5482) are installed to replicate the signal. With 8-bit addressing, a maximum of 246 devices can be addressed and connected to a bus.
Modem time-out (t 0 ) When the controller connects to the GLT but without addressing a Modbus data point, the con - nection is closed after the time specified for Modem time-out has elapsed.
Note! A 15 V DC supply voltage (+15 V at terminal 15 connected to the meter bus connection terminal 3) can be used at the WMZ connection of TROVIS 5476 Controller when the red jumper on the back of the controller is located pointing towards the edge of the controller (Fig.
for details on which listed heat meters fulfill this criterion and can be used for limitation pur - poses. In case of battery-operated heat meters in particular, please note that some makes react with communication intervals if they are polled too frequently.
Function WE Configuration Flow rate limitation OFF 2.0 m h 3 2.0 m h 3 2.0 m h 3 2.0 m h 3 1.0 FB30 = ON At/--- Maximum limit / 0.01 to 650 m h 3 Maximum limit for heating* / 0.01 to 650 m h 3 Maximum limit for DHW / 0.01 to 650 m h 3 Minimum limit/ 0.
Parameter * WE Range of values * Parameter only needs setting with FB31 = ON, select “At“ 9.5 Memory module The use of a memory module (accessory no. 1400-7142) is particularly useful to transfer all data from one TROVIS 5476 Controller to several other TROVIS 5476 Controllers.
EB 5476 EN 75 Installation Fig. 9 · Installation Panel mounting Wall mounting Top hat rail mounting Back of the controller 2 Controller housing 2 1 Dimensions in mm: W x H x D = 144 x 96 x 125.
11 Electrical connection Caution! For electrical installation, you are required to observe the relevant electrotechnical regulations of the country of use as well as the regulations of the local power suppliers.
Connecting the sensors Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the back panel of the housing. Connecting the actuators Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the control - ler output.
Systems Anl 1 to 3 System Anl 4 78 EB 5476 EN Electrical connection Option: Type 5244 Type 5257-5 Potentiometer 1 to 2 k Ω 1) Free 2) For 0 to 20 mA 50 Ω connected in parallel Option: Type 5244 Type.
Systems Anl 5 to 7 System Anl 8 EB 5476 EN 79 Electrical connection Option: Type 5244 Type 5257-5 Potentiometer 1 to 2 k Ω 1) Free 2) For 0 to 20 mA 50 Ω connected in parallel Option: Type 5244 Type.
System Anl 9 System Anl 11 80 EB 5476 EN Electrical connection Potentiometer 1 to 2 k Ω 1) Free 2) For 0 to 20 mA 50 Ω connected in parallel Option: Type 5244 Type 5257-5 Potentiometer 1 to 2 k Ω 1.
12 Appendix 12.1 Function block list FB Function WE Anl Comments 0 Optimization OFF FB0 = ON: Optimization active; when FB0 = ON also FB13 = ON 1 Adaptation OFF FB1 = ON: Adaptation active; when FB1 =.
FB Function WE Anl Comments 9 Parallel pump operation OFF 2, 3, 9 FB9 = ON: Parallel pump operation Select (Anl 2 and 9): PU: Parallel pump operation US: Operation with switchover valve Function block parameter (on selecting: US): Stop parallel oper.
FB Function WE Anl Comments 16 Sensor selection OFF All FB16 = ON; select: P1000: Pt 1000 and Pt 100 sensors* ntc: NTC and Pt 100 sensors* FB16 = OFF: PTC and Pt 100 sensors* * A mixture of both types.
FB Function WE Anl Comments 22 Current input for flow rate measurement OFF All FB22 = ON: Current input active Select: 0: 0 to 20 mA signal feedforwarding 4: 4 to 20 mA signal feedforwarding A 50- Ω .
FB Function WE Anl Comments 29 (5) Meter bus OFF All FB29 = ON: Meter bus communication activated Function block parameters WMZ 1 to 3: Meter bus address / 0 to 255 (WMZ1: 254; WMZ2, 3: 255) Model cod.
FB Function WE Anl Comments 36 (12) to 43 (19) BE8 to BE1 All FB36 to 43 = ON: Binary input in error status register Select: StEIG: Fault indicated by rising edge/make contact FALL: Fault indicated by.
12.2 Parameter list Display Parameter designation Range of values (default values) Gradient, flow 0.2 to 3.2 (1.8) Level, flow –30 to 30 °C (0 °C) 4-point characteristic Press key to set parameter.
Display Parameter designation Range of values (default values) 4-point characteristic, flow temperature Flow temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4 20 to 13.
Display Parameter designation Range of values (default values) Maximum flow temperature 20 to 130 °C (90 °C) Minimum flow temperature 20 to 130 °C (20 °C) Set-back difference 0 to 50 °C (15 °C) .
Display Parameter designation Range of values (default values) Reduced room set point 0 to 40 °C (17 °C) Sustained temperature 0 to 40 °C (15 °C) Gradient of the heating characteristic, return flow 0.
Display Parameter designation Range of values (default values) Min. return flow temperature 20 to 90 °C (65 °C) Can only be set after entering the key number! OT deactivation value in rated operation 0 to 50 °C (22 °C) Times-of-use for heating circuit –> section 1.
Display Parameter designation Range of values (default values) System Anl 9, underfloor heating circuit Gradient, flow 0.2 to 3.2 (0.8) Level, flow –30 to 30 °C (–5 °C) 4-point characteristic Press key to set parameters outdoor temperature, point 1 to 4 flow temperature, point 1 to 4.
Display Parameter designation Range of values (default values) 4-point characteristic, flow temperature Flow temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4.
Display Parameter designation Range of values (default values) Times-of-use for underfloor heating circuit –> section 1.6 DHW heating DHW heating ON 20 to 90 °C (45 °C) With systems Anl 2, 3, 5.
Display Parameter designation Range of values (default values) DHW heating OFF 20 to 90 °C (50 °C) With systems Anl 2, 3, 5, 7, 8, 9 and 11 with two storage tank sensors SF1 and SF2 DHW set point 20.
Display Parameter designation Range of values (default values) Heat exchanger inlet temperature limit 20 to 130 °C (120 °C) Time schedule for DHW heating –> section 1.
Display Parameter designation Range of values (default values) Solar charging OFF 20 to 90 °C (70 °C) Station address (ST-NO) 1 to 247, 8 bit (255) 1 to 999, 16 bit (255) Baud rate (BAUD) 150 to 9600 (9600) EB 5476 EN 97 Appendix 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ST .
12.3 Sensor resistance tables Resistance values with PTC resistors Type 5224 Outdoor Temperature Sensors, Type 5264 and Type 5265 Flow and Return Flow Temperature Sensors, Type 5264 Storage Tank Tempe.
12.4 Technical data Inputs 7 configurable inputs for sensors (Pt 100 and PTC or Pt 100 and Pt 1000 or Pt 100 and NTC) or binary alarms 1 outdoor temperature input for sensor or current signal 4 (0) to.
12.5 Customer data Station Operator Relevant SAMSON office System code number Function block settings 0123456789 1 0 1 1 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 3.
Function block parameters Range of values Pump lag time (FB10 = ON) 1 x T Y to 10 x T Y Hysteresis (FB10 = AUS) 1 to 30 °C Max. system deviation (FB11 = ON) 2 to 10 °C Max. system deviation (FB12 = ON) 2 to 10 °C Proportional gain K P (FB17 = ON) 0.
Function block parameters Range of values Maximum limit (FB31= ON) 0.1 to 6000 kW Maximum limit for heating (FB31 = ON) 0.1 to 6000 kW Maximum limit for DHW (FB31 = ON) 0.
Parameters Range of values Set-back difference – – 0 to 50 °C Max. flow temperature 20 to 130 °C Min. flow temperature 20 to 130 °C Set-back difference 0 to 50 °C OT deactivation value in red. operation –10 to 50 °C Room set point 0 to 40 °C Reduced room set point 0 to 40 °C Sustained temperature 0 to 40 °C Gradient, return flow 0.
Parameters Range of values Return flow limitation temperature during DHW heating 20 to 90 °C Heat exchanger inlet temp. limit 20 to 130 °C Solar circuit pump ON 0 to 30 °C Solar circuit pump OFF 0 .
Time schedules for DHW circuit and circulation pump DHW circuit Circulation pump Start – Stop (1) Start – Stop (2) Start – Stop (1) Start – Stop (2) Monday (1) Tuesday (2) Wednesday (3) Thursd.
106 EB 5476 EN Appendix Key number 1732.
EB 5476 EN 107 Appendix.
Index 4-point characteristic . . . . . . . . . . . . . . . 42 A Adaptation . . . . . . . . . . . . . . . . . . . . . . 47 Automatic mode. . . . . . . . . . . . . . . . . . . . 8 B Baud rate . . . . . . . . . . . . . . . . . . . . . . . 69 Binary input BE1 .
I Installation Panel mounting. . . . . . . . . . . . . . . . . 74 Top hat rail mounting . . . . . . . . . . . . 74 Wall mounting . . . . . . . . . . . . . . . . . 74 Interface Meter bus. . . . . . . . . . . . . . . . . . . . . 70 RS-232-C . . . . . . .
S Sensor calibration . . . . . . . . . . . . . . . . . 20 Sensor failure . . . . . . . . . . . . . . . . . . . . 64 Set-back operation priority through . . . . . . . . . . . . . . . . 55 Start-up . . . . . . . . . . . . . . . . . . . . . 17 - 21 Station address .
EB 5476 EN 111.
112 EB 5476 EN Fig. 11 · Level structure of TROVIS 5476 or Operating level (refer to section 1 for operation) or Parameter level (refer to section 2) or Configuration level (refer to section 2) 00:00.
.
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.
Ein wichtiger Punkt beim Kauf des Geräts Samson 5476 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Samson 5476 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Samson 5476 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Samson 5476 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Samson 5476 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Samson 5476 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Samson 5476 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Samson 5476. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Samson 5476 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.