FORM NO. S1 1-933 REV . 2 Supersedes Form No. S1 1-933 Rev . 1 RSNA-B SUPER HIGH EFFICIENCY 1 3-SEER SERIES NOMINAL SIZES 2-5 TONS [7 .0-1 7 .6 kW] P ACKAGE A IR C ONDITIONERS.
2 T ABLE OF CONTENTS Unit Features & Benefits ..............................................................................3-4 Model Identification Options ..........................................................................5 - 6 General Data RSNA-B Series .
3 UNIT FEA TURES & BENEFITS—RSNA-B These qualit y feature s are inc luded in the Rhe em P acka ge Air Conditioner 5.
4 UNIT FEA TURES & BENEFITS—RSNA-B SERIES 1. All models feature Copeland ® Scroll ® compressors for maxi- mum efficiency and quiet operation. 2. Louvered condenser compartment for protecting the coil against yard hazards and/or weather extremes.
R S N A — B 036 J K 010 X X Factory Installed Options (See Next Page) Heating Capacity (Factory Installed) 000 = No Resistance Heat 005 = 05 KW Resistance Heat (018-030) 010 = 10 KW Resistance Heat .
6 OPTIONS—RSNA-B SERIES Option Code Side Flow AA No Option AK x F A CT OR Y INST ALLED OPTION CODES Example: RSNA-B036JK000 XX (where XX is factory installed option) Example: No Options RSNA-B036JK000 Example: Options with Sideflow RSNA-B036JK000AK Note: Factory installed economizer is not available on these models.
7 GENERAL DA T A—RSNA-B SERIES Model RSNA-B Series B024JK B030JK B036CK B036JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 24,800 [7.27] 31,200 [9.
8 GENERAL DA T A—RSNA-B SERIES Model RSNA-B Series B042CK B042JK B048CK B048JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 42,500 [12.45] 42,500 [12.
9 GENERAL DA T A—RSNA-B SERIES Model RSNA-B Series B060CK B060JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 60,000 [17.58] 60,000 [17.58] EER/SEER 2 11.1/13 11.1/13 Nominal CFM/ARI Rated CFM [L/s] 2000/1850 [897/873] 2000/1850 [897/873] ARI Net Cooling Capacity Btu [kW] 58,000 [16.
10 GENERAL DA T A—RSNA-B SERIES NO TES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat.
11 SYSTEMS PERFORMANCE—RSNA-B SERIES GR OSS SYSTEMS PERFORMANCE D A T A—RSNA-B024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] DR ➀ .
12 SYSTEMS PERFORMANCE—RSNA-B SERIES GR OSS SYSTEMS PERFORMANCE D A T A—RSNA-B036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] DR ➀ .
GR OSS SYSTEMS PERFORMANCE D A T A—RSNA-B048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] DR ➀ .
INDOOR AIRFLO W PERFORMANCE—208 V OL TS External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil Nominal Cooling Capacity T ons [kW] Motor Speed from Factory Motor Speed RPM 730 775 820 865 905 940 0.
15 AIRFLOW PERFORMANCE—RSNA-B SERIES INDOOR AIRFLO W PERFORMANCE—230 V OL TS External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—230 Volts Side Discharge—Wet Coil Bl.
ELECTRICAL DA T A – RSNA-B SERIES Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size 16/16 20/20 Maximum Overcurrent Protection Device Size 25/25 Compressor Motor No. 1 Volts 208/230 Phase 1 HP 2 1/6 RPM 3450 Amps (RLA) 10.4/10.4 Amps (LRA) Unit Information Unit Operating Voltage Range 54/54 187-253 Condenser Motor No.
B024JK No Heat — — 16/16 20/25 20/25 A10J 24.57/32.76 34.6/40.0 45/52 45/45 60/60 A05J 12.28/16.38 17.3/20.0 24/27 25/25 30/30 44/50 45/50 — — — — — 16/16 20/25 20/25 22/25 25/25 — — — RXQJ- Heater Kit Nominal kW Heater KBTU/Hr @ 208/240 V Heater Amp.
30% 2% 21% 2% 29% 2% 20% 2% CORNER WEIGHTS % OF TO T AL UNIT WEIGHT THERMOST A T WIRING ENTRANCE ELECTRICAL POWER ENTRANCE BLOWER/ EV APORA T OR ACCESS P ANEL SIDE SUPPL Y DUCT OPENING SIDE RETURN DUC.
52 7 / 16 " [1332 mm] FIL TER ACCESS P ANEL (FOR UNIT MOUNTED FIL TER ACCESSOR Y BLOWER/ EV APORA TOR ACCESS P ANEL OUTDOOR COIL PROTECTIVE GRILLE 25 5 / 16 " [643 mm] 10 3 / 16 " [259 mm] 4 3 / 4 " [121 mm] 5 1 / 16 " [129 mm] 1 1 / 8 " [28.
20 TYPICAL INST ALLA TIONS.
COMMON SUPPL Y/RETURN CONCENTRIC AIR DIFFUSER SUPPL Y AIR/PERFORMANCE NO TE: The location of the combination supply and return diffuser should not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM [472 L/s] or less and 12 [3.66 m] to 14 feet [4.
DUCT AD APTERS RECT ANGULAR T O R OUND TRANSITIONS (DO WNFLO W) RXMC-CA03 RXMC-CA02 [ ] Designates Metric Con versions 22 ACCESSORIES.
[ ] Designates Metric Con versions RXRE-CAA30 (3 P osition) Provided with enthalpy control, and mixed air sensor . Settings include fully open, fully closed and adjustable mid point.
CFM [L/s] RSNA-B 680 [321] RSNA-B 850 [401] RSNA-B 1020 [481] RSNA-B 1190 [562] RSNA-B 1275 [602] 1500 [708] 1400 [661] 1200 [566] 1000 [472] 800 [378] 1650 [779] 1540 [727] 1320 [623] 1100 [519] 880 [415] Minimum Airflow Model No. Nominal Airflow Maximum Airflow 510 [241] RSNA-B 600 [283] 660 [311] Airflow Pressure Drop, Inches W .
DUCT AD APTER SIDEFLO W SQU ARE T O R OUND TRANSITION RXMC-B A01 Adapts the side rectangular supply and return openings to 14" [356 mm] diameter round openings. Adapters provided with same finish as unit and also provided with thermal insulation.
RXSG-AAA 14 (1 4" [356 mm] High) RXSG-AAA08 (8" [203 mm] High) R OOFCURB (Full P erimeter) RXSG-AAA08, RXSG-AAA 1 4 and RXSG-AAA24 for RSNA-B Series Hinged corners make for fast, easy set-up. NO T f or use with RQKA/RQLA/RQMA P acka ge Heat Pumps.
R OOFCURB (Full P erimeter) (Cont.) [ ] Designates Metric Con versions RXSG-AAA24 (24" [610 mm] High) 27 ACCESSORIES.
[ ] Designates Metric Con versions P A CKA GE AIR CONDITIONERS & GAS/ELECTRIC P A CKA GE UNITS R OOFCURB INST ALLA TION (Full P erimeter) OLD MODEL OLD CURB MODEL NEW MODEL TO OLD MODEL ROOFCURB A.
LIFT KIT—MODEL NO . RXML-A01 The lift kit is intended for temporary installation while the unit is being lifted into position. Kit includes 4 lift brackets.
W ARNING ONL Y ELECTRIC HEA TER KITS SUPPLIED BY THIS MANUF ACTURER AS DESCRIBED IN THIS PUBLICA TION HA VE BEEN DESIGNED, TESTED, AND EV ALU A TED BY A NA TIONALL Y RECOGNIZED SAFETY TESTING A GENCY FOR USE WITH THIS UNIT .
31 WIRING SCHEMA TICS—RSNA-B SERIES.
32 WIRING SCHEMA TICS—RSNA-B SERIES.
33 WIRING SCHEMA TICS—RSNA-B SERIES.
34 WIRING SCHEMA TICS—RSNA-B SERIES.
35 WIRING SCHEMA TICS—RSNA-B SERIES.
36 WIRING SCHEMA TICS—RSNA-B SERIES.
37 NOTES.
38 NOTES.
39 NOTES.
Before pr oceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Pro vincial, and Local codes, regulations, and practices.
Ein wichtiger Punkt beim Kauf des Geräts Rheem RSNA-B Series (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Rheem RSNA-B Series noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Rheem RSNA-B Series - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Rheem RSNA-B Series reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Rheem RSNA-B Series erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Rheem RSNA-B Series besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Rheem RSNA-B Series verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Rheem RSNA-B Series. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Rheem RSNA-B Series gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.