107 W. Main Street Worthington, PA 16262 Phone: 724.297.3416 Fax: 724.297.5189 h t t p :/ / www.a ir ta k. c o m OPERATING INSTRUCTIONS Refrigerated Air Dryers Models D-320 through D-10,000 4-2002.
2 Contents A. INTRODUCTION B. RECEIVING C. LOCATION D. FOUNDATION E. PIPING F. ELECTRICAL G. COMPRESSED AIR CIRCUIT 1. Air to Air Heat Exchanger 2. Air to Refrigerant Heat Exchanger (Evaporator) 3. Drain Traps H. REFRIGERANT CIRCUIT 1. Refrigerant Compressor 2.
3 A. INTRODUCTION AIR/TAK Refrigerated Compressed Air Dryers are of the hi gh-efficiency type, designed to effectively remove moisture from compressed air by means of a refrigerat ion process. The compressed air pressure dewpoint is reduced to 38°F and then reheated to prevent in-plant air lines from sweating.
4 In keeping with good compressed air piping design, the air dryer should be installed on the downstream side of the air receiver and aftercooler. An AIR/TAK prefilter(s) for oil and dirt removal in stalled at the inlet of the dryer is recommended.
5 G. COMPRESSED AIR CIRCUIT 1. Air-to-Air Heat Exchanger: This unique high-efficiency heat exchanger is of a finned shell and tube design. The tubes are of high quality copper and are enhanced by outer fins of corrugated aluminum .
6 The circuiting within the evaporator is serpent ined in such a manner as to guarantee a completely flooded evaporator. Each evaporator is designed to insure adequat e refrigerant velocity to eliminate the problem of oil return to the crankcase. 4. Expansion Valves: The thermostatic expansion valve (TXV) is used on Model D-320-A, and larger.
7 10. Oil Sightglass: The oil sightglass is found on the side of the cr ankcase on accessible scroll compressors to provide a visual means of checking the oil level. The oil must be checked only while the compressor is in operation. During compressor operation the oil sight glass should be approximately 1/2 full.
8 I. START-UP After the installation of your air dryer at a su itable location, the following checks should be made: a) Bypass piping installed and valves set to bypass the dryer.
9 J. DESIGN CONDITIONS Each dryer is shipped complete and ready for installation. Every dryer is tested and preset at the factory for optimum service at the design conditions. The following ar e the standard design conditions for a refrigerated dryer operating at 60 HZ: 38°F (3.
10 Cooling Water Requirements MODEL # HEAT TO COOLING WATER KW INPUT (4) COOLING WATER AMBIENT (1) GPM (2) GPM (3) D-400-W 23682 1780 4.7 1.9 1.95 D-500-W 33894 2550 6.8 2.7 2.6 D-600-W 37250 3650 7.5 3.0 2.92 D-800-W 52859 3980 10.6 4.3 4.22 D-1000-W 66150 5360 13.
11 SYMPTOMS PROBABLE CAUSE REMEDY Dryer not running. a. Disconnect open. a. Close disconnect. High temperature light off, analyzer gauge normal. b. Fuse blown. b. Replace fuse. c. Wiring, improper or broken. c. Check wiring diagram or repair. d. Control transformer d.
12 SYMPTOMS PROBABLE CAUSE REMEDY g. Defective refrigerant g. Repair or replace compressor valves. compressor. h. Suction pressure too high. h. Adjust hot gas bypass valve. Dryer running. a. Leaky refrigerant circuitry. a. Locate and repair. High temperature light on, analyzer gauge pressure low.
13 High pressure drop across a. Excess flow. a. Dryer undersized. dryer inlet and outlet. Replace with larger dryer. b. Low air pressure. b. Dryer undersized. Replace with larger dryer. c. Partially frozen. c. Shut dryer off until ice melts. Power light “ON” but dryer a.
Ein wichtiger Punkt beim Kauf des Geräts AT&T D-320 (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie AT&T D-320 noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für AT&T D-320 - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von AT&T D-320 reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über AT&T D-320 erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon AT&T D-320 besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von AT&T D-320 verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit AT&T D-320. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei AT&T D-320 gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.