© Panasonic HA Air-Conditioni ng (M) Sdn. Bhd. 2010. Unauthorized copying and distribu tion is a violation of law. Order No: PHAAM1006051C3 Indoor Unit Outdoor Unit CS-C18KKS CS-C24KKS CU-C18KKS CU-C24KKS TABLE OF CONTENTS 1. Safety Pr ecautions ....
2 13. Protection C ontrol ............................................49 13.1 Restart Control (Time Delay Safety Control).. ....................................................................49 13.2 7 Minutes Time Sa ve Control .....................49 13.
3 CA UTIO N WA RN ING WA RN ING 1. Safety Precautions • Read the following “SAFET Y PRECAUTIONS” carefully bef ore perform any servicing. • Electrical work must be installed or serviced by a licens ed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installe d.
4 CA UTIO N WA RN ING 20. After completion of installation or service, confirm ther e is no leakage or refrigerant gas. It ma y generate toxic gas when the refriger ant contacts with fire. 21. Ventilate if there is refrigerant gas leakage during operation.
5 2. S pecification Indoor CS-C18KKS CS-C24KKS Model Outdoor CU-C18KKS CU-C24KKS Performance Test Condition SASO (T3) SASO (T1) SASO (T3) SASO (T1) Phase, Hz Single, 60 Single, 60 Power Supply V 220 220 kW 4.40 5.10 5.60 6.50 BTU/h 15000 17400 19100 22200 Capacity kcal/h 3780 4390 4820 5590 Running Current A 9.
6 Control Device Capillary tube Capillary tube Refrigerant Oil cm 3 ATMOS NM56M or SUNISO 4GDI D (650 ) ATMOS M60 or SUNISO 4GDID (1130) Refrigeration Cycle Refrigerant Type g (oz) R22, 1.
7 3. Features • E-ion Air Purifying System with Patrol Sensor o Active e-ions are released to catch du st particles and bring them back the la rge positively charged filter. o Patrol Sensor color changes to indicate the dirt level in the air • Long Installation Piping o CS/CU-C18KK, CS/CU-C24KK, long pip ing up to 25 meters.
8 4. Location of Controls and Components 4.1 Indoor Unit 4.2 Outdoor Unit 4.3 Remote Control.
9 5. Dimensions 5.1 Indoor Unit.
10 5.2 Outdoor Unit.
11 6. Refrigeration Cycle Diagram INDOOR OUTDOOR LIQUID SIDE GAS SIDE CAPILLARY TUBE HEA T EXCHANGER (CONDENSER) THERMOST A T (C24KK only) HEA T EXCHANGER (EV APORA TO R) COMPRESSOR 2-W A Y VA LV E PIPE TEMP .
12 7. Block Diagram.
13 8. Wiring Connection Diagram 8.1 CS-C18KKS CU-C18KKS Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-C18KKS MODEL CU-C18KKS CONNECTION CWA951401J CONNECTION 2KS252F5AA04 BLUE-YELLOW 59.47 Ω C-R 1.959 Ω YELLOW-RED 60.
14 8.2 CS-C24KKS CU-C24KKS Resistance of Outdoor Fan Motor Windings Resistance of Compressor Windings MODEL CU-C24KKS MODEL CU-C2 4KKS CONNECTION CWA951399J CONNECTI ON 2J39S236A1A YELLOW-BLUE 59.47 Ω C-R 0.933 Ω YELLOW-ORANGE 80.58 Ω C-S 1.584 Ω YELLOW-RED 60.
15 9. Electronic Circuit Diagram 9.1 CS-C18KKS CU-C18KKS.
16 9.2 CS-C24KKS CU-C24KKS.
17 10. Printed Circuit Board 10.1 Indoor Unit 10.1.1 Main Printed Circuit Board.
18 10.1.2 Power Printed Circuit Board.
19 10.1.3 Indicator Prin ted Circuit Board 10.1.4 Receiver Printed Circuit Board 10.1.5 High Voltage Power S upply Printed Circuit Board.
20 11. Inst allation Instruction 11.1 Select the Best Location 11.1.1 Indoor Unit • Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. • There should not be any heat source or steam near the unit. • There should not be any ob stacles bl ocking the air circulation.
21 11.2 Indoor Unit 11.2.1 How to Fix In stallation Plate The mounting wall shall be stron g and solid enough to prevent if from the vibration. The centre of installation plate sho uld be at more than c at right and left of the wall. The distance from installation plate edge to ceiling sho uld more than d .
22 11.2.3 Indoor Unit Installation Piping P iping Intak e gri l le Shock absor ber Use sho ck ab so rbe r du ring pu ll ou t t h ep i p i n gt op r o t e c t t h ei n t a k eg r i l l e fr o m d am a g e. Do not t ur n ov er the un i t wit hou t it ’ s sho ck abs or be r dur ing pull ou t t he piping.
23 11.2.4 Connect the Cable to the Indoor Unit 1. The inside and outside con necting cable can be connected without remo ving the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathe d 3 x 2.
24 11.2.5 Wire Stripping And Connecting Requirement 11.2.5.1 Cutting and flaring the piping 1 Please cut using pipe cutter and then re move the burrs. 2 Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused. Turn the pipi ng end down to avoid the metal powder entering the pipe .
25 CA UTIO N 11.3 Outdoor Unit 11.3.1 Install the Outdoor Unit • After selecting the best lo cation, start installa tion to Indoor/Outdoor Unit Installation Dia gram. 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10mm ).
26 11.3.3 Evacuation of the Equipment FOR ENVIRONMENTAL PROTECTION, MANUFACTURER ST RONGLY RECOMMENDS TO USE EVACUATION METHOD. 1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. o Be sure to connect the end of the chargi ng hose with the push pin to the service port.
27 11.3.4 Air Purging of the Piping and Indoor The remaining air in the Refrigerant cycle whi ch contains moisture may cau se malfunction on the compressor. 1 Remove the caps from the 2-way and 3-way valves. 2 Remove the service-port cap from the 3-way valves.
28 11.3.6 Pipe Insulation 1 Please carry out insulation at pipe con nection port ion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insul ated piping end to prevent water from going inside the piping.
29 12. Operation Control 12.1 Cooling Operation • Cooling operation can be set usi ng remote control. • This operation is applied to cool down the roo m temper ature to the setting temperature set on the remote control.
30 12.2 Soft Dry Operation • Soft Dry operation can be set using rem ote control. • Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room. • This operation starts when the intake air temperatur e sensor reaches the setting temperature on the remote control.
31 12.3 Automatic Operation • Automatic operation can be set using re mote control. • This operation starts to operate with in door fan at SL o speed for 20 seconds to judge the inta ke air temperature. • After judged the temperature, the operat ion mode is determined by referring to the below standard.
32 12.4 Indoor Fan Speed Control • Indoor fan speed can be set using remote control. 12.4.1 Fan Speed Rotation Chart Fan Speed (rpm) Speed CS-C18KKS CS-C24KKS Shi 1370 1500 Hi 1200 1350 Me 1110 1230 HLo 1080 1190 CLo 1020 1110 Lo- 850 970 SLo 670 750 Qhi 1110 1150 QMe 1020 1050 QLo 930 960 12.
33 • Auto Fan Speed during coo ling operation: 1 Indoor fan will rotate alternately between off and on a s shown in below diagram. 2 At the beginning of each compressor starts operation, indoo r fan speed increases gradually for deodori zing purpose.
34 12.5 Outdoor Fan Speed Control • There is only one speed for outdoor fan motor. (Applicabl e for CU-C18KK) • There is 2 speeds for outdoor fan motor. Outdoor fan spe ed can be changed to Hi or Lo acco rding to outdoor temperature. (Applicable for CU-C24KK).
35 12.7 Horizontal Airflow Direction Control 12.7.1 Auto Control • When the horizontal airflow is set to Auto using the re mote control, the vanes swings left and ri ght as shown in the diagram. • When stopped with remote control, the dischar ge vanes are reset and stop at the reset positio n.
36 12.9 Quiet Operation (For Cooling Operation or cooling re gion of Soft Dry Operation) • To provide quiet cooling operation condition. • Once the Quiet Operation is set at the remote cont rol, the Quiet LED illuminated.
37 12.10 Timer Control 12.10.1 ON Timer • When the ON Timer is set by using the remote control, t he unit will start to operate sli ghtly before the set time, so that the room will reach nearly to the set temperature by the set time. • For Cooling and Soft Dry operation, the operat ion will start 15 minutes befo re the set time.
38 12.13 Patrol Operation • To monitor air dirtiness level by using Patrol se nsor a nd to maintain air freshness by activates e-ion operation • Patrol operation starts condition o When the unit operation is started with “OFF/ON” button o When the unit stops, “Patrol” operatio n is se lected, Patrol individual operation will start.
39 • Patrol Sensor Control o First 2 minutes from Patrol function activates is st abilization time, during stabilization time, no air dirtin ess level is monitored. The Air Dirtiness leve l is set to Clean, Patrol LED turns blue color. o After that, Patrol sensor starts to record the resist ance value at fixed interval.
40 • Airflow direction (Horizontal, Vertical) Control o During any operation mod e combines with Patrol ope ration, airflow direction follows respective operation mode. o During Patrol individual ope ration if e-ion starts, only Au to Air Swing is allowed.
41 • Patrol Operation Demo Mode o Patrol Operation Dem o Mode start condition Press “Set” button contin uously for 15 seconds by using pointer during Air Conditioner is OFF condition to enter internal setting mode. Press “Timer De crement" button to select “Pt demo”.
42 12.14 E-ion operation • This operation provides clean air by p roducing negative ions to attract dust capt ured at the positively charged active e-ion filters. • e-ion operation start condition o During unit running at any operation mo de, if “e-ion” operation is selected, combination operation (operation mode + e-ion operation) starts.
43 • e-ion Check Mode o e-ion abnormality check mode o Purpose is to improve sensor servic eability when sensor is malfu nction. (1) Control starting condition When all of the conditions are formed Not in Patrol Demo mode. e-ion operation ON.
44 • Error Detection Co ntrol When e-ion indicator blink, it indicates erro r listed below: o Active e-ion Air Purifying system PCB main conne ctor open: Judgment Method • During e-ion operation (include during Patrol ope rati on), Active e-ion Air Purifying system main connector to PCB is opened.
45 12.15 ECO Patrol Operation • A Pyoelectric infrared sensor is used to detect injectio n strength variation of infrared at setting area to determine the presence or absence of human and its activity level.
46 • ECO Patrol Demo Mode Press “Set” button contin uously for 15 seconds by using pointer during Air Conditioner is OFF condition to enter internal setting mode. Press “Timer De crement" button to select “EC demo”. Press “Timer Set” button to toggle ECO Patrol Demo mode.
47 • During ECO Patrol operation, the internal setting tem per ature and fan speed are adjuste d in order to provide comfort and energy saving. • ECO Patrol Start condition. Press ECO Patrol button to select ECO1 and ECO2. • ECO Patrol Stop condition.
48 • ECO Patrol Sensor abnormality check mode • Purpose is to improve sensor se rvic eability when sensor is malfunction. (1) Control starting condition When all of the conditions are formed Not in ECO Patrol Demo m ode. ECO Patrol mode ON.
49 13. Protection Control 13.1 Restart Control (Time Delay Safety Control) • When the thermo-off temperature (temperature whic h comp ressor stops to operate) is reach durin g:- o Cooling operation – the co mpressor stops for 3 minutes (minimum ) before resume operation.
50 Compressor starts for ≥ 5 minutes ▲ T ≤ 2.5°C for 2 minutes Compressor OFF Compressor restart ▲ T = Intake air temperature – Indoor heat excha nger temperature 13.5 Freeze Prevention Control • To protect indoor heat exchanger from freezi ng and to prevent higher volume of refrigerant in liquid form return to compressor.
51 14. Servicing Mode 14.1 Auto OFF/ON Button Auto OFF/ON Button Pressed A uto OFF/ON Button Pressed Auto OFF/ON Button Pressed 5 sec 5 sec Auto Operation Test Run Operation (Forced Cooling Operation) Stop Various Setting Mode Stop 1 AUTO OPERATION MODE The Auto Operation will be activated immediately once the Auto OFF/ON button is pressed.
52 14.2 Remote Control Button 14.2.1 SET Button • To check current remote cont rol transmission code and store the transmi ssion code to EEPROM: o Press “Set” button for more than 10 second s o Press “Timer Set” button u ntil a “beep” sound is heard as confirmati on of transmission code change.
53 15. T roubleshooting Guide 15.1 Refrigeration cycle system In order to diagnose malfunctions, ensu re the air conditioner is free from electrical problems bef ore inspecting the refrigeration cycle. Such problems include in sufficient insulation, problem with the power source, malfunction of a compressor a nd a fan.
54 15.1.1 Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Condition of the air conditioner Low Pressure High Pressure Electric current during o.
55 WA RN ING 16. Disassembly and Assembly Instructions High Voltage is generated in the electrical parts area by the capacitor. Ensure that t he capac itor has discharged sufficiently before proceeding with repair work. Failure to heed this cauti on may result in electric shocks.
56 16.1.3 To remove power electronic controller Figure 3 Figure 4 Figure 5 Figure 6.
57 16.1.4 To remove discharge grille Figure 7 16.1.5 To remove control board Figure 8 16.1.6 To remove cross flow fan and indoor fan motor Figure 9.
58 Figure 10 Figure 11 Figure 12.
59 17. T echnical Data 17.1 Operation Characteristics 17.1.1 CS-C18KKS CU-C18KKS • Cooling Characteristic o Room temperature: 27°C (DBT), 19°C (WBT) o Operation condition: High fan speed o Piping length: 5.
60 • Piping Length Characteristic o Outdoor temperature: 35°C (DBT), 24°C (WBT) o Operation condition: High fan speed o Piping length: 5.0m Current (A ) Gas Side Piping Pressure (MPa) Capa city (kW) Outlet Air (º C ) 22 0V Pi ping L ength (m) 22 0V Pi ping L ength (m) Pi ping L ength (m) 22 0V Pi ping Len gth (m) 22 0V 14.
61 17.1.2 CS-C24KKS CU-C24KKS • Cooling Characteristic o Room temperature: 27°C (DBT), 19°C (WBT) o Operation condition: High fan speed o Piping length: 5.
62 • Piping Length Characteristic o Outdoor temperature: 35°C (DBT), 24°C (WBT) o Operation condition: High fan speed o Piping length: 5.0m Current (A ) Gas Side Piping Pressure (MPa) Capa city (k.
63 18. Exploded View and Replacement Part s List 18.1 Indoor Unit Note The above exploded view is for the purp os e of parts disassembly and replaceme nt.
64 REF. NO. PART NAME & DESCRIPTION QTY CS-C18KKS CS-C24KKS REMARK 1 CHASSY COMPLETE 1 CWD50C1654 ← 2 FAN MOTOR 1 L6CBYYYL0037 L6CBYYYL0039 O 3 CROSS FLOW FAN COMPLETE 1 CWH02C1077 ← 4 BEARING.
65 50 DRAIN HOSE 1 CWH851173 ← 51 BAG COMPLETE - INSTALLATI ON SCREW 1 CWH82C1705 ← 52 INSTALLATION PLATE 1 CWH361098 ← 53 FULCRUM 2 CWH621103 ← 54 OPERATING INSTRUCTION 1 CWF567115 ← 55 INS.
66 18.2 Outdoor Unit Note The above exploded view is for the purp os e of parts disassembly and replaceme nt. The non-numbered pa rts are not kept as standard service parts.
67 REF. NO. PART N A ME & DESCRIPTION QTY CU-C18KKS CU-C24KKS REMARK 1 CHASSY ASS’Y 1 CWD50K2115 CWD50K2100 2 SOUND PROOF MATERIAL 2 CWG302408 ← 3 FAN MOTOR BRACKET 1 CWD541065 ← 4 SCREW - F.
Ein wichtiger Punkt beim Kauf des Geräts Panasonic CU-C18KKS (oder sogar vor seinem Kauf) ist das durchlesen seiner Bedienungsanleitung. Dies sollten wir wegen ein paar einfacher Gründe machen:
Wenn Sie Panasonic CU-C18KKS noch nicht gekauft haben, ist jetzt ein guter Moment, um sich mit den grundliegenden Daten des Produkts bekannt zu machen. Schauen Sie zuerst die ersten Seiten der Anleitung durch, die Sie oben finden. Dort finden Sie die wichtigsten technischen Daten für Panasonic CU-C18KKS - auf diese Weise prüfen Sie, ob das Gerät Ihren Wünschen entspricht. Wenn Sie tiefer in die Benutzeranleitung von Panasonic CU-C18KKS reinschauen, lernen Sie alle zugänglichen Produktfunktionen kennen, sowie erhalten Informationen über die Nutzung. Die Informationen, die Sie über Panasonic CU-C18KKS erhalten, werden Ihnen bestimmt bei der Kaufentscheidung helfen.
Wenn Sie aber schon Panasonic CU-C18KKS besitzen, und noch keine Gelegenheit dazu hatten, die Bedienungsanleitung zu lesen, sollten Sie es aufgrund der oben beschriebenen Gründe machen. Sie erfahren dann, ob Sie die zugänglichen Funktionen richtig genutzt haben, aber auch, ob Sie keine Fehler begangen haben, die den Nutzungszeitraum von Panasonic CU-C18KKS verkürzen könnten.
Jedoch ist die eine der wichtigsten Rollen, die eine Bedienungsanleitung für den Nutzer spielt, die Hilfe bei der Lösung von Problemen mit Panasonic CU-C18KKS. Sie finden dort fast immer Troubleshooting, also die am häufigsten auftauchenden Störungen und Mängel bei Panasonic CU-C18KKS gemeinsam mit Hinweisen bezüglich der Arten ihrer Lösung. Sogar wenn es Ihnen nicht gelingen sollte das Problem alleine zu bewältigen, die Anleitung zeigt Ihnen die weitere Vorgehensweise – den Kontakt zur Kundenberatung oder dem naheliegenden Service.