Benutzeranleitung / Produktwartung Hot Water Energy Management Control des Produzenten Raypak
Zur Seite of 30
INST ALLA TION AND OPERA TING INSTRUCTIONS RayT emp™ Hot W ater Energy Management Contr ol Catalog No: 5000.61B Effective: 04-15-05 Replaces: 09-01-02 P/N 241098.
2 Section 1. GETTING ST ARTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 THE BIG PICTURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 WHA T COMES WITH THE CONTROLL .
3 THE BIG PICTURE This RayT emp control is designed to make recirculating domestic hot water heating systems ener gy efficient. In a r ecirculating sys- tem, hot water is continuously pumped throughout the building. This lar ge loop has many branch- es which extend to fixtures in the rooms.
4 WHA T COMES WITH THE CONTROL Before arriving at the job site to begin the installation, it’ s important to first inspect the system and determine what materials you will need. Some parts are included with the control while the oth- ers you will need to provide.
5 On the sensor end, roll the shielding and tape so it will not contact a conductor . On the control end, the shield should be grounded. Do not ground both ends of the shielding. A void routing wiring on or near other electrical wires, conduit, motors, spark igniters or other sources of high, intermittent voltage or current.
6 Fig # 8285.2 INST ALLA TION LA YOUT.
7 ”DIP” SWITCH SETTINGS ON CIRCUIT BOARD CAUTION: Incorrect DIP switch settings may damage the RayT emp!!! Make all adjustments with ALL power off. The four relay outputs are factory set for normally closed dry contacts. These DIP switches ar e located behind the terminal block, on the right side.
CONNECTING THE OPTIONAL “ELSA” BRAND MODEM Raypak recommends the ELSA Microlink 56k modem for data communication. This modem will work with RayT emp and technical support will be provided if this modem is installed with the cor- rect cables. Raypak will not be able to provide support if you use other modem brands or build your own cables.
9 USING THE FRONT P ANEL TO CHECK SENSORS AND RELA YS The RayT emp front panel features an alphanumeric LCD display of four r ows by 20 lines. Six keys are provided to select scr eens, fields, and make pr ogram changes. The up-arrow and down-arr ow "WINDOW" keys are used to step thru each of the screens.
10 Section 3. CONNECTING A COMPUTER This section explains how to connect your personal computer to the RayT emp. Once connected, you can view all of the front panel screens cover ed in the previous section. Y ou can also retrieve the recorded data and view color graphs of temperatur e and demand profiles.
11 INST ALLING PTT SOFTW ARE ON YOUR PC This section provides instructions for installing PTT communication software. First insert the PTT CD into your CD drive. Double click on the folder Ptt258 then double click on Install. The PTT communication software will then be installed on your C:GBX subdirectory .
12 READING LOGGED DA T A Under the "History Report" menu item, logged data can be retrieved from a RayT emp control, saved to a disk file, viewed graphically on screen, or output to a printer . T o retrieve history , con- nect the RayT emp serial cable between the RayT emp and your laptop PC.
13 T o end the modem session, select the following screen in the LapT op window . This screen is used to terminate the call. The RayT emp will actually terminate the phone connection and prevent the modem from answering the phone for about five minutes.
14 Section 4. PROGRAMMING QUICK REFERENCE This section describes all the programmable features of the contr ol. Y ou make program changes from the front panel or by using a laptop. For information on connection with a LapT op using PTT software, refer to the pr evious section.
15 Screen code and description, in sequence of appearance See page FM PRODUCT IDENTIFICA TION - Model, type, and version 17 SE SENSORS - Displays temperature of each standard sensor 17 OS OPTIONAL SEN.
16 Screen Code and Description - continued See page HL SELECT - Supply High Limit 20 LL SELECT - Supply Low Limit 20 DW SELECT - Demand window in minutes 20 DM SELECT - Demand % for maximum temperatur.
17 FIRST SCREEN A T POWER-UP FM PRODUCT IDENTIFICA TION. This screen displays the model number , type of control, copyright notice, and software version number . Press F2 to select the next screen in or der , or press two keys for direct access to any one of the following screens.
18 ERASE MEMORY / RESET PROGRAM ER ERASE/RESET - Press F4 or F5 to select which item will be r eset or cleared, then press CTRL+E to confirm each action. Set BAUD Rate will reconfigure the serial port accor ding to the BA screen. If the speed is differ- ent, then reset the BAUD rate on your LapT op (garbage characters will appear).
19 TIME SCHEDULE TS TIME SCHEDULE This is a seven-day time clock. Each line is a program for starting a new period (such as Night) on a day (such as M-F) and at a time (such as 6:00 am). Up to 20 lines can be displayed or programmed using the SP ACE, F4 and F5 keys.
20 C6 SELECT - Maximum Extra T emperature C6 and C7 are an extra set of temperatures which can be scheduled for any purpose. They will become the maximum and minimum supply temperature if the Extra schedule is activated by the time clock. Default T emp 140°F .
21 RETURN TEMPERA TURE The return sensor is used to compensate for seasonal changes in loop heat loss. The strategy may raise the supply/branch temperature in cold weather to ensure that the last r ooms on the loop have hot enough water even during low demand periods.
22 BRANCH TEMPERA TURE - NOT USED B0 SELECT - # of Branch Sensors Installed Not used. RELA Y SEQUENCING HS SELECT - # of Heaters Enter 1 thru 4 for the number of heaters connected to relay out- puts 1 thru 4. This allows the RayT emp to correctly sequence heaters and recor d demand.
23 DD SELECT - Differential Increasing DD lengthens the heater burn cycle; decr easing DD improves temperature stability . For instance: desired=140, deadband=1, heater turns off at 141 and on at 139.
24 SA VINGS TEST SETUP S1 SELECT - Day of Month for Savings T est Selecting a value other than 0 (default) acti- vates the flip-flop savings test. This test will cause a simulation of conditions before the RayT emp was installed - for 24 hours on the day specified every month.
25 T otal days in service displays the total operating days in modes RUN, BYP ASS, and OFF . When 24 V AC power is absent this value will not increase however the clock will still operate. Number of power interruptions value is incremented each time 24 V AC power is removed or inter- rupted.
26 LOCA TION TEXT DN TEXT - Company Name Accepts entry of company name into RayT emp memory . This information will appear in installation reports. Edit with SP ACE, BACKSP , F4, and F5. PN TEXT - Property Name Accepts entry of site name into RayT emp memory .
27 F AX MODEM SETUP AND TEST FD TEXT - Fax Dial-Out Use this screen to enter the phone number of the fax machine which is to receive fax alarm messages, installation reports, and/or graphics. Example "A TDT5551212". Edit text with SP ACE, BACKSP , F4, and F5.
28 XH V ALUE - Fax on Hour of Day This option sets the time of day to transmit fax reports. It works in conjunction with XW and XM, above. The RayT emp will attempt to fax the specified data on the specified day (above) and at this specified time. Military time is used with values of 0 to 23, 12 is noon.
29 W ARRANTY The Raypak RayT emp Control is warranted to be free from defects in material and workmanship for a peri- od of one year from the date of installation or fourteen months from date of shipment, whichever occurs first.
Raypak Inc., 2151 Eastman A venue, Oxnard, CA 93030 • (805) 278-5300 • (800) 872-9725 www .raypak.com.
Ein wichtiger Punkt beim Kauf des Geräts Raypak Hot Water Energy Management Control (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Raypak Hot Water Energy Management Control noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Raypak Hot Water Energy Management Control - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Raypak Hot Water Energy Management Control reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Raypak Hot Water Energy Management Control erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Raypak Hot Water Energy Management Control besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Raypak Hot Water Energy Management Control verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Raypak Hot Water Energy Management Control. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Raypak Hot Water Energy Management Control gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.