PV500 - 17 05 - 2000 Section 17 1 INSTALLATION & MAINTENANCE MANUAL FOR MAXIM INTEGRATED WATER HEATING SYSTEM TABLE OF CONTENTS Start - up Procedures 2 Maintenance & Safety Inspections 3 - 5 Wiring Diagrams 6,7 Burner 8 Burner Start - up 9 - 12 Burner Troubleshooting 13.
PV500 - 17 05 - 2000 Section 17 2 START - UP PROCEDURES CAUTION: DO NOT RELIGHT PILOT OR START BURNER WITH COMBUSTION CHAMBER FULL OF GAS OR OI L VAPOR, OR WITH VERY HOT COMBUSTION CHAMBER. 1. Study the burner start - up information included in this manual carefully.
PV500 - 17 05 - 2000 Section 17 3 MAXIM MAINTENANCE AND SAFETY INSPECTIONS 1. Establ ish a preventive maintenance program to assure a longer water heater life. 2. The tank should be flushed at two - or three - month intervals depending on water conditions in your location.
PV500 - 17 05 - 2000 Section 17 4 MAXIM MAINTENANCE AND SAFETY INSPECTIONS (continued) Periodic Inspection of Operation Components (continued) CAUTION: THE RELIEF VA LVE IS A PRIMARY SAFETY DEVICE.
PV500 - 17 05 - 2000 Section 17 5 MAINTENANCE & SAFETY INSPECTION REPORT DATE BURNER INSPECTION COMBUSTION ANALYSIS TANK INSPECTION TANK FLUSH & CLEANOUT TANK FITTING INSPECTION VENT INSPECTIO.
PV500 - 17 05 - 2000 Section 17 6 MAXIM AXIAL FLOW GAS BURNER CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a s easonal or annual combustion check - out be performed by a qualified service agency to ensure safe and efficient operation.
PV500 - 17 05 - 2000 Section 17 7 MAXIM AXIAL FLOW GAS BURNER START - UP (Refer to Figure 17 - 2, page 6 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. A wiring diagram, included in this packet, will show the controls used in our circuitry.
PV500 - 17 05 - 2000 Section 17 8 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) PRESSURE PLATE Set up and Tolerances Figure 17 - 3 13. Connect a test meter to the control for reading the flame response signal. NOTE: Some controls read the flame signal in micro amps and some in volts DC.
PV500 - 17 05 - 2000 Section 17 9 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) This section pertains to MC120 control only. When the blower motor starts, the air proving light on the MC - 120 should be on. This indicates a positive air flow condition.
PV500 - 17 05 - 2000 Section 17 10 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) 17. Check flue gases with a flue analyzer to make final settings of the air shutter. a. The readings need to be taken from a hole in the vent several inches above the heater vent connection, but before draft regulator.
PV500 - 17 05 - 2000 Section 17 11 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER 1. BURNER FAILS TO START Defective On/Off switch. Replace switch. A. Control circuit has an open control contact. Check limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 17 05 - 2000 Section 17 12 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER (continued) C. Defective automatic main or auxiliary gas shut off valves. Check electrical circuitry to valves. Replace valves or correct circuitry a s required.
Ein wichtiger Punkt beim Kauf des Geräts PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.