Benutzeranleitung / Produktwartung R410A des Produzenten Panasonic
Zur Seite of 198
85464849303001 REFERENCE NO . SM830203-01 TECHNICAL DATA & SERVICE MANUAL Model No. Outdoor Units Remarks Remarks 42 36 26 42 36 26 Type Type U Single U-26PE1U6 U-36PE1U6 U-42PE1U6 Cooling/Heating.
IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and oper- ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
Check of Density Limit The room in which the air conditioner is to be installed requires a design that in the event of refrig- erant gas leaking out, its density will not exceed a set limit.
Precautions for Installation Using New Refrigerant 1. Care regarding tubing 1-1. Process tubing Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” Tubing size: Be sure to use the sizes indicated in the table below.
iv 3-2. Use R410A exclusive cylinder only. When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change.
vi Section 1: SPECIFICA TIONS ..................................................................................................... 1-1 1-1 Unit SpecifIcations ...........................................................................................
1. SPECIFICA TIONS 1-1. Unit Specifications.................................................................................................... 1-2 1-2. 1-20 Major Component Specifications ..............................................................
1-2 1. Specifications 1-1 Unit Specifications 4-W a y Cassette T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating .
1-3 1. Specifications 1-1 Unit Specifications 4-W ay Cassette T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating c.
1-4 1. Specifications 1-1 Unit Specifications 4-W a y Cassette T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating .
1-5 1. Specifications 1-1 Unit Specifications 4-W ay Cassette T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating c.
1-6 1. Specifications 1-1 Unit Specifications 4-W a y Cassette T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating .
1-7 1. Specifications 1-1 Unit Specifications 4-W ay Cassette T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating c.
1-8 1. Specifications 1-1 Unit Specifications W all Mounted T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating con.
1-9 1. Specifications 1-1 Unit Specifications W all Mounted T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rating con.
1-10 1. Specifications 1-1 Unit Specifications Ceiling T ype S-26PT1U6 t i n U r o o d n I U-26PE1U6 t i n U r o o d t u O POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling Heating Capacity * [minimum~muximum] BTU / h 24,400 [9,500~24,400] 30,800 [8,000~30,800] 0 0 9 , 7 1 h / U T B * * ) F ˚ 7 1 ( Moisture removal (High) Pints / h 7.
1-11 1. Specifications 1-1 Unit Specifications Ceiling T ype S-36PT1U6 t i n U r o o d n I U-36PE1U6 t i n U r o o d t u O POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling Heating Capaci.
1-12 1. Specifications 1-1 Unit Specifications Ceiling T ype S-42PT1U6 t i n U r o o d n I U-42PE1U6 t i n U r o o d t u O POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling Heating Capaci.
1-13 1. Specifications 1-1 Unit Specifications Ceiling T ype S-26PT1U6 t i n U r o o d n I U-26PS1U6 t i n U r o o d t u O POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling Capacity * [minimum~muximum] BTU / h 24,400 [9,500~24,400] (17˚F)** BTU / h 7 .
1-14 1. Specifications 1-1 Unit Specifications Ceiling T ype S-36PT1U6 t i n U r o o d n I U-36PS1U6 t i n U r o o d t u O POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] (17˚F)** BTU / h 0 .
1-15 1. Specifications 1-1 Unit Specifications Ceiling T ype S-42PT1U6 t i n U r o o d n I U-42PS1U6 t i n U r o o d t u O POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling Capacity * [minimum~muximum] BTU / h 39,000 [9,500~39,000] (17˚F)** BTU / h 6 .
1-16 1. Specifications 1-1 Unit Specifications Low Silhouette Duct T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rat.
1-17 1. Specifications 1-1 Unit Specifications Low Silhouette Duct T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rat.
1-18 1. Specifications 1-1 Unit Specifications Low Silhouette Duct T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rat.
1-19 1. Specifications 1-1 Unit Specifications Low Silhouette Duct T ype Cooling: Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB Heating: Rat.
1-20 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-26PU1U6 Source 230 - 208 VAC / 1 phase / 60 Hz R e m o t e controller (Supplied / Optional) Wired / Wireless (See Unit Specifications) Controller P.
1-21 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-36PU1U6 Source 230 - 208 VAC / 1 phase / 60 Hz R e m o t e controller ( Supplied / Optional ) Wired / Wireless (See Unit Specifications) Controller P. C. B Ass'y CR-26PU1U6-P Control circuit fuse 250 VAC, 5 A Fan (Number … diameter) 1 ( o b r u T ) m m ( .
1-22 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-42PU1U6 Source 230 - 208 VAC / 1 phase / 60 Hz R e m o t e controller (Supplied / Optional) Wired / Wireless (See Unit Specifications) Controller P. C. B Ass'y CR-26PU1U6-P Control circuit fuse 250 VAC, 5 A Fan (Number … diameter) 1 ( o b r u T ) m m ( .
1-23 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-26PK1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller ( Optional / Supplied ) Wired / Wireless (See Unit Specifications) Controller P. C. B Ass'y CB-KR254GXH56A A 5 , V 0 5 2 e s u f t i u c r i c l o r t n o C Fan Cross-flow Number .
1-24 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-26PT1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller ( Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan (Number … diameter) in.
1-25 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-36PT1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller ( Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan (Number … diameter) in.
1-26 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-42PT1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller ( Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan (Number … diameter) in.
1-27 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-26PF1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller ( Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan (Number … diameter) in.
1-28 1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No . S-36PF1U6 Source 230 - 208 V / 1 phase / 60 Hz Remote controller ( Supplied / Optional ) Wired / Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan (Number … diameter) in.
1-29 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model.. ..number W t u p t u o l a n i m o N c c l i o r o s s e r p m o C Coil resistance Ω C – R : 0.
1-30 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model.. ..number W t u p t u o l a n i m o N c c l i o r o s s e r p m o C Coil resistance Ω C – R : 0.
1-31 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. Source Controller P .C.B. Ass'y Compressor Model.. ..number W t u p t u o l a n i m o N c c l i o r o s s e r p m o C Coil resistance Ω C – R : 0.169 R – S :0.
1-32 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. Source Controller P.C.B. Ass'y Compressor Model.. ..number W t u p t u o l a n i m o N c c l i o r o s s e r p m o C Coil resistance Ω C – R : 0.665 R – S : 0.
1-33 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. Source Controller P.C.B. Ass'y Compressor Model.. ..number W t u p t u o l a n i m o N c c l i o r o s s e r p m o C C e c n a t s i s e r l i o C – R : 0.665 R – S : 0.
1-34 1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit MODEL No. Source Controller P .C.B. Ass'y Compressor Model.. ..number W t u p t u o l a n i m o N c c l i o r o s s e r p m o C C e c n a t s i s e r l i o C – R : 0.169 R – S :0.
1-35 1. Specifications 1-3 Other Component Specifications Outdoor Unit U-26PE1U6, U-26PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance k Ω 14 ° F:2 3 . 7 , 5 0 ° F : 9.7 23 ° F:1 8 . 8 , 6 8 ° F : 6.5 32 ° F:1 5 . 0 , 8 6 ° F : 4.
1-36 1. Specifications 1-3 Other Component Specifications Outdoor Unit U-36PE1U6, U-36PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance k Ω 14 ° F:2 3 . 7 , 5 0 ° F: 9 . 7 23 ° F:1 8 . 8 , 6 8 ° F: 6 . 5 32 ° F:1 5 . 0 , 8 6 ° F: 4 .
1-37 1. Specifications U-42PE1U6, U-42PS1U6 . o N L E D O M Thermistor (Coil sensor) : TH2 to 5 Coil resistance k Ω 14 ° F:2 3 . 7 , 5 0 ° F: 9 . 7 23 ° F : 18.8 , 68 ° F : 6.5 32 ° F : 15.0 , 86 ° F: 4 . 4 41 ° F : 12.1 , 104 ° F : 3.1 113 ° F: 2 .
1-38 1. Specifications 1-4 Dimensional data Indoor unit : 4-W a y Cassette T ype 26 T ype 33-27/32 3-15/16 30-9/16 19-11/16 19-11/16 12-1/8 1-3/16 4-7/8 15/32 15/32 1-7/8 33-27/32 32-9/32 (Ceiling ope.
1-39 1. Specifications 1-4 Dimensional data Indoor unit : 4-W a y Cassette T ype 36, 42T ype 45-9/32 41-31/32 31-3/32 19-11/16 13-5/16 1-3/16 4-7/8 15/32 15/32 1-7/8 33-27/32 32-9/32 (Ceiling opening).
1-40 1. Specifications 1-4 Dimensional data Dimension : inch Refrigerant liquid line (3/8") Flare connection Refrigerant gas line (5/8") Flare connection Drain hose OD 45/64 Drain and wiring port (3-5/32) Indoor unit : Wall Mounted T ype 1 SM830203-01_PAC-i_US-letter.
1-41 1. Specifications 1-4 Dimensional data Indoor unit : Ceiling T ype 26 T ype Drain connection Drain connection for left side Refrigerant liquid line (3/8") Flare connection Refrigerant gas li.
1-42 1. Specifications 1-4 Dimensional data Indoor unit : Ceiling T ype 36, 42 T ype Drain connection Drain connection for left side Refrigerant liquid line (3/8") Flare connection Refrigerant ga.
1-43 1. Specifications 1-4 Dimensional data Indoor unit : Low Silhouette Duct T ype 26 T ype Refrigerant liquid line (3/8") Flare connection Refrigerant gas line (5/8") Flare connection Upper drain port (O.
1-44 1. Specifications 1-4 Dimensional data Indoor unit : Low Silhouette Duct T ype 36 T ype Refrigerant liquid line (3/8") Flare connection Refrigerant gas line (5/8") Flare connection Upper drain port (O.
1-45 1. Specifications 23/32 1-7/32 F G H G F 11/32 E D B (O.D.) A (Hole) C-ø1/8 (Hole) 1/4 (Hole) 12-1/32 10-1/4 (O.D.) 29/32 7-7/8 1-25/32 5/16 1-25/32 31/32 13/32 2118_U_I 2-ø1/8 13/32 31/32 8-9/.
1-46 1. Specifications 1-4 Dimensional Data (B) Outdoor Unit: U-26PE1U6, U-26PS1U6 U-36PE1U6, U-36PS1U6 1 SM830203-01_PAC-i_US-letter.indb46 46 SM830203-01_PAC-i_US-letter.
1-47 1. Specifications 1-4 Dimensional Data (B) Outdoor Unit: U-42PE1U6, U-42PS1U6 1 SM830203-01_PAC-i_US-letter.indb47 47 SM830203-01_PAC-i_US-letter.
1-48 1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Unit : U-26PE1U6, U-26PS1U6 Indoor Unit : 26, 30, 36 Types U-36PE1U6, U-36PS1U6 SM830203-00_PAC-i_US-letter.indb48 48 2011/11/09 20:22:21 1 SM830203-01_PAC-i_US-letter.indb48 48 SM830203-01_PAC-i_US-letter.
1-49 1. Specifications 1-5 Refrigerant Flow Diagram Outdoor Unit: U-42PE1U6, U-42PS1U6 Indoor Unit: 42 T ype 1-6 Operating Range T emperature Indoor Air Intake Outdoor Air Intake Cooling Maximum 90 °.
1-50 1. Specifications 1-7 Capacity Correction Graph According to Temperature Condition U-26PE1U6, U-26PS1U6 U-36PE1U6, U-36PS1U6 U-42PE1U6, U-42PS1U6 1 SM830203-01_PAC-i_US-letter.
1-51 1. Specifications 1-8 Noise Criterion Curves 4-W ay Cassette T ype MODEL : S-26PU1U6 SOUND LEVEL : HIGH 38 dB(A), NC 31 LOW 31 dB(A), NC 23 CONDITION : Center, Under the unit 4.9 ft. SOURCE : 208 - 230 V, 1 Phase, 60 Hz MODEL : S-42PU1U6 SOUND LEVEL : HIGH 45 dB(A), NC 38 LOW 34 dB(A), NC 27 CONDITION : Center, Under the unit 4.
1-52 1. Specifications 1-8 Noise Criterion Curves W all Mounted T ype SOURCE : 208 - 230 V, 1 Phase, 60 Hz CONDITION : Distance 3.3 ft., Under the unit 3.
1-53 1. Specifications 1-8 Noise Criterion Curves Ceiling T ype MODEL : S-26PT1U6 SOUND LEVEL : HIGH 40 dB(A), NC 34 LOW 36 dB(A), NC 26 CONDITION : Distance 3.3 ft., Under the unit 3.3 ft. SOURCE : 208 - 230 V, 1 Phase, 60 Hz 60 50 40 30 20 10 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.
1-54 1. Specifications 1-8 Noise Criterion Curves Low Silhouette Duct T ype MODEL : S - 2 6PF1U6 SOUND LEVEL : HIGH 34 dB(A), NC 22 / LOW 27 dB(A), NC 18 CONDITION : Under the unit 4.
1-55 1. Specifications 1-8 Noise Criterion Curves Outdoor Units REMARKS: 1. V alue obtained in the actual place where the unit is installed may be slightly higher than the v alues shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors.
1-56 1. Specifications 1-9 Increasing the Fan Speed Jumper cable Jumper cable Electrical component box (At shipment) (Jumper cable installed) 2159_M_I Fan motor socket Fan motor 900 Air Flow (CFM) External Static Pressure 0 50 0 0.
1-57 1. Specifications 1-10 Air throw distance chart 4-W ay Cassette T ype 03 7 1 0 1 3 1 7 2 0 0 3 7 10 13 HORIZONT AL DIST ANCE (ft.) AXIS AIR VELOCITY (ft.
1-58 1. Specifications 1-10 Air throw distance chart W all Mounted T ype COOLING - - - - - HEA TING F AN SPEED HIGH HIGH ROOM AIR TEMP . 80 ° F7 0 ° F FLAP ANGLE 0 ° , 22.5 ° , 45 ° 45 ° , 67.5 ° Axis air velocity (ft./sec.) Vertical distance (ft.
1-59 1. Specifications 1-10 Air throw distance chart Ceiling T ype Model: 26 T ype 03 7 1 0 1 3 1 7 2 0 2 3 2 6 2 9 3 3 0 3 7 10 13 17 HORIZONT AL DIST ANCE (ft.
1-60 1. Specifications 1-11. ELECTRICAL WIRING General Precautions on Wiring (1) as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
1-61 1. Specifications Inter-unit power wiring P ower wiring Inter-unit control wiring 8P terminal board Outdoor Unit Indoor Unit U1 U2 1 2 G L1 L2 Wiring System Diagrams Basic wiring diagram f or standard control NOTE Disconnect s witch may be needed b y the National/Local code.
1-62 1. Specifications WARNING Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.
1-63 1. Specifications 1-12. Installation Instructions 1. Tubing Size Outdoor Unit Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units.
1-64 1. Specifications CAUTION 1. This unit requires no additional refrigerant charge up to 100 ft. tubing length. In case of more than 100 ft., additional refrigerant charge is required. Refer to Table 1-3. 2. In case of multi type installation, indoor units should be installed within the same room.
1-65 1. Specifications 3. SELECTING THE INSTALLATION SITE 3-1. Outdoor Unit AVOID: heat sources, exhaust fans, etc. (Fig. 1-3) damp, humid or uneven locations DO: choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F constantly.
1-66 1. Specifications 3-2. Air-Discharge Chamber for Top Discharge Be sure to install an air discharge chamber in the field when: it is difficult to keep a space of min. 20" between the air discharge outlet and an obstacle. the air discharge outlet is facing a sidewalk and discharged hot air may bother passers-by.
1-67 1. Specifications 3-5. Dimensions of Wind Ducting Reference diagram f or air-dischar ge chamber (fi eld supply) For U-26PE(S)1U6 / U-36PE(S)1U6 unit ① Air discharge chamber ② Air discharge c.
1-68 1. Specifications Dimensions of Outdoor Unit with air-disc harge chamber (fi eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 unit U-42PE(S)1U6 unit 13-3/8 2-17/32 21-13/16 1/2 6-11/16 25-31/32 4-5/16 2 .
1-69 1. Specifications Reference diagram f or air-dischar ge chamber (fi eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 Required space around outdoor unit If the air discharge chamber is used, the space shown belo w must be secured around the outdoor unit.
1-70 1. Specifications 3-6. Dimensions of Snow Ducting Reference diagram f or snow-pr oof vents (fi eld suppl y) For U-26PE(S)1U6 / U-36PE(S)1U6 unit ① Unit top, sno w-proof vent ② Unit left side.
1-71 1. Specifications Dimensions of outdoor unit with snow-pr oof vents (fi eld supply) U-26PE(S)1U6 / U-36PE(S)1U6 unit U-42PE(S)1U6 unit 11-57/64 16-47/64 15-15/16 14-61/64 25/64 19/3 2 25/32 30-5.
1-72 1. Specifications Reference diagram f or snow-pr oof vents – 1 Space requirements for setting – (1) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 ] t i n u f o t n o r f e h t o t e l c a t s b .
1-73 1. Specifications Reference diagram f or snow-pr oof vents – 2 Space requirements for setting – (2) U-26PE(S)1U6 / U-36PE(S)1U6 / U-42PE(S)1U6 [Obstacles to the fr ont and rear of unit] The top and both sides must remain open.
1-74 1. Specifications 4. HO W T O INST ALL THE OUTDOOR UNIT 4-1. Installing the Outdoor Unit Use concrete or a similar material to create the base, and ensure good drainage. Ordinarily , ensure a base height of 2". or more. If a drain pipe is used, or f or use in cold-weather regions, ensure a height of 6".
1-75 1. Specifications 5. SELECTING THE INSTALLATION SITE 5-1. Indoor Unit AVOID: areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. direct sunlight. locations near inverter lamps which may affect the performance of the unit.
1-76 1. Specifications 6. HO W T O INST ALL THE INDOOR UNIT 4-W ay Cassette T ype (U1 T ype) 6-1. Suspending the Indoor Unit This unit uses a drain pump. Use a level gauge to check that the unit is level. 6-2. Preparation f or Suspending (1) Fix the suspension bolts securely in the ceiling using the method shown in the diag rams (Figs.
1-77 1. Specifications 6-3. Placing the Unit Inside the Ceiling (1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts using the supplied full-scale installation diagram. (Fig. 1-15) The size of the opening f or the indoor unit can be confir med b y attaching the full-scale installation diagram beneath the unit.
1-78 1. Specifications 6-4. Installing the Drain Piping (1) Prepare standard hard PVC pipe f or the drain and use the supplied drain hose and hose band to pre- v ent water leaks. The PVC pipe must be purchased separately . The transparent par t allows y ou to check dr ainage.
1-79 1. Specifications 6-5. Checking the Draina g e After wiring and piping are completed, use the follo w- ing procedure to check that the w ater will drain smooth- ly . For this , prepare a buc ket and wiping cloth to catch and wipe up spilled water .
1-80 1. Specifications Ceiling P anel 6-6. Bef ore Installing the Ceiling Panel (1) Remov e the air-intake grille and air filter from the ceiling panel.
1-81 1. Specifications 6-7. Installing the Ceiling P anel (1) Lift the ceiling panel and position it to align the panel hook with the panel catch of the indoor unit. NOTE The ceiling panel must be mounted in the correct direction. Note that the 2 catches of the panel differ in size .
1-82 1. Specifications 6-9. Duct for Fresh Air There is a duct connection part on side of the indoor unit. (Fig. 1-27) (1) Accessories Check that the following parts are in the box when unpacking. (2) Installation Fit the duct connection box into the rectangular hole of air-intake plenum with the accessory screws.
1-83 1. Specifications (d) Installing the ceiling panel Attach the ceiling panel to the air-intake plenum. Drawing the panel downwards sets the panel in position temporarily with the panel catch (at 2 locations). Remove the socket cover of the air-intake plenum and pass the 8P sockets through it.
1-84 1. Specifications W all Mounted T ype (K1 T ype) 6-10. Removing the W all Fixture from the Unit Remove the set screws and take off the rear panel. (Fig. 1-30) NOTE Tubing can be extended in 3 directions as shown in Fig. 1-31. Select the direction that provides the shortest run to the outside unit.
1-85 1. Specifications 6-12. Installing the Rear P anel on the W all Be sure to confirm that the wall is strong enough to suspend the unit. See either Item a) or b) below depending on the wall type. a) If W ooden Wall (1) Attach the rear panel to the wall with the 10 screws pro- vided.
1-86 1. Specifications 6-13. Removing the Grille to Install the Indoor Unit Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, f ollow the steps given below: How to remo ve the grille (1) Set the 2 flaps in the horizontal position.
1-87 1. Specifications 6-15. Wiring Instructions General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit.
1-88 1. Specifications 6-17. Shaping the T ubing (1) Shape the refrigerant tubing so that it can easily go into the hole. (Fig. 1-45) (2) Push the wiring, refrigerant tubing and drain hose through the hole in the wall. Adjust the indoor unit so it is securely seated on the wall fixture.
1-89 1. Specifications Ceiling T ype (T1 T ype) 6-19. Suspending the Indoor Unit (1) Place the full-scale diagram (supplied) on the ceiling at the spot where you want to install the indoor unit.
1-90 1. Specifications (5) Before suspending the indoor unit, remove the 2 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 1-54. Then remove both side panels sliding them along the unit toward the front after removing the two screws which fix them.
1-91 1. Specifications Ceiling surface . x o r p p A h c n i 1 Suspension bolt Washer (supplied) Nut (field supply) Fig. 1-58 Fig. 1-59 Fig. 1-60 (7) Suspend the indoor unit as follows. (a) Mount a washer and two hexagonal nuts on each suspension bolt as shown in Fig.
1-92 1. Specifications 6-20. Duct for Fresh Air There is a duct connection port (knock-out hole) at the right-rear on the panel top of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by knocking it out and connect the duct to the indoor unit through the connection port.
1-93 1. Specifications Low Silhouette Ducted T ype (F1 T ype) 6-22. Required Minimum Space f or Installation and Service This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
1-94 1. Specifications 6-23. Suspending the Indoor Unit Depending on the ceiling type: • Insert suspension bolts as shown in Fig. 1-69 or • Use existing ceiling supports or construct a suitable support as shown in Fig.
1-95 1. Specifications Fig. 1-73 shows an example of installation. 6-24. Installing the Drain Piping (1) Prepare standard hard PVC pipe for the drain and use the supplied hose band to prevent water leaks.
1-96 1. Specifications CA UTION Do not install an air bleeder tube as this ma y cause water to spray fr om the drain pipe outlet. (Fig. 1-76) If it is necessary to increase the height of the drain pipe, the section directly after the connection port can be raised a maximum of 19-11/16".
1-97 1. Specifications 6-26. Increasing the Fan Speed If e xter nal static pressure is too great (due to long e xtension of ducts, f or example), the air flo w volume ma y drop too low at each air outlet.
1-98 1. Specifications 6-27. When Installing the Indoor Unit Confir m that the indoor unit should be installed in a horizontal position. Use the le vel gauge or vinyl tube and chec k e very four corner of the unit is in horizontal. If the air outlet duct flange is positioned with downw ard gradient, there is in danger of water splash or drainage .
1-99 1. Specifications SUPPLEMENT ON DRAIN PIPING Checkpoint after installation After installation of indoor and outdoor units, panels and electrical wiring, check the following items. k r a m e R k c e h C m o t p m y S t n i o p k c e h C 1 Make sure whether indoor and outdoor units are correctly installed.
1-100 1. Specifications 7. HO W T O INST ALL THE WIRELESS REMO TE CONTROLLER IMPORT ANT When using this air conditioner with the wireless remote controller it ma y sometimes be impossible to change the operation modes while other indoor unit is running.
1-101 1. Specifications 7-2. Room T emperature Sensor Setting The room temperature sensors are b uilt into the indoor unit and the wireless remote controller . Either of these room temperature sensors can operate . The system is shipped from the f actor y set to the indoor unit sensor .
1-102 1. Specifications <CZ-R WSU1U> 4-W ay Cassette T ype (U1 T ype) 7-5. Indicator Section Installation Remove the ceiling panel and indicator cover and install the indicator section. (1) Remov e the ceiling panel. (2) Remov e the cor ner cov er behind the mar k section.
1-103 1. Specifications Ceiling T ype (T1 T ype) 7-7. Indicator Section Installation Remov e the side panel to install the indicator section. (Fig. 1-91) (1) Remov e the side panel. Open the air intake g r ille, remo ve the scre w at one place and then remov e the side panel by sliding it tow ard the front (arrow direction).
1-104 1. Specifications 7-9. Electrical Wiring 7-10-1. How to use the test run setting (U1, T1 T ypes) (1) Set DIP s witch [DS] No . 1 on the wireless receiver unit PCB from OFF to the ON position. (2) Press the ON/OFF operation b utton on the wireless remote controller .
1-105 1. Specifications 7-11. Misoperation Alarm Indicators Alar m indicator lamps on the indoor unit indicate the error cause if the air conditioner f ails to operate upon being s witched on. The possible alar m indications are giv en in T able 1-9. Fig.
1-106 1. Specifications <CZ-R WSC1U> CA UTION If the signal receiving unit is installed near a rapid-start or inverter type fluorescent lamp (neither one uses glow lamps), it may be impossible to receive signals fr om the wireless remote controller .
1-107 1. Specifications When using the signal receiving unit on a wall with the front e xposed, choose a wall surf ace that the signal receiving unit can be mounted on. (1) Inser t a fl athead screwdriv er into the slot on the lower side of the signal receiving unit and pr y off the bac k case.
1-108 1. Specifications 7-13. Electrical Wiring CA UTION Be sure to do the wiring correctly (incorrect wiring will damage the equipment). Recommended wire diameter and allowab le length f or signal receiving unit wir ing and its branch wiring: A WG #18, MAX 1,300 ft.
1-109 1. Specifications 7-15. Misoperation Alarm Indicators A blinking lamp f or other than the signal receiving unit fi lter shows that a prob lem has occurred in the unit, so make an inspection. (Refer to servicing information in the ser vice manual, etc.
1-110 1. Specifications 7-16. Basic Wiring Diagram CA UTION Be sure to do the wiring correctly (incorrect wiring will damage the equipment). Wiring procedure Carr y out the wiring according to the abov e wir ing diagram. Address setting is automatically ex ecuted after turning on the system.
1-111 1. Specifications 7-17. Wiring System Diagram for Group Contr ol This diagram sho ws when sev eral units (maximum of 8) are controlled by a signal receiving unit (main unit). In this case, a signal receiving unit can be connected at any indoor unit.
1-112 1. Specifications 7-18. Wiring System Diagram for Multiple Remote Contr ollers T o operate 1 indoor unit with 2 signal receiving units set at diff erent locations. CA UTION Carry out the wiring correctly (incorrect wiring will damage the equipment).
1-113 1. Specifications <CZ-R WSK1U> 7-19. T est Run Procedure W all mounted T ype (K1 T ype) 7-20. Check Items Bef ore the T est Run (1) T ur n ON the remote po wer switch at least 12 hours bef ore the test r un in order to charge the crankcase heater .
1-114 1. Specifications 7-21. Preparing for the T est Run 7-21-1. Changing the room temperature sensor Room temperature sensors are installed inside the indoor unit and the wireless remote controller .
1-115 1. Specifications 7-22. Precautions Request that the customer be present at the time the test r un is perf or med. Explain the Operating Instructions to the customer , and then have the customer actually oper ate the system. Be sure to pass the manual and warranty certifi cate to the customer .
1-116 1. Specifications 7-23. When Setting Indoor Unit Control PCB Switch for W all Mounted Indoor Unit When using both the wired and wireless remote controller , refer to the procedure below . If this setting is not made correctly an alar m will occur .
1-117 1. Specifications 7-24. Diagnosis T able Wired remote Cause E 0 1 E 0 2 E 0 9 E 1 4 E 0 4 E 0 6 E 1 5 E 1 6 E 2 0 P 0 5 L 0 2 P 0 9 dis pla yed L 0 7 displa yed Indoor unit 1:1 connection (single type) Nothing is displa yed Nothing is displa yed displa yed displa yed Operating lamp is blinking.
1-118 1. Specifications 1-13. HOW TO PROCESS TUBING 8. HOW TO INSTALL THE TIMER WIRED REMOTE CONTROLLER The liquid tubing side is connected by a flare nut, and Refer to the Instraction Manual attaehed to the Timer Remote Controller. the gas tubing side is connected by brazing.
1-119 1. Specifications Caution Before Connecting T ubes Tightly (1) Apply a sealing cap or water-proof tape to pre vent dust or w ater from entering the tubes before the y are used. (2) Be sure to apply refrigerant lubricant to the matching surfaces of the fl are and union bef ore connecting them together .
1-120 1. Specifications Do not use a spanner to tighten the valv e stem caps. Doing so ma y damage the valv es. Depending on the installation conditions, applying e xcessive torque ma y cause the nuts to crac k.
1-121 1. Specifications 4. T aping the T ubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes per mit) should be taped together with armor ing tape in 1 bundle . T o pre vent condensation from o verfl o wing the drain pan, keep the dr ain hose separate from the refrigerant tubing.
1-122 1. Specifications 1-14. LEAK TEST , EV A CU A TION AND ADDITIONAL REFRIGERANT CHARGE P erform an air-tightness test for this pac kage A/C. Check that there is no leakage from an y of the connections. Air and moisture in the refrigerant system ma y hav e undesirable eff ects as indicated below .
1-123 1. Specifications (3) Pressurize the system up to 4.15 MP a (42 kgf/cm 2 G) with dr y nitrogen gas and close the cylinder v alve when the gauge reading reaches 4.
1-124 1. Specifications CA UTION T o avoid gas fr om leaking when removing the c harge hose, make sure the stem of the gas tube is turned all the way out (“B ACK SEA T”) position. 3. Charging Additional Refrigerant Charging additional refrigerant (calculated from the liquid tube length as shown in Section "1-12.
2-1 Room T emperature Contr ol .......................................................................................... 2 -2 2-2 Cold Draft Prevention (Heating Cycle) ........................................................................ 2- 4 2-3 Automatic Fan Speed (Indoor Unit) .
2-2 2. Processes and functions Fig. 1 (THERMO. OFF) (THERMO. ON) ROOM TEMP. THERMO. ON 5 MINUTES MORE THAN 5 MINUTES 3 MINUTES SET TEMP COMPRESSOR OUTDOOR F AN (H OR M) INDOOR F AN F F O F F O F F O F F O 1 1. Refer to 2-4 Outdoor Fan Speed Control MORE THAN 3 MINUTES MORE THAN 5 MINUTES N O N O N O N O N O N O SET SPEED T+2 ° F T–2 ° F .
2-3 2. Processes and functions Fig. 2 THERMO . ON THERMO . ON +2 ° F F F O F F O 2 1. Refer to 2-4 Outdoor F an Speed Control OFF SET SPEED N O N O N O ON (REVERSING CYCLE) ON TEMP .
2-4 2. Processes and functions Fig. 3 92 88 81 77 50 SET FA N SPEED A UT O OR H M L LL LL/OFF LL L L L LL LL/OFF LL L M M LL LL/OFF LL L M H MAX. 6 MINUTES “ST ANDBY” INDICA T OR INDOOR UNIT COIL TEMP .
2-5 2. Processes and functions Fig. 4 INDOOR F AN SPEED L H MM H 1923_M_S ROOM TEMP . (deg) SET TEMP . +3 +2 +1 H M : High : Middle L: L o w Chart Explanations and notes When the f an speed changes, it keeps the speed step f or at least 3 minutes, e ven if the temperature changes to another speed step during the time.
2-6 2. Processes and functions 124 142 2- 4 Control Functions Electronic control valve control Opening of the electronic control valve is controlled so that the appropriate operating conditions are ma.
2-7 2. Processes and functions 36 (36, 48 types) Overcurrent protection control ( 1 ) If the overcurrent protection circuit detects abnormal current, the compressor is stopped.
2-8 2. Processes and functions 1 • • • • • 2 3 Defrost control Defrost sequence Heating operation (25-minute mask) F rost detection Defrost star t (rev erse cycle defrost) Defrost in progress Defrost cancel Star t-up operation Operating frequency: 61.
2-9 2. Processes and functions F an motor plug (CN004) EEPROM IC MDC Heat exchanger temper ature (C2) sensor Heat exchanger temper ature (C1) sensor Suction temperature (TS) sensor Outdoor air tempera.
2-10 2. Processes and functions Push-button switch (black): Automatic address setting switch • If the system address switch (S002: set to 0 at time of shipment) setting is other than "0" (.
2-11 2. Processes and functions 3P plug (blac k): T erminal plug for the communications line • At the time of shipment from the factory , the shor t-circuiting socket (2P , b lack) is installed between pins 1 and 2 on the terminal plug (terminal = yes).
SM830203-01_PAC-i_US-letter.indb12 12 SM830203-01_PAC-i_US-letter.indb12 12 2012/01/26 14:25:11 2012/01/26 14:25:11.
3-1 3-2 Indoor Units................................................................................................................... 3-2 Outdoor Units..................................................................................................
3-2 3. Electrical data 3-1 Indoor Units 4-Way Cassette Type : S-26PU1U6, S-36PU1U6, S-42PU1U6 SM830203-00_PAC-i_US-letter.indb2 2 SM830203-00_PAC-i_US-letter.
3-3 3. Electrical data 4-Way Cassette Type : S-26PU1U6, S-36PU1U6, S-42PU1U6 SM830203-00_PAC-i_US-letter.indb3 3 SM830203-00_PAC-i_US-letter.indb3 3 2011/11/09 20:22:53 2011/11/09 20:22:53.
3-4 3. Electrical data Wall Mounted Type : S-26PK1U6 SM830203-00_PAC-i_US-letter.indb4 4 SM830203-00_PAC-i_US-letter.indb4 4 2011/11/09 20:22:53 2011/11/09 20:22:53.
3-5 3. Electrical data Wall Mounted Type : S-26PK1U6 SM830203-00_PAC-i_US-letter.indb5 5 SM830203-00_PAC-i_US-letter.indb5 5 2011/11/09 20:22:54 2011/11/09 20:22:54.
3-6 3. Electrical data Ceiling Type : S-26PT1U6, S-36PT1U6, S-42PT1U6 SM830203-00_PAC-i_US-letter.indb6 6 SM830203-00_PAC-i_US-letter.indb6 6 2011/11/09 20:22:54 2011/11/09 20:22:54.
3-7 3. Electrical data Ceiling Type : S-26PT1U6, S-36PT1U6, S-42PT1U6 SM830203-00_PAC-i_US-letter.indb7 7 SM830203-00_PAC-i_US-letter.indb7 7 2011/11/09 20:22:54 2011/11/09 20:22:54.
3-8 3. Electrical data Low Silhouette Ducted Type : S-26PF1U6, S-36PF1U6 SM830203-00_PAC-i_US-letter.indb8 8 SM830203-00_PAC-i_US-letter.indb8 8 2011/11/09 20:22:55 2011/11/09 20:22:55.
3-9 3. Electrical data Low Silhouette Ducted Type : S-26PF1U6, S-36PF1U6 SM830203-00_PAC-i_US-letter.indb9 9 SM830203-00_PAC-i_US-letter.indb9 9 2011/11/09 20:22:55 2011/11/09 20:22:55.
3-10 3. Electrical data 3-2 Outdoor Units U-26PE1U6 SM830203-00_PAC-i_US-letter.indb10 10 SM830203-00_PAC-i_US-letter.indb10 10 2011/11/09 20:22:55 2011/11/09 20:22:55.
3-11 3. Electrical data 3-2 Outdoor Units U-26PE1U6 SM830203-00_PAC-i_US-letter.indb11 11 SM830203-00_PAC-i_US-letter.indb11 11 2011/11/09 20:22:55 2011/11/09 20:22:55.
3-12 3. Electrical data 3-2 Outdoor Units U-26PS1U6 SM830203-00_PAC-i_US-letter.indb12 12 SM830203-00_PAC-i_US-letter.indb12 12 2011/11/09 20:22:56 2011/11/09 20:22:56.
3-13 3. Electrical data 3-2 Outdoor Units U-26PS1U6 SM830203-00_PAC-i_US-letter.indb13 13 SM830203-00_PAC-i_US-letter.indb13 13 2011/11/09 20:22:56 2011/11/09 20:22:56.
3-14 3. Electrical data 3-2 Outdoor Units U-36PE1U6 SM830203-00_PAC-i_US-letter.indb14 14 SM830203-00_PAC-i_US-letter.indb14 14 2011/11/09 20:22:56 2011/11/09 20:22:56.
3-15 3. Electrical data 3-2 Outdoor Units U-36PE1U6 SM830203-00_PAC-i_US-letter.indb15 15 SM830203-00_PAC-i_US-letter.indb15 15 2011/11/09 20:22:56 2011/11/09 20:22:56.
3-16 3. Electrical data 3-2 Outdoor Units U-36PS1U6 SM830203-00_PAC-i_US-letter.indb16 16 SM830203-00_PAC-i_US-letter.indb16 16 2011/11/09 20:22:57 2011/11/09 20:22:57.
3-17 3. Electrical data 3-2 Outdoor Units U-36PS1U6 SM830203-00_PAC-i_US-letter.indb17 17 SM830203-00_PAC-i_US-letter.indb17 17 2011/11/09 20:22:57 2011/11/09 20:22:57.
3-18 3. Electrical data 3-2 Outdoor Units U-42PE1U6 SM830203-00_PAC-i_US-letter.indb18 18 SM830203-00_PAC-i_US-letter.indb18 18 2011/11/09 20:22:58 2011/11/09 20:22:58.
3-19 3. Electrical data 3-2 Outdoor Units U-42PE1U6 SM830203-00_PAC-i_US-letter.indb19 19 SM830203-00_PAC-i_US-letter.indb19 19 2011/11/09 20:22:58 2011/11/09 20:22:58.
3-20 3. Electrical data 3-2 Outdoor Units U-42PS1U6 SM830203-00_PAC-i_US-letter.indb20 20 SM830203-00_PAC-i_US-letter.indb20 20 2011/11/09 20:22:59 2011/11/09 20:22:59.
3-21 3. Electrical data 3-2 Outdoor Units U-42PS1U6 SM830203-00_PAC-i_US-letter.indb21 21 SM830203-00_PAC-i_US-letter.indb21 21 2011/11/09 20:22:59 2011/11/09 20:22:59.
SM830203-00_PAC-i_US-letter.indb22 22 SM830203-00_PAC-i_US-letter.indb22 22 2011/11/09 20:22:59 2011/11/09 20:22:59.
4-1. Meaning of Alarm Messages ......................................................................................... 4-2 4-2. Symptoms and Parts to Inspect ................................................................................... 4-5 4-3.
4-2 4. Service procedures Remote controller is detecting error signal from indoor unit E01 E02 E10 E11 E14 E03 E08 E09 E04 E05 E06 E07 E15 E12 E16 E20 E17 E18 E31 L01 L02 L03 L04 L07 L08 L09 L10 L11 L.
4-3 4. Service procedures P09 P01 P10 P03 P04 P05 P15 P19 P20 P22 P26 P29 P31 H01 F01 F02 F10 F04 F06 F07 F08 F12 F29 Ceiling panel connection failure Indoor protection Fan protectiv e ther mostat Float switch Discharge temperature trouble High pressure switch or compressor motor thermal protector is activated.
4-4 4. Service procedures (2) LED Indicator Messages on Outdoor Control PCB Power ON sequence 1. No communication from indoor units in system 2. Communication received from 1 or more indoor units in system 3. Regular communication OK (Capacity and unit quantity match) If it is not possible to advance to 3, repeats 1 → 2.
4-5 4. Service procedures 4-2. Symptoms and Parts to Inspect Judgment condition Clear condition P03 P05 P04 P15 P19 P20 P22 P26 Remote controller alarm display Alarm contents Judgment and correction Abnormal discharge temperature • Discharge temp . detected at or abov e the specified value .
4-6 4. Service procedures Judgment condition Clear condition P29 F04 F06 Alarm contents Judgment and correction Recov er y at restar t Recov er y at restar t Recov er y at restar t Recov er y at restar t Recov er y at restar t Current detection circuit trouble • AC current v alue is high ev en when compressor is stopped.
4-7 4. Service procedures Judgment condition Clear condition F31 L02 L04 L07 L10 L13 E07 E06 E14 E15 E16 E20 E31 H01 Remote controller alarm display Alarm contents Judgment and correction A utomatic recovery EEPROM troub l e Reading/writing f ailure Recov er y at power reset 1.
4-8 4. Service procedures No No No No No No No No No Ye s Ye s Ye s Ye s Ye s Ye s Ye s Ye s Ye s [Alarm “P29”] (MDC trouble) (1) Input power detection circuit troub le Compressor does not run. Breakdown Motor current detection circuit trouble Is power OK? Correct power line.
4-9 4. Service procedures No No No No No No No Ye s Ye s Ye s Ye s Ye s Ye s Ye s Replace outdoor unit control PCB. (2) [Alarm “P26”] HIC PCB trouble) IGBT short-circuit protection on inverter control (IPDU) PCB Is power OK? Correct power line . Are circuit wiring, connector connections, and reactor connections OK? Correct.
4-10 4. Service procedures HIC + Between terminals Resistance HIC + HIC + HIC + HIC – HIC – HIC – HIC – U V W U V W Resistance 200 k Ω or more 300 k Ω or more 300 k Ω or more 300 k Ω or more 200 k Ω or more 200 k Ω or more 200 k Ω or more No Ye s Replace outdoor unit control PCB.
4-11 4. Service procedures No No No No Ye s Ye s Ye s Ye s (4) [Alarm "P22"] Outdoor unit f an motor dr iv e circuit trouble Are connectors CN003 and CN004 connected correctly to the outdoor unit control PCB? Correct the connector connections.
4-12 4. Service procedures No No Ye s Ye s Check the outdoor unit control PCB. Replace if PCB has failed. Sensor trouble (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Are connecto.
4-13 4. Service procedures Sensor installation Sensor Sensor type Sensor Sensor type s s e r d d a s s e r d d a n o i t a c o l 00 Room temp. 05 – (temp . used for control)* 01 Remote controller temp. 06 Discharge temp . Indoor unit 02 Indoor intake temp.
4-14 4. Service procedures Check Pin Shor t-circuit the cooling check pin (or heating chec k pin) on the outdoor unit control PCB to perform the control described below . 1. Thermistor checks The checks listed belo w are performed for 1 second each, in order from the top do wn.
5-1. Overview ......................................................................................................................... 5 - 2 5-2. Functions ..............................................................................................
5-2 5. Outdoor unit maintenance remote control 5-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this wa y , the setting switches that were located on earlier PCBs hav e been conv er ted to EEPROM data.
5-3 5. Outdoor unit maintenance remote control Remote controller Assy Special service checker wiring Relay connector (2P , white) PCB connector (3P , blue) RC (3P , blue) Outdoor unit PCB 5-3. Normal Display Operations and Functions Normal display functions • Connect the special service checker wiring to the outdoor unit PCB.
5-4 5. Outdoor unit maintenance remote control Display (functions) • Use the temperature setting and buttons to change the item code. s k r a m e R s t n e t n o c y a l p s i D e d o c m e t I 00 (.
5-5 5. Outdoor unit maintenance remote control *2: 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as sho wn below , using the 7-segment 4-digit ( ) displa y and the colon.
5-6 5. Outdoor unit maintenance remote control 5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor T emperatures <Operating procedure> ( 1 ) Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode.
5-7 5. Outdoor unit maintenance remote control 5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History * Displa ys outdoor unit alarms only . Does not display indoor unit alarms. * Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device.
5-8 5. Outdoor unit maintenance remote control List of Item Codes r e t e m a r a P e d o c m e t I 01 Control system schedule 02 Control system schedule 03 Control system schedule 04 Snowfall sensor .
5-9 5. Outdoor unit maintenance remote control Setting mode 2 <Operating procedure> ( 1 ) Press and hold the button, button, and button simultaneously for 4 seconds or longer . ( 2 ) Use the temperature setting and buttons to change the item code .
5-10 5. Outdoor unit maintenance remote control r e t e m a r a P e d o c m e t I 80 Refrigerant type 407 = R407C 22 = R22 410 = R410A 81 Outdoor unit capacity* 0 = Disabled 80 : 26 type 112 : 36 typ .
6-1. Preparing for T est Run ............................................................................................... 6-2. Caution .................................................................................................................
6-2 6. Test run 6. TEST RUN 6-1. Preparing for T est Run Before attempting to start the air conditioner , check the following: ( 1 ) All loose matter is removed from the cabinet espe- cially steel filings, bits of wire, and clips. ( 2 ) The control wiring is correctly connected and all electrical connections are tight.
6-3 6. Test run U1, K1, T1, F1 Type 6-2. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings required for operation were made at the time of shipment.
6-4 6. Test run 6-4. Items to Check Before the Test Run (1) (2) Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater. Fully open the closed valves on the liquid tube and gas tube sides. 6-5. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer.
6-5 6. Test run Wired remote controller displa y Cause Correction Nothing is display ed Nothing is display ed E 0 1 dis play ed E 0 2 display ed E 0 9 display ed E 1 4 display ed E 0 4 display ed E 0 .
6-6 6. Test run 6-8. Examples of Wiring Diagrams Basic wiring diagram 1 Single-type system Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) 1 2 12 0 L2 U1 RC U2 L1 U2 U1 G 1 2 System address rotary switch (Set to “0” at the time of shipment.
6-7 6. Test run 1 2 12 L2 U1 RC U2 L1 U2 U1 G 1 2 12 L2 U1 RC U2 L1 U2 U1 G 1 2 System address rotary switch (Set to “ 0 ” at the time of shipment.) Outdoor unit Indoor unit Wired remote controller WHT BLK (Optional) Remote controller wiring (Field supply) System address rotary switch (Set to “ 0 ” at the time of shipment.
6-8 6. Test run Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...) ON 1 2 0 System address rotary switch (Set to “0” at time of shipment) System address rotary switch System address DIPswitch OFF ON 10s 20s 3 – 5HP Outdoorunit control PCB Fig.
6-9 6. Test run Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed.
201201 SM830203-01_PAC-i_US-letter.indb1 1 SM830203-01_PAC-i_US-letter.indb1 1 2012/01/27 13:49:35 2012/01/27 13:49:35.
Ein wichtiger Punkt beim Kauf des Geräts Panasonic R410A (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Panasonic R410A noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Panasonic R410A - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Panasonic R410A reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Panasonic R410A erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Panasonic R410A besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Panasonic R410A verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Panasonic R410A. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Panasonic R410A gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.